Professional Documents
Culture Documents
N-10012-4-OPM-1501-0 Operation and Maintenance Manual Evaporation Section PDF
N-10012-4-OPM-1501-0 Operation and Maintenance Manual Evaporation Section PDF
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
DISCLAIMER:
The purpose of the operation and maintenance manual (O & M manual) is to establish general
guidelines for the safe and proper use and maintenance of the Process Plant (as defined in the Supply
Agreement executed between the recipient and Praj Industries Limited) supplied by Praj Industries
Limited (PIL). These instructions are submitted with the implicit understanding that:
a) They are a guide to the recipient for the operation and maintenance of the Process Plant for efficient
operation.
b) The recipient has assigned skilled & competent maintenance and operating personnel for the
functioning of the Process Plant described herein.
c) The recipient has read, understood and thoroughly examined the aforesaid instructions prior to abiding
with the requirements.
The information contained in the O & M manual is confidential, and is meant solely for the use of the
recipient only and is not for circulation. This document is not to be reported or copied or made
available to others. The information contained herein is based on:
The operating parameters and auxiliary / utility consumption mentioned in the O&M manual are to be
used as guidelines only and the same may change during Process Plant stabilisation as well as due to
change in input specification. PIL is not liable for any operational hazards or injuries caused to
anybody on account of the use of the processes mentioned in the O & M manual. During the warranty
period Praj Industries Limited shall not be liable for any claims, losses, and damages arising out of the
use of the Process Plants by the recipient on account of non-compliance with the terms of this O & M
manual.
The recipient shall comply with all applicable laws while using the Process Plants with respect to which
this operation and maintenance manual is provided.
Start-up assistance or field engineering service provided by PIL during the pre commissioning and
commissioning period or thereafter on the request of the recipient shall in no way relieve the recipient
of the responsibility for the proper maintenance and use of the Process Plant.
PIL reserves the right to alter, amend and / or modify the operation and maintenance manuals from
time to time.
In no event shall PIL be liable for any damages and /or liabilities on account of any indirect, incidental,
special, consequential or any other similar losses.
The information incorporated in the O & M manual is subject to copyright and must not be used,
disseminated, copied or disclosed to third parties without the written consent of PIL.
If you are not the intended recipient you should forthwith destroy all copies and inform PIL at
info@praj.net.
© Praj Industries Limited All Rights Reserved Registered Office: Praj Industries Limited, `Praj House',
Bavdhan, Pune- 411021 Maharashtra, India.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
TABLE OF CONTENT
1.0 INTRODUCTION 07
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
TABLE OF CONTENT
3.0.4 a SOP for Preparation of 3-5 % w/w Nitric acid solution in CIP 95
Tank T-1506
3.0.4 b SOP for Preparation of 3-5 % w/w caustic solution in CIP Tank 96
T-1351
3.0.4 e SOP for CIP of Falling Film Effect – III (H-1503) 102
3.0.4 f SOP for CIP of Falling Film Standby Effect (H-1504) 104
3.0.4 i SOP for CIP of Forced Circulation Standby Effect (H-1507) 110
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
TABLE OF CONTENT
4.1 Plant Short Shutdown & Start-up after Short Shutdown 138
4.2 Plant Long Duration Shutdown & Start-up after Long 143
Duration Shutdown
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
PART–I
THEORETICAL ASPECTS
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1.0 INTRODUCTION
All data and information submitted here in regarding design details, operation
system, processing techniques should not be divulged to others without the written
consent from PRAJ INDUSTRIES LIMITED, INDIA. Here after PRAJ INDUSTRIES
LIMITED, INDIA shall be called as PIL.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
As per of the contract, all chemicals, feedstock and utilities shall be made available by
VICENTIN S.A.I.C. AVELLANEDA, SANTA FE - ARGENTINA and shall ensure
readiness for completion of mechanical work as detailed out in contract.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
All steam heated evaporator bodies, no matter what their configuration, have the
following standard components –
HEAT EXCHANGER - contains tubes, tube sheets, and shell enclosing the tubes along
with tube sheets.
MIST ELIMINATOR - serves to remove fine, small particles of liquid from vapours
released from vapour liquid separator.
VAPOR PIPE - direct released vapours from vapour liquid separator to condenser.
RECIRCULATION PIPE - recirculation piping transfer the liquid from vapour liquid
separator to heat exchanger.
RECIRCULATION PUMP - recirculation pump transfer the liquid from vapour liquid
separator to heat exchanger.
CONDENSATE PIPE - outlet piping removes condensate from the heating element
shell to a condensate tank, thus removing the condensate from the evaporator system.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
VAPOR INLET
HEAT
EXCHANGER
SHELL
SECTION
NON-CONDENSIBLE
GAS OUTLET
CONDENSATE
VAPOR OUTLET OUTLET
VAPOR-LIQUID
SEPARATOR
(VLS)
FEED INLET
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Vapor Out
Steam / Vapour in
Concensate Out
Feed In
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
The heating element is provided with a non-condensable vent gas outlet connection. One
non-condensable gas vent is located near the top of the shell section and one non-
condensable gas vent is located near the bottom of the shell section. These locations
along with the internal tube support baffle arrangement allows for the vapours to be
directed through the total length of the tube bundle.
DISTRIBUTION BOX
The top main liquid box of the falling film evaporator bodies is an extension of the heater
shell above the top tube sheet. The top liquid box contains the spray shower distribution
nozzles which are located above the top tube sheet to provide even distribution of liquid
to all of the tubes. The top liquid box contains four (4) spray shower distributor nozzles.
The large volume of circulating Thin Stillage causes a liquid level to build on the plate
which serves to provide an even flow of Thin Stillage to all of the tubes.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Vapor Out
Mist Eliminator
Feed In
Recirculation In
Recirculation Out
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
MIST ELIMINATOR
After the larger liquid particles fall out of the vapour, a "polishing" device, called a Mist
eliminator is used to remove the smaller particles from the vapour. These smaller liquid
particles can resemble a mist or a fog. A wire mesh type mist eliminator is provided in
the upper section of the vapour body to remove the smaller liquid particles. A wire mesh
type mist eliminator uses both impingement and change of direction to provide
extremely low pressure drops. This type is designed for vertical vapour flow and is of
the self-draining type.
Vapor
Flow
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
GENERAL
The Evaporation plant is designed to operate with three Cases
Case-I – Feedstock Corn.
Case II – Feedstock Sorghum without Tannin with Recycle of Thin Stillage.
Case III – Feedstock Sorghum with Tannin without Recycle of Thin Stillage.
In order to have energy saving, there is thermal integration of Evaporation section with
Mash Column (C-1401) in Distillation section.
The Evaporation plant consists of two sections. The First section consist of three effect
Falling Film Evaporators operating on principle of multi-effect evaporation. One
common standby evaporator is also provided to have continuous operation of the plant
during cleaning in place (CIP) of any Falling Film evaporator. Hence at any time three
evaporator bodies will be in operation.
The position of the Falling Film evaporator in multiple effect system is mentioned in
below table.
Mode of
Under CIP First Effect Second Effect Third Effect
Operation
Mode A H-1501 H-1502 H-1503 H-1504
Mode B H-1502 H-1501 H-1503 H-1504
Mode C H-1503 H-1501 H-1502 H-1504
Mode D H-1504 H-1501 H-1502 H-1503
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Thus H-1501 will always act as First Effect whenever in operation, Falling Film Effect
– II (H-1502) can operate as First Effect or Second effect, Falling Film Effect – III (H-
1503) can operate as Second effect or Third effect, and Falling Film Standby Effect (H-
1504) will always operate as Third effect.
The Second section consists of two effect Forced Circulation evaporators operating on
principle of multi-effect evaporation. One common standby evaporator is also provided
to have continuous operation of the plant during cleaning in place (CIP) of any Forced
Circulation evaporator. Hence at any time two evaporator bodies will be in operation.
Second Section will be operative only with Case II and Case III with sorghum as feed
stock.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Thin Stillage vapors generated in Falling Film Effect - III will be condensed in Surface
Condenser (H-1508). Concentrated Syrup (34.00% w/w to 35.00% w/w) will be send to
Concentrated Syrup Tank (T-1505).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
be used for preheating the Treated Process Condensate in Treated Process Condensate
Preheater (H-1510) and then will be sent to Process Condensate Treatment Plant.
Necessary vacuum required will be generated by Water Ring Vacuum Pump (P-
1513A/B). Concentrated Syrup from Falling Film Effect - III will be collected in
Concentrated Syrup Tank (T-1505) and then will be sent for storage.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Concentrated Thin Stillage from Falling Film Effect - I will be fed to Falling Film Effect -
II. Thin Stillage vapors generated in Falling Film Effect - II will be used as heating source
for Falling Film Effect - III. Partially Concentrated Syrup from Falling Film Effect - II will
be fed to the Falling Film Effect - III.
Thin Stillage vapors generated in Falling Film Effect - III will be partially used as a heat
source for Mash Column (C-1401) in Distillation Section and remaining vapors will be
condensed in Process Condenser (H-1511). And partially Concentrated Syrup (29.00%
w/w to 30.00% w/w) will be fed to the second section.
Partially Concentrated Syrup will be fed to Forced Circulation Effect –II where it will be
concentrated up to 35% w/w. Steam condensate generated will be collected in Steam
Condensate Tank (T-1504). After that it will be recycled to boiler section after preheating
Thin Stillage in Thin Stillage Preheater (H-1509A/B).
Thin Stillage Vapors generated in Forced Circulation Effect –II will be totally condensed
in Surface Condenser (H-1508). Process condensate generated from Surface
Condenser(H-1508), Process Condenser (H-1511) and Forced Circulation Effect –II of
second section will be collected in Process Condensate Tank – 2 (T-1503) and will be
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Necessary vacuum required will be generated by Water Ring Vacuum Pump (P-
1513A/B). Concentrated Syrup from Forced Circulation Effect –II will be collected in
Concentrated Syrup Tank (T-1505) and then will be sent for storage.
C) Case III – Feedstock Sorghum with Tannin without Recycle of Thin Stillage.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Falling Film Effect - I. Steam condensate from shell of Falling Film Effect - I will be
collected in Steam Condensate Tank (T-1504). Thin Stillage vapors generated from
Falling Film Effect - I will be used as heating source for Falling Film Effect - II. Partially
Concentrated Syrup from Falling Film Effect - I will be fed to Falling Film Effect - II. Thin
Stillage vapors generated in Falling Film Effect - II will be used as heating source for
Falling Film Effect - III. Partially Concentrated Syrup from Falling Film Effect - II will be
fed to the Falling Film Effect - III.
Thin Stillage vapors generated in Falling Film Effect - III will be partially used as a heat
source for Mash Column (C-1401) in Distillation section and remaining vapors will be
condensed in Process Condenser (H-1511). And partially Concentrated Syrup (29.00%
w/w to 30.00% w/w) will be fed to the second section.
Partially Concentrated Syrup will be fed to Forced Circulation Effect -II where it will be
concentrated up to 35% w/w. Steam condensate generated will be collected in Steam
Condensate Tank (T-1504). After that it will be recycled to boiler section after preheating
Thin Stillage in Thin Stillage Preheater (H-1509A/B).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Thin Stillage Vapors generated in Forced Circulation Effect -II will be totally condensed
in Surface Condenser (H-1508). Process condensate generated from Surface Condenser
(H-1508), Process Condenser (H-1511) and Forced Circulation Effect –II of second section
will be collected in Process Condensate Tank – 2 (T-1503) and will be transferred to
Process Condensate Tank -1 (T-1502). Similarly Process Condensate generated from
Falling Film Effect – II and Falling Film Effect - III will be collected in Process
Condensate Tank – 1 (T-1502). This Process Condensate will be used for preheating the
Treated Process Condensate in Treated Process Condensate Preheater (H-1510) and then
will be sent to Process Condensate Treatment Plant.
Necessary vacuum required will be generated by Water Ring Vacuum Pump (P-
1513A/B). Concentrated Syrup from Forced Circulation Effect -II will be collected in
Concentrated Syrup Tank (T-1505) and then will be sent for storage.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
concentrated Thin Stillage is transferred to Vapor Liquid Separator for FF Effect – III (V-
1503) based on liquid level control and recirculated through Recirculation Pump for FF
Effect – III (P-1503).
In Sorghum case, Vapours generated in Falling Film effect –II will be used as heating
media for Falling Film Effect – III.
In Corn case, Vapors generated in Falling Film effect –II will be used partially as
heating media for Mash Column in Distillation section and Falling Film Effect – III.
Level of Vapor Liquid Separator for FF Effect – II (V-1502) is controlled by level
indicator and controller LIC-150201 through level control valve (LCV-150201).
P&ID No.: N-10012-1-P&ID1503: P&I DIAGRAM FOR FALLING FILM EFFECT -III
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
in Falling Film Standby Effect (H-1504) will be condensed in Surface Condenser (H-
1508). Level of Vapor Liquid Separator for FF Standby Effect (V-1504) is controlled by
level indicator and controller LIC-150401 through level control valve (LCV-150401).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
The density of concentrated syrup is controlled by density indicator and controller DIC-
150601 based on the control logic selection. The density controller (DIC-15601) is in
cascade with low pressure steam flow totaliser indicator controller FQIC-150501 and
FQIC-150901, which ultimately control the concentration of Concentrated Syrup.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
In Corn Case, Thin Stillage Vapors from Falling Film Effect – III (H-1503) or Falling
Film Standby Effect (H-1504) are condensed in Surface Condenser (H-1508).
Evaporation condensate from Falling Film Effect – II (H-1502), Falling Film Effect – III
(H-1503) & Falling Film standby Effect (H-1504) is collected in Process Condensate
Tank - 1 (T-1502).
Evaporation Condensate from Forced Circulation Effect – II (H-1506) & Forced
Circulation Standby Effect (H-1507), Surface Condenser (H-1508) and Process
Condenser (H-1511) is collected in Process Condensate Tank – 2 (T-1503). Level of
Process Condensate Tank – 2 (T-1503) is controlled by level indicator and controller
LIC-150801 through level control valve (LCV-150801). The process condensate from
Process Condensate Tank – 2 (T-1503) is transferred to Process Condensate Tank – 1
(T-1502) based on liquid level control through Flow Totalizer and Indicator (FQI-
150801).
Necessary vacuum required will be generated by Water Ring Vacuum Pump (P-
1513A/B). The required vacuum is controlled by pressure indicator and controller
PIC-150801 through pressure control valve (PCV-150801).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
transferred through Steam Condensate Pump (P-1511) and used to preheat Thin
Stillage in Thin Stillage Preheater (H-1509A/B).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Concentrated Nitric Acid solution is to be prepared in CIP Tank (T-1506) and will be
transferred by CIP Transfer Pump (P-1515) to the effect under CIP. Measured quantity of
Concentrated Nitric Acid is to be taken in CIP Tank (T-1506) through FQI - 151201.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
QUANTITY
TAG NO. DESCRIPTION TECHNICAL DETAILS
OP. S/B.
Type: Cylindrical /
vertical shell with
K-1502 Condensate Pot – 2 1 0 Dished ends
Capacity : 0.37 m3
N-
Spray Nozzle For FF Effect - I 2 0 Full cone spray
1501A/B
N-
Spray Nozzle For FF Effect - II 2 0 Full cone spray
1502A/B
N-1503
Spray Nozzle For FF Effect - III 4 0 Full cone spray
A/B/C/D
N-1504 Spray Nozzle For FF Standby
0 4 Full cone spray
A/B/C/D Effect
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
QUANTITY
TAG NO. DESCRIPTION TECHNICAL DETAILS
OP. S/B.
Recirculation Pump for FC Type: Centrifugal Pump
P-1506 1 0
Effect - II with Motor Capacity :250 m3/hr
Recirculation Pump for FC Type: Centrifugal Pump
P-1507 0 1
Standby Effect with Motor Capacity :250 m3/hr
Thin Stillage Feed Pump with Type: Centrifugal Pump
P-1508A/B 1 1
Motor Capacity :51 m3/hr
Process Condensate Pump – 1 Type: Centrifugal Pump
P-1509 1 0
with Motor Capacity :35 m3/hr
Process Condensate Pump – 2 Type: Centrifugal Pump
P-1510 1 0
with Motor Capacity :5 m3/hr
Steam Condensate Pump with Type: Centrifugal Pump
P-1511 1 0
Motor with Motor Capacity :20 m3/hr
Concentrated Syrup Transfer Type: Centrifugal Pump
P-1512 1 0
Pump with Motor Capacity :12 m3/hr
Evaporation Vacuum Pump Water Ring Vacuum
P-1513A/B 1 1
with Motor Pump
Concentrated Syrup Pump with Type: Centrifugal Pump
P-1514A/B 1 1
Motor Capacity :12 m3/hr
Type: Centrifugal Pump
P-1515 CIP Transfer Pump with Motor 1 0
Capacity :35 m3/hr
Type: Centrifugal Pump
P-1516 CIP Drain Pump with Motor 1 0
Capacity :35 m3/hr
Type: Cylindrical /
Vertical Shell with
T-1501 Thin Stillage Feed Tank 1 0 Conical Top & Slopping
Bottom.
Capacity : 30 m3
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
QUANTITY
TAG NO. DESCRIPTION TECHNICAL DETAILS
OP. S/B.
Type: Cylindrical /
Horizontal Shell with
T-1502 Process Condensate Tank – 1 1 0 Dished Ends
Capacity : 5 m3
Type: Cylindrical /
Horizontal Shell with
T-1503 Process Condensate Tank – 2 1 0 Dished Ends
Capacity : 3 m3
Type: Cylindrical /
Horizontal Shell with
T-1504 Steam Condensate Tank 1 0
Dished Ends
Capacity : 3 m3
Type: Cylindrical /
Vertical Shell with
T-1505 Concentrated Syrup Tank 1 0
Dished Ends
Capacity : 2 m3
Type: Cylindrical /
Vertical Shell with
T-1506 CIP Tank 1 0 Dished Ends.
Capacity: 15 m3
Type: Cylindrical /
Vertical Shell with
Vapor Liquid Separator for FF
V-1501 1 0 Conical Top & Dished
Effect - I
Bottom.
Capacity : 35 m3
Type: Cylindrical /
Vertical Shell with
Vapor Liquid Separator for FF Conical Top & Dished
V-1502 1 0
Effect - II Bottom.
Capacity : 35 m3
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
QUANTITY
TAG NO. DESCRIPTION TECHNICAL DETAILS
OP. S/B.
Type: Cylindrical /
Vertical Shell with
Vapor Liquid Separator for FF Conical Top & Dished
V-1503 1 0
Effect - III Bottom.
Capacity : 35 m3
Type: Cylindrical /
Vertical Shell with
Vapor Liquid Separator for FF
V-1504 0 1 Conical Top & Dished
Standby Effect
Bottom.
Capacity : 35 m3
Type: Cylindrical /
Vapor Liquid Separator for FC Vertical Shell with
V-1505 1 0 Dished Top & Bottom.
Effect - I
Capacity : 2.8 m3
Type: Cylindrical /
Vapor Liquid Separator for FC Vertical Shell with
V-1506 1 0
Effect - II Dished Top & Bottom.
Capacity : 2.8 m3
Type: Cylindrical /
Vapor Liquid Separator for FC Vertical Shell with
V-1507 0 1
Standby Effect Dished Top & Bottom.
Capacity : 2.8 m3
Y-1501 Mist Eliminator for FF Effect -I 1 0 Wire Mesh Type
Mist Eliminator for FF
Y-1502 1 0 Wire Mesh Type
Effect–II
Mist Eliminator for FF
Y-1503 1 0 Wire Mesh Type
Effect–III
Mist Eliminator for FF Standby
Y-1504 0 1 Wire Mesh Type
Effect
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
QUANTITY
TAG NO. DESCRIPTION TECHNICAL DETAILS
OP. S/B.
Y-1505 Mist Eliminator for FC Effect -I 1 0 Wire Mesh Type
Y-1506 Mist Eliminator for FC Effect -II 1 0 Wire Mesh Type
Mist Eliminator for FC Standby
Y-1507 0 1 Wire Mesh Type
Effect
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
SET PRESSURE
TAG NO. DESCRIPTION
bar (g)
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
PART–II
PRE-START-UP ACTIVITIES
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1. The procedures and operating conditions listed here are guidelines only and may
be modified on start-up. The control system must be flexible enough to
accommodate these changes.
2. These instructions do not cover peripheral equipment, which may affect the plant
operation.
3. It is expected that the operator may be required to take some decisions and actions
not covered by this manual. The operator will be expected to monitor the system
during operation, and may need to intervene to assure safe operation of the plant
as and when required. The control system must be flexible enough to allow
operator intervention when necessary.
4. Operator should read the bought-out items operation manual / safety procedures
received from respective vendors and follow the instructions as mentioned in their
manual before starting / stopping the respective item.
5. Operating personnel should follow the safety regulations as per factory rules as
well as factory acts and regulations.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Inspection is nothing but P&ID & Layout audit. It is necessary to conduct P&ID &
Layout audit to ensure that plant erection is done as per the recommended design.
Audit report should be made and if in case any work is pending it should be brought
to notice of project engineer and should be completed considering pre-start-up and
start-up schedule. All instruments should be mounted at respective locations, tested,
calibrated and ready for use. Ensure that all the equipment and instruments are
properly tagged and respective tag numbers and nameplates are visible to operators
to avoid any confusion during operation. Pipes should be colored and coded for
proper identification and ease of operation as per the codes prescribed by local legal
body.
Once P&ID & Layout audit is completed and system is ready in all respects carry out
internal inspection of all equipment. Ensure that there should not be any foreign
material inside. It should be free from all debris. Note that external process area is
equally important and it should be neat and clean. There should not be any machinery
lying inside the process area, which may create obstacle in operation.
Once physical inspection of all equipment is completed open bottom most nozzles for
flushing purpose. Make temporary arrangements for putting water from top of the all
equipment for flushing. Remember that these temporary arrangements made should
be removed after water flushing. Flush all the equipment till you get clear water from
bottom nozzles of the respective equipment.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
B. Flushing of Piping
During erection there are chances that metal pieces, welding rod pieces, cotton balls
etc. may trap inside pipelines. It is necessary to flush piping to avoid problems like
chocking, damaging of instruments, and pumps during pre-start-up and start-up.
Liquid lines can be flushed with water. Steam lines flushed with steam and airlines
can be flushed with air. Please remember that one end of the line should be open to
atmosphere and other end should be connected to flushing media. During flushing
please follow safety aspects also.
D. Box up of System
Once equipment’s inspection & cleaning is completed and piping flushing is
completed, box up the total system. Ensure that all pipe lines are properly connected
in place. All manholes / man-ways, drains, vents should be closed properly and
system should be made ready for use.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
control panel with valve opening in field. After complete stroke checking its formal
report should be made and problems faced should be reported and rectified.
F. Interlock testing
All interlocks should be tested before putting system on line. For interlock test
methods refer to instrumentation instruction manual. Process person should witness
this test and joint report should be made.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
5. Ensure establishment of cooling water circuit for Evaporation section. Ensure the
performance of temperature transmitters on cooling water lines.
4 Gradually open steam to Falling Film Evaporator section by opening Flow control
valve (FCV-150901) 10% in MAN mode.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Water Flushing/cold water trail is nothing but cleaning of equipment and arresting
the leakage. It is very important to test plant on water first to see its performance so as
not to face any problem during actual plant operation. During water trial itself it is
important to tune-up all the instruments and observe the performance of rotating
equipment. Before starting actual water trial ensure there is sufficient Process water
stock available. Following are the equipment to be tested on water along with allied
rotating accessories and pipelines:
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
x. Pumps
y. Condensate pots
z. CIP loop consisting CIP Tank (T-1506) and Pumps (P-1515, P-1516)
Before starting actual water flushing ensure availability of process water and other
utilities.
All motors, pumps, are to be operated remotely/ manual with in coordination with
field personnel. It is presumed that instrument airline flushing, control valve stroking
of all control valves and instrumentation continuity has already been done. Flushing
of Sealing Water Header and utility headers has been done thoroughly.
Ensure flow of sealing water to the required pumps.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1. Ensure sufficient fresh water stock available, and all solenoid valves in
evaporation sections are closed.
2. Open manual valve on fresh water line to CIP Tank (T-1506). Water will start
flowing to CIP Tank (T-1506). Open CIP Transfer Pump (P-1515) suction valve and
drain valve; close the drain valve after clear water is observed. CIP Tank (T-1506)
level starts increasing. Calibrate LIT-151201. When CIP Tank (T-1506) level reaches
50% (variable), Start CIP Transfer Pump (P-1515). Open pump discharge valve and
CIP Tank (T-1506) circulation valve.
3. Ensure the performance of CIP Transfer Pump (P-1515). When CIP Tank (T-1506)
level reaches 60-70% (Variable), close CIP Tank (T-1506) circulation valve and open
CIP solution inlet manual valve (100BF151137) on Thin Stillage Feed Tank (T-
1501). Water will start flowing to Thin Stillage Feed Tank (T-1501). Open Thin
Stillage Feed Pump (P-1508A/B) suction valve and drain valve; close the drain
valve after clear water is observed. Thin Stillage Feed Tank (T-1501) level starts
increasing. Calibrate LIT-151102. When Thin Stillage Feed Tank (T-1501) level
reaches 50% (variable), Start Thin Stillage Feed Pump (P-1508A/B). Open Thin
Stillage Feed Pump (P-1508A/B) discharge valve and Thin Stillage Feed Tank (T-
1501) recirculation valve. Ensure the performance of Thin Stillage Feed Pump (P-
1508A/B).
When Thin Stillage Feed Tank (T-1501) level reaches 60-70% (Variable), close Thin
Stillage Feed Tank (T-1501) recirculation valve and open manual valves across
Thin Stillage Preheater (H-1509A/B), XV-150102 and Level Control Valve (LCV-
150101) of Vapor Liquid Separator for FF Effect - I (V-1501) 10 % (Variable) in
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
MAN mode. Water will start flowing to Vapor Liquid Separator for FF Effect – I
(V-1501) through Thin Stillage Preheater (H-1509A/B).
4. Level in Vapor Liquid Separator for FF Effect – I (V-1501) will start rising.
Calibrate LIT-150101. When Level in Vapor Liquid Separator for FF Effect – I (V-
1501) reaches 30% (variable), open CIP drain valve of Vapor Liquid Separator for
FF Effect – I (V-1501). Open CIP Drain Pump (P-1516) suction header blind flange
to drain the flushing liquid. Close CIP drain valve after observing clear liquid.
When Vapor Liquid Separator for FF Effect – I (V-1501) level reaches 40%
(Variable), open Recirculation Pump for FF Effect – I (P-1501) suction valve and
start Recirculation Pump for FF Effect – I (P-1501). Open the pump discharge valve
gradually as per the current on performance curve adjusts the circulation valve.
Pump must not be started if discharge valve of Recirculation Pump for FF Effect – I
(P-1501) is open. Due to circulation Vapor Liquid Separator for FF Effect – I (V-
1501) level will come down little bit. Take Level Control Valve (LCV-150101) of
Vapor Liquid Separator for FF Effect – I (V-1501) in AUTO mode with 40%
(Variable) set point. Ensure the flow pattern of falling liquid from Falling Film
Effect – I (H-1501) to Vapor Liquid Separator for FF Effect – I (V-1501). Ensure the
performance of Recirculation Pump for FF Effect – I (P-1501).
5. Open XV-150203/XV-150202 and Level Control Valve (LCV-150201) of Vapor
Liquid Separator for FF Effect – II (V-1502) in MAN mode. Water will start flowing
from Recirculation Pump for FF Effect – I (P-1501) discharge to Vapor Liquid
Separator for FF Effect – II (V-1502). Level in Vapor Liquid Separator for FF Effect
– II (V-1502) will start rising. Calibrate LIT-150201. When Level in Vapor Liquid
Separator for FF Effect – II (V-1502) reaches 30% (variable), Open CIP drain valve
of Vapor Liquid Separator for FF Effect – II (V-1502). Close CIP drain valve after
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
observing clear liquid. When Vapor Liquid Separator for FF Effect – II (V-1502)
level reaches 40% (Variable), open Recirculation Pump for FF Effect – II (P-1502)
suction valve and start Recirculation Pump for FF Effect – II (P-1502). Open the
pump discharge valve gradually as per the current on performance curve adjusts
the circulation valve. Pump must not be started if discharge valve of Recirculation
Pump for FF Effect – II (P-1502) is open. Due to circulation Vapor Liquid Separator
for FF Effect – II (V-1502) level will come down little bit. Take Level Control Valve
(LCV-150201) of Vapor Liquid Separator for FF Effect – II (V-1502) in AUTO mode
with 40% (Variable) set point. Ensure the flow pattern of falling liquid from Falling
Film Effect – II (H-1502) to Vapor Liquid Separator for FF Effect – II (V-1502).
Ensure the performance of Recirculation Pump for FF Effect – II (P-1502).
6. Open XV-150302/XV-150303 and Level Control Valve (LCV-150301) of Vapor
Liquid Separator for FF Effect – III (V-1503) in MAN mode. Water will start
flowing from Recirculation Pump for FF Effect – II (P-1502) discharge to Vapor
Liquid Separator for FF Effect – III (V-1503). Level in Vapor Liquid Separator for
FF Effect – III (V-1503) will start rising. Calibrate LIT-150301. When Level in Vapor
Liquid Separator for FF Effect – III (V-1503) reaches 30% (variable), Open CIP drain
valve of Vapor Liquid Separator for FF Effect – III (V-1503). Close CIP drain valve
after observing clear liquid. When Vapor Liquid Separator for FF Effect – III (V-
1503) level reaches 40% (Variable), open Recirculation Pump for FF Effect – III (P-
1503) suction valve and start Recirculation Pump for FF Effect – III (P-1503). Open
the pump discharge valve gradually as per the current on performance curve
adjusts the circulation valve. Pump must not be started if discharge valve of
Recirculation Pump for FF Effect – III (P-1503) is open. Due to circulation Vapor
Liquid Separator for FF Effect – III (V-1503) level will come down little bit. Take
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Level Control Valve (LCV-150301) of Vapor Liquid Separator for FF Effect – III (V-
1503) in AUTO mode with 40% (Variable) set point. Ensure the flow pattern of
falling liquid from Falling Film Effect – III (H-1503) to Vapor Liquid Separator for
FF Effect – III (V-1503). Ensure the performance of Recirculation Pump for FF
Effect – III (P-1503).
7. Open XV-150402/XV-150403 and Level Control Valve (LCV-150401) of Vapor
Liquid Separator for FF Standby Effect (V-1504) in MAN mode. Water will start
flowing from Recirculation Pump for FF Effect – III (P-1503) discharge to Vapor
Liquid Separator for FF Standby Effect (V-1504). Level in Vapor Liquid Separator
for FF Standby Effect (V-1504) will start rising. Calibrate LIT-150401. When Level
in Vapor Liquid Separator for FF Standby Effect (V-1504) reaches 30% (variable),
Open CIP drain valve of Vapor Liquid Separator for FF Standby Effect (V-1504).
Close CIP drain valve after observing clear liquid. When Vapor Liquid Separator
for FF Standby Effect (V-1504) level reaches 40% (Variable), open Recirculation
Pump for FF standby Effect (P-1504) suction valve and start Recirculation Pump
for FF standby Effect (P-1504). Open the pump discharge valve gradually as per
the current on performance curve adjusts the circulation valve. Pump must not be
started if discharge valve of Recirculation Pump for FF Standby Effect (P-1504) is
open. Due to circulation Vapor Liquid Separator for FF Standby Effect (V-1504)
level will come down little bit. Take Level Control Valve (LCV-150401) of Vapor
Liquid Separator for FF Standby Effect (V-1504) in AUTO mode with 40%
(Variable) set point. Ensure the flow pattern of falling liquid from Falling Film
Standby Effect (H-1504) to Vapor Liquid Separator for FF Standby Effect (V-1504).
Ensure the performance of Recirculation Pump for FF Standby Effect (P-1504).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
8. Open XV-150502 and Level Control Valve (LCV-150501) of Vapor Liquid Separator
for FC Effect - I (V-1505) in MAN mode. Water will start flowing from P-1503/P-
1504 discharge to Vapor Liquid Separator for FC Effect - I (V-1505). Level in Vapor
Liquid Separator for FC Effect - I (V-1505) will start rising. Calibrate LIT-150501.
When Level in Vapor Liquid Separator for FC Effect - I (V-1505) reaches 30%
(variable), open CIP drain valve of Vapor Liquid Separator for FC Effect - I (V-
1505). Close CIP drain valve after observing clear liquid. When Vapor Liquid
Separator for FC Effect - I (V-1505) level reaches 40% (Variable), open Recirculation
Pump for FC Effect - I (P-1505) suction valve and start Recirculation Pump for FC
Effect - I (P-1505). Open the pump discharge valve gradually as per the current on
performance curve adjusts the circulation valve. Pump must not be started if
discharge valve of Recirculation Pump for FC Effect - I (P-1505) is open. Due to
circulation Vapor Liquid Separator for FC Effect - I (V-1505) level will come down
little bit. Take Level Control Valve (LCV-150501) of Vapor Liquid Separator for FC
Effect - I (V-1505) in AUTO mode with 40% (Variable) set point. Ensure the flow
pattern from Vapor Liquid Separator for FC Effect – I (V-1505) to Forced
Circulation Effect – I (H-1505). Ensure the performance of Recirculation Pump for
FC Effect - I (P-1505).
9. Open XV-150601/XV-15602 and Level Control Valve (LCV-150601) of Vapor
Liquid Separator for FC Effect - II (V-1506). in MAN mode. Water will start
flowing from Recirculation Pump for FC Effect - I (P-1505) discharge to Vapor
Liquid Separator for FC Effect - II (V-1506). Level in Vapor Liquid Separator for FC
Effect - II (V-1506) will start rising. Calibrate LIT-150601. When Level in Vapor
Liquid Separator for FC Effect - II (V-1506) reaches 30% (variable), open CIP drain
valve of Vapor Liquid Separator for FC Effect - II (V-1506). Close CIP drain valve
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
after observing clear liquid. When Vapor Liquid Separator for FC Effect - II (V-
1506) level reaches 40% (Variable), open Recirculation Pump for FC Effect - II (P-
1506) suction valve and start Recirculation Pump for FC Effect - II (P-1506). Open
the pump discharge valve gradually as per the current on performance curve
adjusts the circulation valve. Pump must not be started if discharge valve of
Recirculation Pump for FC Effect - II (P-1506) is open. Due to circulation Vapor
Liquid Separator for FC Effect - II (V-1506) level will come down little bit. Take
Level Control Valve (LCV-150601) of Vapor Liquid Separator for FC Effect - II (V-
1506) in AUTO mode with 40% (Variable) set point. Ensure the flow pattern from
Vapor Liquid Separator for FC Effect–II (V-1506) to Forced Circulation Effect–II
(H-1506). Ensure the performance of Recirculation Pump for FC Effect - II (P-1506).
10. Open XV-150701/XV-15702 and Level Control Valve (LCV-150701) for Vapor
Liquid Separator for FC Standby Effect (V-1507). in MAN mode. Water will start
flowing from P-1505/P-1506 discharge to Level in Vapor Liquid Separator for FC
standby Effect (V-1507). Level in Vapor Liquid Separator for FC standby Effect (V-
1507) will start rising. Calibrate LIT-150701. When Level in Vapor Liquid Separator
for FC Standby Effect (V-1507) reaches 30% (variable), Open CIP drain valve of
Vapor Liquid Separator for FC Standby Effect (V-1507). Close CIP drain valve after
observing clear liquid. When Vapor Liquid Separator for FC Standby Effect (V-
1507) level reaches 40% (Variable), open suction valve of Recirculation Pump for
FC Standby Effect (P-1507) and start Recirculation Pump for FC Standby Effect (P-
1507). Open the pump discharge valve gradually as per the current on
performance curve adjusts the circulation valve. Pump must not be started if
discharge valve of Recirculation Pump for FC Standby Effect (P-1507) is open. Due
to circulation Vapor Liquid Separator for FC Standby Effect (V-1507) level will
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
come down little bit. Take Level Control Valve (LCV-150701) for Vapor Liquid
Separator for FC Standby Effect (V-1507) in AUTO mode with 40% (Variable) set
point. Ensure the flow pattern from Vapor Liquid Separator for FC Standby Effect
(V-1507) to Forced Circulation Standby Effect (H-1507). Ensure the performance of
Recirculation Pump for FC Standby Effect (P-1507).
11. Close CIP Drain Pump (P-1516) suction header blind flange.
12. Open manual valve on CIP Drain Pump (P-1516) suction. Open CIP Drain Pump
(P-1516) suction drain valve till clear water observed. Start CIP Drain Pump (P-
1516). Open CIP Drain Pump (P-1516) discharge manual valve (100BF15216) to
Concentrated Syrup Tank (T-1505). Water will start flowing to Concentrated
Syrup Tank (T-1505). Level in Concentrated Syrup Tank (T-1505) will start rising.
Calibrate LIT-151101. When Level in Concentrated Syrup Tank (T-1505) reaches
30% (variable), Open suction valve and drain valve of Concentrated Syrup Pump
(P-1514A/B). Close CIP drain valve after observing clear liquid. When
Concentrated Syrup Tank (T-1505) level reaches 40% (Variable), Start Concentrated
Syrup Pump (P-1514A/B) and flush the line from Concentrated Syrup Pump (P-
1514A/B) to syrup storage station by opening respective manual valve. Also flush
the recirculation lines. Ensure the performance of Concentrated Syrup Pump (P-
1514A/B).
13. After ensuring the line flushing, stop Concentrated Syrup Pump (P-1514A/B) and
close manual CIP drain valves.
14. Make temporary connection of fresh water for Process Condensate Tank - 2 (T-
1503) flushing. Start fresh water to Process Condensate Tank - 2 (T-1503). Open
Process Condensate Pump - 2 (P-1510) suction valve and drain valve. Close the
drain valve after observing clear water from the drain. Level in Process
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Condensate Tank - 2 (T-1503) will start rising. Calibrate LIT-150801. When Process
Condensate Tank - 2 (T-1503) level reaches 50% (Variable), start Condensate Pump
- 2 (P-1510). Take Level Control Valve (LCV-150801) of Process Condensate Tank -
2 (T-1503) in MAN mode and flush the discharge line to Process Condensate Tank–
1 (T-1502). After ensuring the line flushing close the valve to Process Condensate
Tank – 1 (T-1502). Ensure the flow through FIT-150801. Ensure the performance of
Process Condensate Pump - 2 (P-1510).
15. Open the manual valves on process condensate line from H-1506 / H-1507 Forced
Circulation effect II and Forced Circulation Standby effect to Process Condensate
Tank – 2 (T-1503) one by one and flush the respective lines. Close the manual
valves on respective process condensate line after flushing.
16. Take fresh water from Process Condensate Tank – 2 (T-1503) to Process
Condensate Tank - 1 (T-1502) for flushing through Process Condensate Pump – 2
(P-1510). Open Process Condensate Pump - 1 (P-1509) suction valve and drain
drain valve. Close the drain valve after observing clear water from the drain. Level
in Process Condensate Tank - 1 (T-1502) will start rising. Calibrate LIT-151001.
When Process Condensate Tank - 1 (T-1502) level reaches 50% (Variable), start
Process Condensate Pump - 1 (P-1509). Open Process Condensate Pump - 1 (P-
1509) discharge valve and flush the discharge line up to treatment plant through
Treated Process Condensate Preheater (H-1510). After flushing the discharge line
up to treatment plant, flush the discharge line routed for cleaning of Vapor Liquid
Separators of Falling film effect and Forced Circulation effect one by one. Also
flush line to Thin Stillage Tank (T-1801). Flush the emergency process condensate
supply line to all falling film Effect and forced circulation effect. After ensuring the
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
line flushing closes the valve and open valve to Process Condensate Treatment
section. Ensure the performance of Process Condensate Pump - 1 (P-1509).
17. Open the manual valves on process condensate line from respective Falling Film
effect to Process Condensate Tank – 1 (T-1502) and flush the respective lines. Close
the manual valves on respective process condensate line after flushing.
18. Make temporary connection of fresh water for Steam Condensate Tank (T-1504)
flushing. Start fresh water to Steam Condensate Tank (T-1504). Open Steam
Condensate Pump (P-1511) suction valve and drain valve. Close the drain valve
after observing clear water from the drain. Level in Steam Condensate Tank (T-
1504) will start rising. Calibrate LIT-150901. When Steam Condensate Tank (T-
1504) level reaches 50% (Variable), start Steam Condensate Pump (P-1511). Open
Steam Condensate Pump (P-1511) discharge valve and flush the discharge line to
Thin Stillage Preheater (H-1509A/B) by opening manual valves. After ensuring the
line flushing closes the valve. Ensure the performance of Steam Condensate Pump
(P-1511).
19. Open the manual valves on steam condensate line from respective Falling Film
effect and Forced circulation effect to Steam Condensate Tank (T-1504) one by one
and flush the respective lines. Close the manual valves on respective steam
condensate line after flushing.
20. Close all manual valves as well as solenoid valves in Evaporation sections after
water trial.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Vacuum test has to be carried out for all the equipment, which is subjected to vacuum
condition during the plant operation. Vacuum trial is to be carried out to detect air
leakage in the system.
Before staring the vacuum trials vacuum pump should be tested and its performance
should be monitored.
• Ensure cooling water is available for the vacuum pump PHE.
• Ensure the required pressure of fresh water is available for Vacuum Pumps.
• Check the Vacuum Pumps for free rotation, direction of rotation and lubrication.
• Check the suction and discharge piping of Vacuum Pumps. Put wire mesh in
suction line of the pump to avoid any foreign material entering in pump and
further damage of it.
• Ensure water flushing of soft water line to Vacuum Pump and vacuum pump
discharge chamber flushing completed.
Once these preliminary checks are over, read the operation manual of the vacuum
pump supplier and follow the instructions given therein to start the pump. Before
starting the pump ensure that air bleed valve is completely open and then start the
pump. Note the current. Check for unusual sound and vibration. If the pump
performance is satisfactory, run it continuously for one hour. After satisfactory
operation for one hour check standby pumps in a same manner.
ALWAYS REFER VACUUM PUMP SUPPLIER’S OPERATING AND
MAINTENANCE MANUAL FOR START-UP.
Isolate the system in such a way so that nothing should come in or nothing should go
out only it should be connected to vacuum system. Close all drains, vents, and
manholes.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Ensure vacuum trial for Distillation section is completed. Ensure vacuum pumps are
in running condition.
Following equipment will be under vacuum in Evaporation Section.
a. Vapour Liquid Separators for FF Effect - I (V-1501)
b. Tube side of Falling Film Effect – I (H-1501)
c. Shell & Tube side of Falling Film Effect – II (H-1502)
d. Vapour Liquid Separators for FF Effect - II (V-1502)
e. Shell & Tube side of Falling Film Effect – III (H-1503)
f. Vapour Liquid Separators for FF Effect – III (V-1503)
g. Shell & Tube side of Falling Film Standby Effect (H-1504)
h. Vapour Liquid Separators for FF Standby Effect (V-1504)
i. Tube side of Forced Circulation Effect – I (H-1505)
j. Vapour Liquid Separators for FC Effect – I (V-1505)
k. Shell & Tube side of Forced Circulation Effect – II (H-1506)
l. Vapour Liquid Separators for FC Effect – II (V-1506)
m. Shell & Tube side of Forced Circulation Standby Effect (H-1507)
n. Vapour Liquid Separators for FC Standby Effect (V-1507)
o. Shell side of Surface Condenser (H-1508) and Process Condenser (H-
1511)
p. Process Condensate Tank - 1 (T-1502)
q. Process Condensate Tank - 2 (T-1503)
r. Condensate pots (K-1501 & K-1502).
s. All related process pipeline connected to equipment.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1. Ensure following isolation & solenoid valves position in addition to the list as
given in vacuum trial for Evaporation section.
1. Manual valve 350BF150125 on suction of Recirculation Pump for FF Effect – I
(P-1501) – CLOSED.
2. Manual valve 250BF150112 on discharge of Recirculation Pump for FF Effect – I
(P-1501) – CLOSED.
3. Manual valve 350BF150222 on suction of Recirculation Pump for FF Effect – II
(P-1502) – CLOSED.
4. Manual valve 250BF150217 on discharge of Recirculation Pump for FF Effect –
II (P-1502) – CLOSED.
5. Manual valve 350BF150332 on suction of Recirculation Pump for FF Effect – III
(P-1503) – CLOSED.
6. Manual valve 250BF150327 on discharge of Recirculation Pump for FF Effect –
III (P-1503) – CLOSED.
7. Manual valve 350BF150409 on suction of Recirculation Pump for FF Standby
Effect (P-1504) – CLOSED.
8. Manual valve 250BF150425 on discharge of Recirculation Pump for FF Standby
Effect (P-1504) – CLOSED.
9. Manual valve 200BF150530 on suction of Recirculation Pump for FC Effect – I
(P-1505) – CLOSED.
10. Manual valve 250BF150524 on discharge of Recirculation Pump for FC Effect - I
(P-1505) – CLOSED.
11. Manual valve 200BF150627 on suction of Recirculation Pump for FC Effect – II
(P-1506) – CLOSED.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
for Vapor Liquid Separator V-1504 (LCV-150401), Level Control Valve for
Vapor Liquid Separator V-1505 (LCV-150501), Level Control Valve for Vapor
Liquid Separator V-1506 (LCV-150601), Level Control Valve for Vapor Liquid
Separator V-1507 (LCV-150701), Process Condensate Tank - 2 (T-1503) Level
Control Valve (LCV-150801), Process Condensate Tank – 1 (T-1502) Level
Control Valve (LCV-151001). - CLOSED.
35. Manual valves of air bleed & Thin Stillage Vapor bleed for Vapor Liquid
Separators for FF Effect - I (V-1501), Vapor Liquid Separators for FF Effect - II
(V-1502), Vapor Liquid Separators for FF Effect - III (V-1503), Vapor Liquid
Separators for FF Standby Effect (V-1504), Vapor Liquid Separators for FC
Effect - I (V-1505), Vapor Liquid Separators for FC Effect - II (V-1506) and
Vapor Liquid Separators for FC Standby Effect (V-1507) – CLOSED.
36. Manual valve on process condensate line to Process Condensate Tank - 1 (T-
1502) and Process Condensate Tank – 2 (T-1503) – CLOSED.
37. All drains, vents, bleed and sample points valves – CLOSED.
38. All pressure / vacuum gauges valves – OPEN.
39. All valves on utility and process condensate lines for sight glass cleaning –
CLOSED.
2. Ensure healthiness of tight shutoff of solenoid valves while taking vacuum trial in
evaporation section. If any solenoid valve passes, the vacuum will be generated for
that particular effect which to be observed from local gauges and to be rectified
accordingly.
3. Open solenoid valve (XV-151301 and XV-151302) on the line which is connected to
suction line of vacuum pump (P-1513 A/B). Start Vacuum Pumps (P-1513A/B) by
referring operation and maintenance manual of Vacuum Pumps.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
4. Open respective manual valves across Shell side of Surface Condenser (H-1508)
and Process Condenser (H-1511), Forced Circulation Standby Effect (H-1507),
Forced Circulation Effect – II (H-1506), Falling Film Standby Effect (H-1504),
Falling Film Effect – III (H-1503), Falling Film Effect – II (H-1502) connected to
Vacuum system.
5. Open respective manual valves on Thin Stillage Vapor outlet from Vapour Liquid
Separators for FC Standby Effect (V-1507), Vapour Liquid Separators for FC Effect
– II (V-1506), Vapour Liquid Separators for FC Effect – I (V-1505)
6. Stop vacuum pumps after desired vacuum is achieved.
7. Observe the drop in vacuum and note down the vacuum drop w.r.t. time. If
vacuum drop is less than 40 mm Hg per hour then vacuum trial is acceptable. If
vacuum drop is more than 40 mmHg per hour then rectify the leakage and attend
it to reduce vacuum drop.
8. Once vacuum trial is OK release vacuum by opening the vent valves or, keep the
vacuum and start evaporation or water boiling as planned.
9. Now take distillation and evaporation system as a single system under vacuum for
trial. Open interconnecting manual valve 600BF150407/600BF150408 from
Evaporation section to Distillation section. Once the air leakages are arrested,
isolate the whole system by closing the valve on the suction line of the Vacuum
pump and stop the vacuum pump.
10. Check the rate of drop in vacuum and it should not be more than 40 mm of
mercury per hour.
11. This will confirm the vacuum test. Make formal report for evaporation vacuum
trial.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
The purpose of steam trial is to ensure the line up, leakages, instruments healthiness.
Steam trial is to be carried out in coordination with boiler house. It is presumed that
instrument airline flushing, control valve stroking of all control valves and
instrumentation continuity has already been done. Vacuum Trials have been
completed as well. Flushing of all utility headers has been done thoroughly. PSV
tested and installed at its place. Steam trial is nothing but running plant without Thin
Stillage. It is very important to test plant on water first to see its performance so as not
to face any problem during actual plant operation. During water trial itself it is
important to tune-up all the instruments and observe the performance of rotating
equipment too.
During steam trial all motors, pumps are to be operated remotely in coordination with
field personnel.
It is presumed that instrument air line flushing, control valve stroking of all control
valves and instrumentation continuity, water flushing, vacuum trial has already been
done. Flushing of Sealing Water Header and utility headers has been done
thoroughly. Ensure flow of sealing water to the required pumps. Ensure following
systems are ready up to respective user’s isolation point –
1. Power supply
2. Instrument air supply
3. Steam supply
4. Cooling water
5. Fresh water supply
6. Sealing water supply
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Manual valves on steam line, steam condensate line, Thin Stillage Vapor
line and Thin Stillage line -OPEN.
Isolation valve on steam to Evaporation section 1 - CLOSED.
Falling Film Effect – I (H-1501) non condensable manual valves – OPEN.
Falling Film Effect – I (H-1501) steam condensate line out to Steam
Condensate Tank (T-1504).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
8. Ensure Steam Flow Control Valve (FCV-150901) closed. Open upstream side
manual valve of Steam Flow Control Valve (FCV-150901).
9. Ensure steady pressure of low pressure steam header. Inform boiler house
regarding the use of steam.
10. Gradually open manual valve on low pressure steam line to Falling Film Effect – I
(H-1501)
11. Open steam flow control valve (FCV-150901) 5% (Variable) in MAN mode.
Condensation of steam will start on shell side of Falling Film Effect – I (H-1501) by
giving its thermal energy to the circulating fluid on tube side. Adjust venting
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
observing clear water from the drain. Level in Steam Condensate Tank (T-1504)
will start rising. When Steam Condensate Tank (T-1504) level reaches 75%
(Variable), open Steam Condensate Pump (P-1511) suction valve and start the
pump. Open Steam Condensate Pump (P-1511) discharge valve. Open manual
valves on discharge line. Open Steam Condensate Tank (T-1504) Level Control
Valve (LCV-150901) in MAN mode. Ensure the flow of steam condensate to steam
condensate return header (B/L) through Thin Stillage Preheater (H-1509A/B).
Take Steam Condensate Tank (T-1504) Level Control Valve (LCV-150901) in AUTO
mode with 50% (Variable) set point.
21. Increase in TI-150101 & TI-150201 is the indication of evaporation from Vapour
Liquid Separator for FF Effect – I (V-1501) or Vapor Liquid Separator for FF Effect
– II (V-1502). Take FQIC-150901 in AUTO mode with the flow at 10% (Variable)
valve opening. Gradually go on increasing the steam flow set point up to required
capacity go on increasing the steam flow set point up to required capacity.
22. Increase in TI-150502 & TI-150602 is the indication of evaporation from Vapor
Liquid Separator for FC Effect – I (V-1505) & Vapor Liquid Separator for FC Effect
– II (V-1506). Take FQIC-150501 in AUTO mode with the flow at 10% (Variable)
valve opening. Gradually, go on increasing the steam flow set point up to required
capacity.
23. Gradually start reducing the opening of Pressure Control Valve (PCV-150801) in
MAN mode. Because of evaporation pressure will start building in Vapour Liquid
Separator for FC Effect - I (V-1505), Vapour Liquid Separator for FC Effect - II (V-
1506) & Vapour Liquid Separator for FC Standby Effect (V-1507). Take PIC-150801
in AUTO mode with 0.2 kg/cm2 (a) set point.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
24. Based on evaporation rate in Vapour Liquid Separator for FF Effect – I (V-1501),
Vapour Liquid Separator for FF Effect - II (V-1502), Vapour Liquid Separator for FF
Effect - III (V-1503), Vapour Liquid Separator for FF Standby Effect (V-1504),
Vapour Liquid Separator for FC Effect – I (V-1505), Vapor Liquid Separator for FC
Effect – II (V-1506) and Vapour Liquid Separator for FC Standby Effect (V-1507)
respective level control valves will open in order to maintain the level.
25. In Sorghum case, Vapours from Vapour Liquid Separator for FF Effect - I (V-1501),
Vapour Liquid Separator for FF Effect - II (V-1502), Vapour Liquid Separator for FF
Effect – III (V-1503) and Vapour Liquid Separator for FF Standby Effect (V-1504)
will start condensing on shell side of Falling Film Effect – II (H-1502), Falling Film
Effect – III (H-1503), Falling Film Standby Effect (H-1504) and Process Condenser
(H-1511) respectively by giving its thermal energy to the circulating fluid on tube
side. And Vapors from Vapor Liquid Separator for FC Effect – I (V-1505), Vapor
Liquid Separator for FC Effect – II (V-1506) and Vapor Liquid Separator for FC
Standby Effect will start condensing on shell side of Forced Circulation Effect – II
(H-1506), Forced Circulation Standby Effect (H-1507) and Surface Condenser (H-
1508) respectively by giving its thermal energy to the circulating fluid on tube side.
26. In Corn case, Vapours from Vapour Liquid Separator for FF Effect - I (V-1501),
Vapour Liquid Separator for FF Effect - II (V-1502), Vapour Liquid Separator for FF
Effect – III (V-1503) and Vapour Liquid Separator for FF Standby Effect (V-1504)
will start condensing on shell side of Falling Film Effect – II (H-1502), Falling Film
Effect – III (H-1503), Falling Film Standby Effect (H-1504) and Surface Condenser
(H-1508) respectively by giving its thermal energy to the circulating fluid on tube
side.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
27. Process condensate from Falling Film Effect – II (H-1502), Falling Film Effect – III
(H-1503) and Falling Film Standby Effect (H-1504) will start flowing to Process
Condensate Tank – 1 (T-1502) through condensate pot. When Process Condensate
Tank - 1 (T-1502) level reaches 50% (Variable), open Process Condensate Pump - 1
(P-1509) suction valve and start the pump. Open Process Condensate Pump - 1 (P-
1509) discharge valve. Open Process Condensate Tank - 1 (T-1502) Level Control
Valve (LCV-151001) in MAN mode. Ensure the flow of condensate to Process
Condensate Treatment Plant. Take LIC-151001 in AUTO mode with 50% (Variable)
set point.
28. Process condensate from Forced Circulation Effect – II (H-1506), Forced Circulation
Standby Effect (H-1507), Process Condenser (H-1511) and Surface Condenser (H-
1508) will start flowing to Process Condensate Tank – 2 (T-1503). When Process
Condensate Tank - 2 (T-1503) level reaches 50% (Variable), open Process
Condensate Pump - 2 (P-1510) suction valve and start the pump. Open Process
Condensate Pump - 2 (P-1510) discharge valve. Open Process Condensate Tank - 2
(T-1503) Level Control Valve (LCV-150801) in MAN mode. Ensure the flow of
condensate to Process Condensate Tank – 1 (T-1502) through FIT-150801. Take
LIC-150801 in AUTO mode with 50% (Variable) set point.
29. Observe the vapour condensation on flow glass provided on H-1501, H-1502, H-
1503, H-1504, H-1505, H-1506 and H-1507. Condensation can be ensured from flow
glass on condensate line of H-1501, H-1502, H-1503, H-1504, H-1505, H-1506 and
H-1507.
30. Based on evaporation rate in H-1501, H-1502, H-1503, H-1504, H-1505, H-1506 and
H-1507 respective level control valves will open in order to maintain the level.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
31. Ensure tuning of all controllers. Continue the water boiling in Evaporation section
for at least 24 hrs.
32. After ensuring the steady state process parameters during water boiling check the
performance of all equipment. Switchover the respective users to standby pumps,
standby PHE etc. Also check the changeover of evaporation effect one by one.
(Refer: Control & Interlock Descriptive Logic N-10012-4-ILD 1501, section “N-
Changeover Modes for falling film evaporators and forced circulation
evaporators’)
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
SR.
PARAMTERS TAG NO. UNIT VALUE
NO.
1 V-1501 level LIC-150101 % 50
2 V-1502 level LIC-150201 % 50
3 V-1503 level LIC-150301 % 50
4 V-1504 level LIC-150401 % 50
5 V-1505 level LIC-150501 % 50
6 V-1506 level LIC-150601 % 50
7 V-1507 level LIC-150701 % 50
8 P-1501 to H-1501 Temperature TI-150101 oC 103.5
9 LP steam to H-1501/H-1502 TI-150102 oC 112
10 V-1501 Temp. TI-150103 oC 103.1
11 P-1502 to H-1502 Temperature TI-150201 oC 103.5
12 V-1502 Temp. TI-150202 oC 103.1
13 P-1503 to H-1503 Temperature TI-150301 oC 96.3
14 V-1503 Temp. TI-150302 oC 95.5
15 P-1504 to H-1504 Temperature TI-150401 oC 85.5
16 V-1504 Temp. TI-150402 oC 84.5
17 P-1505 to H-1505 Temperature TI-150501 oC 92.3
18 H-1505 to V-1505 TI-150502 oC 92.3
19 V-1505 Temp. TI-150503 oC 90.6
20 P-1506 to H-1506 Temperature TI-150601 oC 67
21 H-1506 to V-1506 Temperature TI-150602 oC 67
22 V-1506 Temp. TI-150603 oC 65
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
SR.
PARAMTERS TAG NO. UNIT VALUE
NO.
23 P-1507 to H-1507 Temperature TI-150701 oC 67
24 H-1507 to V-1507 Temperature TI-150702 oC 67
25 V-1507 Temp. TI-150703 oC 65
26 Cooling water supply Temp. TI-150801 oC 31
27 Cooling water return Temp. TI-150802 oC 41
Thin Stillage Vapor to P-1513A/B oC
28 TI-150803 62
Temp.
29 Thin Stillage to H-1509A/B Temp. TI-150901 oC 80
30 P-1511 to H-1509A/B Temp. TI-150902 oC 112
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
SR.
PARAMTERS TAG NO. UNIT VALUE
NO.
45 T-1502 level LIC-151001 % 50
46 T-1505 level LIC-151101 % 50
47 T-1501 level LI-151102 % 50
48 T-1506 level LI-151201 % 50
NOTE –
Above parameters are only guidelines. Actual operating parameters shall be fine-
tuned at site during Commissioning.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
PART – III
PROCESS START-UP
AND
PROCESS PARAMETERS
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Operator must read and understand these instructions before operating the
plant.
1. The procedures and operating conditions listed here are guidelines only and may
be modified on start-up. The control system must be flexible enough to
accommodate these changes.
2. These instructions do not cover peripheral equipment, which may affect the plant
operation.
3. It is expected that the operator may be required to take some decisions and actions
not covered by this manual. The operator will be expected to monitor the system
during operation, and may need to intervene to assure safe operation of the plant
as and when required. The control system must be flexible enough to allow
operator intervention when necessary.
4. Operator should read the bought-out items operation manual / safety procedures
received from respective vendors and follow the instructions as mentioned in their
manual before starting / stopping the respective item.
5. Operating personnel should follow the safety regulations as per factory rules as
well as factory acts and regulations.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
10. During initial start-up the solid concentration in concentrated syrup will be less
because on less total solids in Thin Stillage mash itself. So do not allow the Thin
Stillage with low total solids to Concentrated Syrup Tank (T-1505). Start P-
1514A/B and divert thin stillage to Feed Tank. After establishment of total solids
from evaporation, divert Concentrated Syrup to storage area.
11. Based on evaporation rate in Falling Film Effect – I (H-1501), Falling Film Effect – II
(H-1502), Falling Film Effect – III (H-1503), Forced Circulation Effect – I (H-1505),
Forced Circulation Effect – II (H-1506) water from evaporators will be replaced by
Thin Stillage. Based on evaporation rate the solid concentration in evaporators will
increase gradually.
12. Keep close watch on –
Current of motors for Recirculation Pump for FF Effect – I (P-1501)
Current of motors for Recirculation Pump for FF Effect – II (P-1502)
Current of motors for Recirculation Pump for FF Effect – III (P-1503)
Current of motors for Recirculation Pump for FC Effect - I (P-1505)
Current of motors for Recirculation Pump for FC Effect - II (P-1506)
Current of motors for Thin Stillage Feed Pump (P-1508A/B)
Current of motors for Process Condensate Pump – 1 (P-1509)
Current of motors for Process Condensate Pump – 2 (P-1510)
Current of motors for Steam Condensate Pump (P-1511)
Current of motors for Concentrated Syrup Transfer Pump (P-1512)
Current of motors for Concentrated Syrup Pump (P-1514 A/B)
V-1505/V-1506 Density indication on DIC-150601
Total solids analysis report from laboratory for Vapor Liquid Separator
for FF Effect - I (V-1501)
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Total solids analysis report from laboratory for Vapor Liquid Separator
for FF Effect - II (V-1502)
Total solids analysis report from laboratory for Vapor Liquid Separator
for FF Effect - III (V-1503)
Total solids analysis report from laboratory for Vapor Liquid Separator
for FC Effect - I (V-1505)
Total solids analysis report from laboratory for Vapor Liquid Separator
for FC Effect - II (V-1506)
13. After achieving the solid concentration in evaporation section, divert concentrated
syrup to storage. Take DIC-150601 in AUTO mode with FQIC-150601 in
CASCADE mode. If density at DIC-150601 increases, it will decrease the set point
of FQIC-150601 and vice versa.
14. Check FQI-150801 on process condensate to T-1502 flow rate.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
FQIC-
1 Thin Stillage Vapor to C-1401 Kg/hr 8620
150401
FQIC-
2 LP steam to H-1505/H-1506 Kg/hr 685.14
150501
FQIC-
3 Concentrated Syrup to T-1505 Kg/hr 8723.26
150601
4 Process Condensate to T-1502 FQI-150801 Kg/hr 21736.30
FQIC-
5 LP steam to H-1501/H-1502 Kg/hr 11926.07
150901
6 Thin Stillage Feed Flow FQI-151101 Kg/hr 43458
FQIC-
1 Thin Stillage Vapor to C-1401 Kg/hr 8620
150401
FQIC-
2 LP steam to H-1505/H-1506 Kg/hr 658.35
150501
FQIC-
3 Concentrated Syrup to T-1505 Kg/hr 8382.16
150601
4 Process Condensate to T-1502 FQI-150801 Kg/hr 16361.43
FQIC-
5 LP steam to H-1501/H-1502 Kg/hr 8986.93
150901
6 Thin Stillage Feed Flow FQI-151101 Kg/hr 34901
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
FQIC-
1 Thin Stillage Vapor to C-1401 Kg/hr 8125
150401
FQIC-
2 Concentrated Syrup to T-1505 Kg/hr 7152.04
150601
3 Process Condensate to T-1502 FQI-150801 Kg/hr 623.93
FQIC-
4 LP steam to H-1501/H-1502 Kg/hr 8514.91
150901
5 Thin Stillage Feed Flow FQI-151101 Kg/hr 24336
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
LEVEL
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
TOTAL SOLIDS
NOTE –
1. Above parameters are only guidelines. Actual operating parameters shall be
fine-tuned at site during Commissioning.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
The evaporation plant is designed such that CIP of any one Falling Film Effect out of
four Falling Film Effect and CIP of any one Forced Circulation Effect out of three Forced
Circulation Effect can be carried out at a time, while the other evaporators will be in
operation.
3.0.4 a SOP for Preparation of 3-5 % w/w Nitric acid solution in CIP Tank T-1506
1. Ensure Nitric Acid CIP Tank (T-1506) vent line is clear.
2. Ensure CIP Tank (T-1506) is empty.
3. Ensure CIP Tank (T-1506) drain valve is closed.
4. Open valve on fresh water supply line and fill the required quantity of water in the
tank (Check against level of the tank). During normal operation of the plant
instead of fresh water, evaporation condensate can also be taken by opening
respective manual valve.
5. Close valve on water supply line and confirm level in the tank.
6. Open manual valve on CIP Transfer Pump (P-1515) suction and start CIP Transfer
Pump (P-1515) with re-circulation in the tank by opening manual circulation valve.
Keep the liquid in circulation.
7. Ensure Nitric Acid stock in Nitric Acid Storage Tank.
8. Open solenoid valve XV-151201 on Nitric Acid supply line to T-1506. Take
measured quantity Nitric Acid in T-1506 through FIT-151201. Close XV-151201.
Keep Nitric Acid CIP solution under circulation for half hour.
9. Ensure and confirm the Nitric Acid concentration of the tank.
10. Nitric Acid CIP solution is ready for CIP.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
3.0.4 b SOP for Preparation of 3-5 % w/w caustic solution in CIP Tank T-1351
1. Ensure CIP Tank T-1351 vent line is clear.
2. Ensure the CIP Tank (T-1351) is empty.
3. Ensure CIP Tank (T-1351) drain valve is closed.
4. Fresh water has to be used for CIP solution preparation by opening respective
manual valve.
5. Open manual valve on Fresh Water supply line to CIP Tank (T-1351) and fill the
required quantity of water in the CIP Tank (T-1351) (Check against level of the
tank).
6. Close valve on water supply line and confirm level in the tank.
7. Open valve on CIP Pump (P-1351A/B) suction and Start CIP Pump (P-1351A/B)
with re-circulation in the tank by opening re-circulation manual valve. Keep the
liquid in re-circulation.
8. Ensure Caustic stock in Storage Tank.
9. Take measured quantity caustic lye in CIP Tank T-1351.
10. Keep caustic CIP solution under circulation for half hour.
11. Ensure and confirm the caustic concentration of the tank through sample points.
12. Caustic CIP solution is ready for CIP.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
9. Ensure Nitric Acid solution is prepared and ready for transfer. Open XV-151201
Solenoid valve and start CIP Transfer Pump (P-1515). Open manual valve allow
CIP solution to be filled in Falling Film Effect – I (H-1501).
10. When level reaches 50-60% in Vapor Liquid Separator for FF Effect – I (V-1501),
stop CIP Transfer Pump (P-1515), Close manual valve on CIP solution inlet, and
start Recirculation Pump for FF Effect – I (P-1501). .
11. Re-circulate the solution through Falling Film Effect – I (H-1501) for 4 Hr. Stop
Recirculation Pump for FF Effect – I (P-1501). Open CIP drain manual valve and
start the CIP drain pump (P-1516) & transfer CIP solution to Effluent treatment.
12. Ensure Caustic solution is prepared and ready for transfer. Open suction valve and
start CIP Pump (P-1351). Open respective manual valve at CIP Pump (P-1351)
discharge and allow CIP solution to be filled in Falling Film Effect – I (H-1501).
13. When level reaches 50-60% in Vapor Liquid Separator for FF Effect - I start
Recirculation Pump for FF Effect – I (P-1501).
14. Re-circulate the solution through Falling Film Effect –I for 4 Hr. Stop Recirculation
Pump for FF Effect – I (P-1501). Drain Exhaust CIP by opening CIP drain manual
valves. Start CIP drain pump (P-1516) & transfer CIP solution to Effluent
treatment.
15. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Falling Film Effect – I (H-1501) same way like transfer of CIP solution.
16. Recirculate water through Falling Film Effect –I (H-1501) for 1 hrs. Stop
Recirculation Pump for FF Effect – I (P-1501). Drain Exhaust CIP by opening CIP
drain manual valves. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
17. Falling Film Effect – I (H-1501) is now ready and can be taken online.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
18. Close Air bleed valve and open valve on vacuum line to take initial vacuum. When
sufficient vacuum is available close vacuum valve and open XV-150102.
19. When level reaches 50-60% in Vapor Liquid Separator for FF Effect - I start
Recirculation Pump for FF Effect – I (P-1501). Open manual valves on transfer line
from Recirculation Pump for FF Effect – I (P-1501).
20. Open manual valve on steam condensate line and start steam by opening manual
valve. (Adjust set point of FQIC-150901 as per requirement).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
6. Stop Recirculation Pump for FF Effect – II (P-1502), Open manual Air bleed valve
and release the vacuum in the effect. Let this valve remain open till the entire
CIP.
7. Open manual valve on CIP drain line of Vapor Liquid Separator for FF Effect – II
(V-1502) and start CIP drain Pump (P-1516). (Check CIP drain Pump suction
before starting) Transfer the Thin Stillage hold up to tank Thin Stillage Feed Tank
(T-1501) by opening respective manual valve. Drain the effect completely. Open
manual valve on line across Pump for FF Effect – II (P-1502) to drain Discharge
line.
8. After draining stop CIP drain Pump (P-1516) and close drain valve.
9. Fill the Vapor Liquid Separator (V-1502) with process condensate by opening
manual valve and XV-150201 up to just above normal operating level. Recirculate
this condensate for 30 minutes to 1 hour. And drain it.
10. Ensure Nitric Acid solution is prepared and ready for transfer. Open XV-151201
Solenoid valve and start pump CIP Transfer Pump (P-1515). Open manual valve
allow CIP solution to be filled in Falling Film Effect – II (H-1502).
11. When level reaches 50-60% in Vapor Liquid Separator for FF Effect – II (V-1502)
stop CIP Transfer Pump (P-1515), Close manual valve on CIP solution inlet, and
start Recirculation Pump for FF Effect – II (P-1502). Close manual valve on CIP
solution line.
12. Re-circulate the solution through Falling Film Effect – II (H-1502) for 4 Hr. Stop
Recirculation Pump for FF Effect – II (P-1502). Drain Exhaust CIP by opening CIP
drain manual valve. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
13. Ensure Caustic solution is prepared and ready for transfer. Open suction valve
and start CIP Pump (P-1351). Open respective manual valve at CIP Pump (P-
1351) discharge and allow CIP solution to be filled in Falling Film Effect – II (H-
1502).
14. When level reaches 50-60% in Vapor Liquid Separator for FF Effect – II (V-1502)
start Recirculation Pump for FF Effect – II (P-1502).
15. Re-circulate the solution through Falling Film Effect –II for 4 Hr. Stop
Recirculation Pump for FF Effect – II (P-1502). Drain Exhaust CIP by opening CIP
drain manual valves as described above. Start CIP drain pump (P-1516) &
transfer CIP solution to Effluent treatment.
16. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Falling Film Effect – II (H-1502) same way like transfer of CIP solution.
17. Recirculate water through Falling Film Effect –II (H-1502) for 1 hrs. Stop
Recirculation Pump for FF Effect – II (P-1502). Drain Exhaust CIP by opening CIP
drain manual valves. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
18. Falling Film Effect – II (H-1502) is now ready and can be taken online.
19. Close Air bleed valve and open valve on vacuum line to take initial vacuum.
When sufficient vacuum is available close vacuum valve and open XV-150202 &
XV-150203. Start Recirculation Pump for FF Effect – II (P-1502) and open manual
valves on transfer line from Recirculation Pump for FF Effect – II (P-1502).
20. Open manual valve on steam condensate line and start steam by opening manual
valve. (Adjust set point of FQIC-150901 as per requirement).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
9. Ensure Nitric Acid solution is prepared and ready for transfer. Open XV-151201
Solenoid valve and start pump CIP Transfer Pump (P-1515). Open manual valve
allow CIP solution to be filled in Falling Film Effect – III (H-1503).
10. When level reaches 50-60% in Vapor Liquid Separator for FF Effect – III (V-1503)
stop CIP Transfer Pump (P-1515), Close manual valve on CIP solution inlet, and
start Recirculation Pump for FF effect – III (P-1503). Close manual valve on CIP
solution line.
11. Recirculate the solution through Falling Film Effect - III (H-1503) for 4 Hr. Stop
Recirculation Pump for FF Effect – II (P-1502). Drain Exhaust CIP by opening CIP
drain manual valve. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
12. Ensure Caustic solution is prepared and ready for transfer. Open suction valve and
start CIP Pump (P-1351). Open respective manual valve at CIP Pump (P-1351)
discharge and allow CIP solution to be filled in Falling Film Effect – III (H-1503).
13. When level reaches 50-60% in Vapor Liquid Separator for FF Effect – III (V-1503)
start Recirculation Pump for FF Effect – III (P-1503).
14. Recirculate the solution through Falling Film Effect – III for 4 hr. Stop
Recirculation Pump for FF Effect – III (P-1503). Drain Exhaust CIP by opening CIP
drain manual valves as described above. Start CIP drain pump (P-1516) & transfer
CIP solution to Effluent treatment.
15. After this take water in of the CIP tank T-1506 / T-1351, and transfer it to Falling
Film Effect – III (H-1503) same way like transfer of CIP solutions.
16. Recirculate water through Falling Film Effect –III (H-1503) for 1 hrs. Stop
Recirculation Pump for FF Effect – III (P-1503). Drain Exhaust CIP by opening CIP
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
drain manual valves. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
17. Falling Film Effect – III (H-1503) is now ready and can be taken online.
18. Close Air bleed valve and open valve on vacuum line to take initial vacuum. When
sufficient vacuum is available close vacuum valve and open XV-150302 & XV-
150303. Start Recirculation Pump for FF Effect – III (P-1503) and open manual
valves on transfer line from Recirculation Pump for FF Effect – III (P-1503).
19. Open manual valve on process condensate line and start Thin Stillage vapor by
opening manual valve.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
6. Open manual valve on CIP drain line of Vapor Liquid Separator for FF Standby
Effect (V-1504) and start pump CIP drain Pump (P-1516) (check CIP drain pump
suction before starting). Thin Stillage Feed Tank (T-1501)/ Concentrated Syrup
Tank (T-1505) by opening respective manual valve. Drain the effect completely.
Open manual valve on line across Pump for FF Standby Effect (P-1504) to drain
discharge line.
7. After draining stop CIP drain Pump (P-1516) and close drain valve.
8. Fill the Vapor Liquid Separator (V-1504) with process condensate by opening
manual valve and XV-150401 up to just above normal operating level. Recirculate
this condensate for 30 minutes to 1 hour. And drain it.
9. Ensure Nitric Acid solution is prepared and ready for transfer. Open XV-151201
Solenoid valve and start pump CIP Transfer Pump (P-1515). Open manual valve
allow CIP solution to be filled in Falling Film Standby Effect (H-1504).
10. When level reaches 50-60% in Vapor Liquid Separator for FF Standby Effect (V-
1504), stop CIP Transfer Pump (P-1515), Close manual valve on CIP solution inlet,
and start Recirculation Pump for FF Standby Effect (P-1504). Close manual valve
on CIP solution line.
11. Recirculate the solution through Falling Film standby Effect (H-1504) for 4 Hr.
Stop Recirculation Pump for FF Standby Effect – II (P-1504). Drain Exhaust CIP by
opening CIP drain manual valve as described above. Start CIP drain pump (P-
1516) & transfer CIP solution to Effluent treatment.
12. Ensure Caustic solution is prepared and ready for transfer. Open suction valve and
start CIP Pump (P-1351). Open respective manual valve at CIP Pump (P-1351)
discharge and allow CIP solution to be filled in Falling Film Standby Effect (H-
1504).
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
13. When level reaches 50-60% in Vapor Liquid Separator for FF Standby Effect (V-
1504), start Recirculation Pump for FF Standby Effect (P-1504).
14. Recirculate the solution through Falling Film Standby Effect for 4 hr. Stop
Recirculation Pump for FF Standby Effect (P-1504). Drain Exhaust CIP by opening
CIP drain manual valves as described above. Start CIP drain pump (P-1516) &
transfer CIP solution to Effluent treatment.
15. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Falling Film Standby Effect (H-1504) same way like transfer of CIP solutions,
16. Recirculate water through Falling Film Standby Effect (H-1504) for 1 hrs. Stop
recirculation Pump for FF Standby Effect (P-1504). Drain Exhaust CIP by opening
CIP drain manual valves. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
17. Falling Film Standby Effect (H-1504) is now ready and can be taken online
18. Close Air bleed valve and open valve on vacuum line to take initial vacuum. When
sufficient vacuum is available close vacuum valve and open XV-150402 & XV-
150403. Start Recirculation Pump for FF Standby Effect (P-1504) and open manual
valves on transfer line from Recirculation Pump for FF Standby Effect (P-1504).
19. Open manual valve on process condensate line and start Thin Stillage vapor by
opening manual valve.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
3. Close manual valves on steam line to Forced Circulation Effect – I (H-1505), Thin
Stillage Vapor line from Vapor Liquid Separator for FC Effect - I (V-1505), Steam
condensate line and vent line.
4. Ensure that Forced Circulation Effect – I (H-1505) whose CIP is to be performed is
completely isolated from rest of the system.
5. Stop Recirculation Pump for FC Effect – I (P-1505) Open manual Air bleed valve
and release the vacuum in the effect. Let this valve remain open till the entire CIP.
6. Start draining the hold up by opening manual valve and by using CIP Drain Pump
(P-1516) to Thin Stillage Feed Tank (T-1501)/ Concentrated Syrup Tank (T-1505).
After removal of hold up close manual valve on CIP drain line and stop CIP Drain
Pump (P-1516).
7. Fill the Vapor Liquid Separator (V-1505) with process condensate by opening
manual valve up to just above normal operating level. Recirculate this condensate
for 30 minutes to 1 hour. And drain it.
8. Open manual valve on Nitric CIP solution line and Start filling Vapor Liquid
Separator for FC Effect - I (V-1505) by Nitric CIP solution by using CIP Transfer
Pump (P-1515). When level in Vapor Liquid Separator for FC Effect - I (V-1505)
reaches 30-40% stop filling Nitric CIP solution by closing respective manual valve.
Start Recirculation Pump for FC Effect – I (P-1505) and Recirculate the liquid for 3-
4 hrs.
9. Drain Exhaust CIP by opening CIP drain manual. Start CIP drain pump (P-1516) &
transfer CIP solution to Effluent treatment.
10. Procedure in Step 5 and 6 explained above should be repeated with caustic CIP
solution also.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
11. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Forced Circulation Effect – I (H-1505) same way like transfer of CIP solution.
12. Recirculate water through Forced Circulation Effect – I (H-1505) for 1 hrs. Stop
Recirculation Pump for FC Effect – I (P-1505). Drain Exhaust CIP by opening CIP
drain manual valves. Start CIP drain pump (P-1516) & transfer CIP solution to
Effluent treatment.
13. Forced Circulation Effect – I (H-1505) is now ready and can be taken online.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
6. Stop Recirculation Pump for FC Effect – II (P-1506). Open manual Air bleed
valve and release the vacuum in the effect. Let this valve remain open till the
entire CIP.
7. Start draining the hold up by opening manual valve and by using CIP Drain
Pump (P-1516) to tank Thin Stillage Feed Tank (T-1501)/ Concentrated Syrup
Tank (T-1505). After removal of hold up close manual valve on CIP drain line
and stop CIP Drain Pump (P-1516).
8. Fill the Vapor Liquid Separator (V-1506) with process condensate by opening
manual valve up to just above normal operating level. Recirculate this
condensate for 30 minutes to 1 hour. And drain it.
9. Open manual valve on Nitric CIP solution line and Start filling the Vapor
Liquid Separator for FC Effect - II (V-1506) by Nitric CIP solution by using CIP
Transfer Pump (P-1515). When level in Vapor Liquid Separator for FC Effect - II
(V-1506) reaches 30-40% stop filling Nitric CIP solution by closing respective
manual valve. Start Recirculation Pump for FC Effect – II (P-1506) and
Recirculate the liquid for 3-4 hrs.
10. Drain Exhaust CIP by opening CIP drain manual. Start CIP drain pump (P-
1516) & transfer CIP solution to Effluent treatment.
11. Procedure in Step 5 and 6 explained above should be repeated with caustic CIP
solution also.
12. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Forced Circulation Effect – II (H-1506) same way like transfer of CIP solution.
13. Recirculate water through Forced Circulation Effect – II (H-1506) for 1 hrs. Stop
Recirculation Pump for FC Effect – II (P-1506). Drain Exhaust CIP by opening
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
CIP drain manual valves. Start CIP drain pump (P-1516) & transfer CIP
solution to Effluent treatment.
14. Forced Circulation Effect – II (H-1506) is now ready and can be taken online.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
8. Open manual valve on Nitric CIP solution line and Start filling the Vapor
Liquid Separator for FC Standby Effect (V-1507) by Nitric CIP solution by using
CIP Transfer Pump (P-1515). When level in Vapor Liquid Separator for FC
Standby Effect (V-1507) reaches 30-40%, stop filling Nitric CIP solution by
closing respective manual valve. Start Recirculation Pump for FC Standby
Effect (P-1507) and Recirculate the liquid for 3-4 hrs.
9. Drain Exhaust CIP by opening CIP drain manual. Start CIP drain pump (P-
1516) & transfer CIP solution to Effluent treatment.
10. Procedure in Step 5 and 6 explained above should be repeated with caustic CIP
solution also.
11. After this take water in any of the CIP tank T-1506 / T-1351, and transfer it to
Forced Circulation Standby Effect (H-1507) same way like transfer of CIP
solution.
12. Recirculate water through Forced Circulation Standby Effect (H-1507) for 1 hrs.
Stop Recirculation Pump for FC Standby Effect (P-1507). Drain Exhaust CIP by
opening CIP drain manual valves. Start CIP drain pump (P-1516) & transfer
CIP solution to Effluent treatment.
13. Forced Circulation Standby Effect (H-1507) is now ready and can be taken
online.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Sr. Frequency of
Parameters
No. analysis
1 Vapor Liquid Separator For FF Effect – I (V-1501), total solids Once a day
2 Vapor Liquid Separator For FF Effect – II (V-1502), total solids Once a day
3 Vapor Liquid Separator For FF Effect – III (V-1503), total solids Once a day
5 Vapor Liquid Separator For FC Effect – I (V-1505), Total solids Once a day
6 Vapor Liquid Separator For FC Effect – Ii (V-1506), Total solids Once a day
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Sr. Frequency of
Parameters
No. analysis
Vapor Liquid Separator For FC Effect – I (V-1505), Specific
12 Every 2 hours
Gravity & Brix
Vapor Liquid Separator For FC Effect – II (V-1506), Specific
13 Every 2 hours
Gravity & Brix
Vapor Liquid Separator For FC Standby Effect (V-1507),
14 Every 2 hours
Specific Gravity & Brix
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
3.0.7. TROUBLESHOOTING
In this section some common cases were considered which guides the operating
personnel to arrive at the solution; troubles apart from the mentioned cases may also
occur, operator has to take appropriate action accordingly.
Operators should check the heat exchanger condensate levels during their normal,
routine rounds of the evaporator. Operators should also become familiar with the
normal evaporator temperature and pressure profile. Many times variations in the
pressure/temperature profile will be the first indication of an ensuing upset.
Important sources of information are the temperature differences between the heating
elements as these can be an indication of abnormal operation. Adequate performance
of the entire evaporator depends most heavily on maintaining a proper
temperature/pressure distribution profile.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
PART – IV
PROCESS SHUTDOWN
AND
PROCESS START-UP
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1. Inform boiler house regarding the stoppage of steam in all sections of the
plant.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
19. Start Process Condensate Pump – 2 (P-1510); ensure level indicator and controller
LIC-150801 in AUTO mode. Take Flow Totaliser and Indicator FQI-150801 in
AUTO mode.
20. Ensure level in Steam Condensate Tank (T-1504).
21. Start Steam Condensate Pump (P-1511). Ensure level indicator and controller LIC-
150901 in AUTO mode.
22. Thin Stillage Vapor will start flowing to Mash Column (C-1401).
23. Gradually increase steam to respective Falling Film Effect H-1501/H-1502. Take
Flow Totaliser Indicator and Controller FQIC-150901 in AUTO mode.
24. Gradually increase steam to respective Forced Circulation Effect H-1505/H-1506.
Take Flow Totaliser Indicator and Controller FQIC-150501 in AUTO mode.
25. Start Concentrated Syrup Transfer Pump (P-1512) based on the syrup flow path
status. And line out Concentrated Syrup to Concentrated Syrup Tank (T-1505).
26. Ensure Density Indicator and Controller DIC-15601 is in AUTO mode with Flow
Totaliser Indicator and Controller FQIC-150601 in CAS mode.
27. Monitor Vacuum and level in evaporators.
28. Establish Thin Stillage Feed Tank (T-1501), Concentrated Syrup Tank (T-1505) and
CIP Tank (T-1506) tank circulation.
29. Start Concentrated Syrup Pump (P-1514A/B). Ensure Level Indicator and
Controller LIC-151101 in AUTO mode.
30. Maintain all parameters are as per standard operating parameters mentioned in
section “3.0.3 PROCESS PARAMETERS” of this manual.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
18. Start Process Condensate Pump – 2 (P-1510); ensure level indicator and controller
LIC-150801 in AUTO mode. Take Flow Totaliser and Indicator FQI-150801 in
AUTO mode.
19. Ensure level in Steam Condensate Tank (T-1504).
20. Start Steam Condensate Pump (P-1511). Ensure level indicator and controller LIC-
150901 in AUTO mode.
21. Thin Stillage Vapor will start flowing to Mash Column (C-1401).
22. Gradually increase steam to respective Falling Film Effect H-1501/H-1502. Take
Flow Totaliser Indicator and Controller FQIC-150901 in AUTO mode.
23. Gradually increase steam to respective Forced Circulation Effect H-1505/H-1506.
Take Flow Totaliser Indicator and Controller FQIC-150501 in AUTO mode.
24. Start Concentrated Syrup Transfer Pump (P-1512) based on the syrup flow path
status. And line out Concentrated Syrup to Concentrated Syrup Tank (T-1505).
25. Ensure Density Indicator and Controller DIC-15601 is in AUTO mode with Flow
Totaliser Indicator and Controller FQIC-150601 in CAS mode.
26. Monitor Vacuum and level in evaporators.
27. Establish Thin Stillage Feed Tank (T-1501), Concentrated Syrup Tank (T-1505) and
CIP Tank (T-1506) tank circulation.
28. Start Concentrated Syrup Pump (P-1514A/B). Ensure Level Indicator and
Controller LIC-151101 in AUTO mode.
29. Maintain all parameters are as per standard operating parameters mentioned in
section “3.0.3 PROCESS PARAMETERS” of this manual.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
18. Start Process Condensate Pump – 2 (P-1510); ensure level indicator and controller
LIC-150801 in AUTO mode. Take Flow Totaliser and Indicator FQI-150801 in
AUTO mode.
19. Ensure level in Steam Condensate Tank (T-1504).
20. Start Steam Condensate Pump (P-1511). Ensure level indicator and controller LIC-
150901 in AUTO mode.
21. Thin Stillage Vapor will start flowing to Mash Column (C-1401).
22. Gradually increase steam to respective Falling Film Effect H-1501/H-1502. Take
Flow Totaliser Indicator and Controller FQIC-150901 in AUTO mode.
23. Gradually increase steam to respective Forced Circulation Effect H-1505/H-1506.
Take Flow Totaliser Indicator and Controller FQIC-150501 in AUTO mode.
24. Start Concentrated Syrup Transfer Pump (P-1512) based on the syrup flow path
status. And line out Concentrated Syrup to Concentrated Syrup Tank (T-1505).
25. Ensure Density Indicator and Controller DIC-15601 is in AUTO mode with Flow
Totaliser Indicator and Controller FQIC-150601 in CAS mode.
26. Monitor Vacuum and level in evaporators.
27. Establish Thin Stillage Feed Tank (T-1501), Concentrated Syrup Tank (T-1505) and
CIP Tank (T-1506) tank circulation.
28. Start Concentrated Syrup Pump (P-1514A/B). Ensure Level Indicator and
Controller LIC-151101 in AUTO mode.
29. Maintain all parameters are as per standard operating parameters mentioned in
section “3.0.3 PROCESS PARAMETERS” of this manual.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
1. Inform boiler house regarding the stoppage of steam in all sections of the plant.
2. Take steam flow control valve FCV-150901 in MAN mode and change set point to
zero.
3. Take steam flow control valve FCV-150501 in MAN mode and change set point to
zero.
4. Monitor all the evaporation effect and tank levels.
5. Ensure and stop thin Stillage feed to respective Vapor Liquid separator for FF
Effect – I (V-1501), Vapor Liquid separator for FF Effect – II (V-1502), Vapor Liquid
separator for FF Effect – III (V-1503), Vapor Liquid separator for FF Standby Effect
(V-1504), Vapor Liquid separator for FC Effect – I (V-1505), Vapor Liquid separator
for FC Effect – II (V-1506) and Vapor Liquid Separator for FC Standby Effect (V-
1507) under operating mode through flow totalizer and indicator FQI-151101.
6. Ensure respective Recirculation pump for FF Effect – I (P-1501), Recirculation
pump for FF Effect – II (P-1502), Recirculation pump for FF Effect – III (P-1503),
Recirculation pump for FF Standby Effect (P-1504), Recirculation pump for FC
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Separator for FC Effect – II (V-1506) & Vapor Liquid Separators for FC Standby
Effect (V-1507) through flow totalizer and indicator FQI-151101 under operating
mode.
13. Ensure sufficient level in respective Vapor Liquid Separators for FF Effect - I (V-
1501), Vapor Liquid Separators for FF Effect - II (V-1502), Vapor Liquid Separators
for FF Effect - III (V-1503), Vapor Liquid Separators for FF Standby Effect (V-1504),
Vapor Liquid Separators for FC Effect – I (V-1505), Vapor Liquid Separator for FC
Effect – II (V-1506) & Vapor Liquid Separators for FC Standby Effect (V-1507)
under operating mode. Start respective circulation pumps Recirculation Pump for
FF Effect – I (P-1501), Recirculation Pump for FF Effect - II (P-1502), Recirculation
Pump for FF Effect - III (P-1503), Recirculation Pump for FF Standby Effect (P-
1504), Recirculation Pump for FC Effect - I (P-1505), Recirculation pump for FC
Effect – II (P-1506) and Recirculation Pump for FC Standby Effect (P-1507) under
operating mode and establish the circulation.
14. Gradually open steam flow control valve FCV-150901 to respective Falling Film
Effect H-1501/H-1502 in MAN mode as per falling film evaporators operating
Mode.
15. Gradually open steam flow control valve FCV-150501 to respective Forced
Circulation Effect H-1505/H-1506 in MAN mode as per forced circulation
evaporators operating Mode.
16. Ensure flow of steam condensate from respective Falling Film Effect H-1501/H-
1502 and Forced Circulation Effect H-1505/H-1506.
17. Thin Stillage Vapor will start condensing on shell side of Falling Film Effect – II
(H-1502), Falling Film Effect – III (H-1503), Falling Film standby Effect (H-1504),
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Forced Circulation Effect – II (H-1506) and Forced Circulation standby Effect (H-
1507) depending upon operating Mode of evaporators.
18. Ensure flow of evaporation condensate from Falling Film Effect – II (H-1502),
Falling Film Effect – III (H-1503), Falling Film standby Effect (H-1504), Forced
Circulation Effect – II (H-1506) and Forced Circulation standby Effect (H-1507)
depending upon operating Mode of evaporators.
19. Ensure level in Process Condensate Tank – 1 (T-1502).
20. Start Process Condensate Pump - 1 (P-1509); ensure level indicator and controller
LIC-151001 in AUTO mode.
21. Ensure level in Process Condensate Tank – 2 (T-1503).
22. Start Process Condensate Pump – 2 (P-1510); ensure level indicator and controller
level indicator and controller LIC-150801 in AUTO mode. Take Flow Totaliser and
Indicator FQI-150801 in AUTO mode.
23. Ensure level in Steam Condensate Tank (T-1504).
24. Start Steam Condensate Pump (P-1511). Ensure level indicator and controller LIC-
150901 in AUTO mode.
25. Thin Stillage Vapor will start flowing to Mash Column (C-1401).
26. Gradually increase steam to respective Falling Film Effect H-1501/H-1502. Take
Flow Totaliser Indicator and Controller FQIC-150901 in AUTO mode.
27. Gradually increase steam to H-1505/H-1506. Take Flow Totaliser Indicator and
Controller FQIC-150501 in AUTO mode.
28. Start Concentrated Syrup Transfer Pump (P-1512) based on the syrup flow path
status. And line out Concentrated Syrup to Concentrated Syrup Tank (T-1505).
29. Ensure Density Indicator and Controller DIC-15601 is in AUTO mode with Flow
Totaliser Indicator and Controller FQIC-150601 in CAS mode.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Apart from emergency shut down like power failure, cooling water failure, steam
failure and instrument air failure as mentioned earlier, there are ‘n’ number of factors,
which may lead to pre planned plant shut down for short duration till the affecting
factor will get re-normalized.
In this SOP it is assumed that power, cooling water, steam and instrument air and
other necessary utilities are available for safe short shut down of the plant. It is also
assumed that the shutdown is not more than 8 hrs. If the shutdown is more than 8 hrs,
follow normal plant shut down procedure where it is necessary to empty out the
tanks.
Based on the leading factor for plant shut down, operator has to take appropriate and
safe actions accordingly.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
5. Stop Thin Stillage feed to respective Vapor Liquid Separator for FF Effect – I (V-
1501), Vapor Liquid Separator for FF Effect – II (V-1502), Vapor Liquid Separator
for FF Effect – III (V-1503), Vapor Liquid Separator for FF Standby Effect (V-1504),
Vapor Liquid Separator for FC Effect – I (V-1505), Vapor Liquid Separator for FC
Effect – II (V-1506) and Vapor Liquid Separator for FC Standby Effect (V-1507)
under operating mode through flow totalizer and indicator FQI-151101.
6. Keep running all respective evaporation recirculation pumps ( Falling Film Effect –
I (H-1501), Falling Film Effect – II (H-1502), Falling Film Effect – III (H-1503),
Falling Film Standby Effect (H-1504), Forced Circulation Effect – I (H-1505), Forced
Circulation Effect – II (H-1506) and Forced Circulation Standby Effect (H-1507)) as
per operating mode.
7. Keep Evaporation vacuum pump (P-1513A/B) running, if it is necessary to stop
vacuum pump, stop vacuum pump after 1 hrs of stopping steam to evaporation
section.
8. Keep cooling water system running, as it is required.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
under operating mode. Start respective circulation pumps Recirculation Pump for
FF Effect – I (P-1501), Recirculation Pump for FF Effect - II (P-1502), Recirculation
Pump for FF Effect - III (P-1503), Recirculation Pump for FF Standby Effect (P-
1504), Recirculation Pump for FC Effect - I (P-1505), Recirculation pump for FC
Effect – II (P-1506) and Recirculation Pump for FC Standby Effect (P-1507) under
operating mode and establish the circulation.
13. Gradually open steam flow control valve FCV-150901 to respective Falling Film
Effect H-1501/H-1502 in MAN mode as per falling film evaporators operating
Mode.
14. Gradually open steam flow control valve FCV-150501 to respective Forced
Circulation Effect H-1505/H-1506 in MAN mode as per forced circulation
evaporators operating Mode.
15. Ensure flow of steam condensate from respective Falling Film Effect H-1501/H-
1502 and Forced Circulation Effect H-1505/H-1506.
16. Thin Stillage Vapor will start condensing on shell side of Falling Film Effect – II
(H-1502), Falling Film Effect – III (H-1503), Falling Film standby Effect (H-1504),
Forced Circulation Effect – II (H-1506) and Forced Circulation standby Effect (H-
1507) depending upon operating Mode of evaporators.
17. Ensure flow of evaporation condensate from Falling Film Effect – II (H-1502),
Falling Film Effect – III (H-1503), Falling Film standby Effect (H-1504), Forced
Circulation Effect – II (H-1506) and Forced Circulation standby Effect (H-1507)
depending upon operating Mode of evaporators.
18. Ensure level in Process Condensate Tank – 1 (T-1502).
19. Start Process Condensate Pump - 1 (P-1509); ensure level indicator and controller
LIC-151001 in AUTO mode.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Long duration shut down is generally planned shutdown for any reason there are
some planned maintenance jobs, which are to be carried out during shut down;
jobs like hot jobs, vessel entries, and cold jobs too.
Following are the steps involved while taking long duration shutdown
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
14. Close all manual valves on steam header to all users. Stop steam to the plant. Drain
all steam headers by opening respective bypass valves on steam traps.
15. Stop Evaporation Vacuum Pump (P-1513A/B) after 2 hrs after stopping steam to
evaporation plant.
16. Stop cooling water to individual users and stop cooling water pumps after 1 hrs
after stopping vacuum pumps.
17. Open air bleed valves on pressure control valve PCV-150801 and break the
vacuum completely. Close air bleed valve after ensuring the system equalization
with atmosphere.
18. Close manual valves on sealing water to respective pumps.
19. Stop instrument air compressor.
20. Drain the whole system. Drain the cooling water holdup.
Note:-
If it is necessary to have completed shut down of the plant and all tanks needs
to be emptied out.
If the plant shutdown is planned more than 1 month it is advisable to drain
cooling waterside of heat exchangers by opening dummy flanges.
Break the vacuum completely and equalizing with atmosphere Pressure.
Empty out all tanks in evaporation section.
Perform CIP for Plate type heat exchanger and evaporator.
Flush all lines with water and drain completely and open the all pumps and
evaporator drain valve.
Ensure all tanks / PHEs / lines emptied out completely.
Isolate all equipment by manual valves.
All safety norms to be follow before starting any hot / cold job after plant shutdown.
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
Separators for FF Effect - III (V-1503), Vapor Liquid Separators for FF Standby
Effect (V-1504), Vapor Liquid Separators for FC Effect – I (V-1505), Vapor
Liquid Separator for FC Effect – II (V-1506) & Vapor Liquid Separators for FC
Standby Effect (V-1507) under operating mode. Start respective circulation
pumps Recirculation Pump for FF Effect – I (P-1501), Recirculation Pump for FF
Effect - II (P-1502), Recirculation Pump for FF Effect - III (P-1503), Recirculation
Pump for FF Standby Effect (P-1504), Recirculation Pump for FC Effect - I (P-
1505), Recirculation pump for FC Effect – II (P-1506) and Recirculation Pump
for FC Standby Effect (P-1507) under operating mode and establish the
circulation.
16. Gradually open steam flow control valve FCV-150901 to respective Falling Film
Effect H-1501/H-1502 in MAN mode as per falling film evaporators operating
Mode.
17. Gradually open steam flow control valve FCV-150501 to respective Forced
Circulation Effect H-1505/H-1506 in MAN mode as per forced circulation
evaporators operating Mode.
18. Ensure flow of steam condensate from respective Falling Film Effect H-
1501/H-1502 and Forced Circulation Effect H-1505/H-1506.
19. Thin Stillage Vapor will start condensing on shell side of Falling Film Effect –
II (H-1502), Falling Film Effect – III (H-1503), Falling Film standby Effect (H-
1504), Forced Circulation Effect – II (H-1506) and Forced Circulation standby
Effect (H-1507) depending upon operating Mode of evaporators.
20. Ensure flow of evaporation condensate from Falling Film Effect – II (H-1502),
Falling Film Effect – III (H-1503), Falling Film standby Effect (H-1504), Forced
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA
34. Start Concentrated Syrup Pump (P-1514A/B). Ensure level indicator and
controller LIC-151101 in AUTO mode.
35. Maintain all parameters are as per standard operating parameters mentioned in
section “3.0.3 PROCESS PARAMETERS” of this manual..
-------------------XXXX------------------
THIS DOCUMENT IS THE PROPERTY OF PRAJ INDUSTRIES LTD., INDIA AND SHOULD NOT BE REPRODUCED WITHOUT WRITTEN
CO NFI D E N TI A L CONSENT FROM,”PRAJ INDUSTRIES LTD, “PRAJ HOUSE”, BAVDHAN, PUNE 411021, INDIA