COMMENTS ON 33Kv & 6.6Kv ISOLATOR

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

ANNEXURE – I

LIST OF COMMON COMMENTS ON 33kV & 6.6kV LOAD BREAK SWITCH

Project drawing no shall be furnished for each drawing sheet.

Paint shade 632 as per IS-5 shall be provided as finish paint.

Isolator shall have padlocking facility in ON & OFF condition.

Isolator advance contact auxiliary switch shall be provided for tripping up-
stream HT breaker.

Specify the contact no. going to the HT switchgear. Advance contact for
HT breaker trip & isolator ON for close permissive.

Auxiliary contact shall have minimum 3NO + 3NC contact. There seem to
have some discrepancy between no. of auxiliary contact appearing in the
drawing & bill of material. The same shall be clarified.

LT HRC fuse rating appearing in the drawing & BOM are contradictory.
The same shall be clarified.

For 33kV isolator panel, party shall confirm that incoming & outgoing
gland plate shall be suitable for the termination of 33kV, 3 x (3C x 300)
sq.mm, Aluminum cable.

33kV bus support insulator voltage level shall be considered as 36kV


minimum. Type of material for 33kV bus support insulator shall be
furnished.

6.6kV bus support insulator voltage level shall be considered as 7.2kV


minimum. Type of material for 6.6kV bus support insulator shall be
furnished.

Bushing shall have minimum creepage distance of 25mm/kV.

Earth switch ON & OFF mechanical indication shall be provided.

Load bearing member shall be 2.5mm thick & non-load bearing shall be
2.0mm thick. Gland plate shall be 3.0mm thick.

PVC insulated flexible multi-strand 1100V grade Cu. 2.5sq.mm grey


colored for control circuit shall be provided.

Bus bar shall be insulated with color coded heat shrinkable PVC sleeve.

Party shall clearly indicate in the foundation drawing the cut-out size for
power & control cable.
Panel dimension shall be included in “NOTE”.

Sufficient nos. of cable support structure for both incoming & outgoing
cable chamber shall be provided.

The bus bar size indicated in the drawing seems to be inadequate. Party
shall clarify the bus bar size chosen for particular bus bar rating for both
33kV & 6.6kV isolators.