Criticool FC: Cooling Capacity 107kW 1571kW Free Cooling Capacity 119kW 1753kW
Criticool FC: Cooling Capacity 107kW 1571kW Free Cooling Capacity 119kW 1753kW
CRITICOOL FC
Cooling Capacity:107kW~1571kW
2
Unit Identification
Refrigerant Type
R134=R134a
R407=R407c
R22=R22
Compressor quantity
Compressor type:
V-Dual Screw Compressor
3
Features
Continuous running
Free cooling
365 days a year, 24 hours a day continuous uninterrupted
Patented three-way adjustment technology can realize the
operation. State-of-the-art computerized control system fully
"free cooling" function of the chiller. the free cooling coils are
and automatically monitors the operation status of each
made of special copper tube aluminum-made fins and steel
component of the unit and issues a pre-alarm of potential
plating base of anodized aluminum alloys or sprayed with
faults through the computer expert diagnosis system.
epoxy resin; Thus, the operation cost will be greatly reduced
Corrosion and rust prevention units are all made of anti-
and the service life of such unit will be extended
corrosion and anti-rust materials to adapt to work in a variety
considerably as well. Computer control system according to
of outdoor environments. Galvanized steel base with epoxy
the outdoor ambient temperature and indoor load
resin. The top of the unit is made of stainless steel, with a
requirements automatically regulate the water proportion
clamped-in partition at the bottom and noise and vibration
into the cooling coil, make full use of natural cold source.
isolation material inside. Aluminum frame and panels made
CRITICOOL-FC series dedicated data center air-cooled
of galvanized steel coated PVC.
chiller save running costs by 10% to 60% than the
Reasonable design and easy maintenance Unit design is
comfortable central air-conditioning chiller. It greatly reduces
reasonable, compact structure, easy maintenance;
the operating cost and greatly extends the service life of the
compressor, electric control cabinet, control system and
unit.
related refrigeration components are installed in a separate
space separated from the airflow. All closed system panel
Low-temperature starting and operation
can be disassembled, the unit can work under normal
With the advanced systematic design, special liquid impact
maintenance conditions.
prevention compressor and continuous & stepless
regulating condensing airflow, it will ensure that the system
Compressor
will be stable under high-pressure operation. Low pressure
Compressors are the world famous brand compressor,
start-up control program of the compressor prevents start-
which can realize the cooling regulation of 15%~ 100%.
up liquid shock. Sound system configuration design ensures
high stability under harsh working conditions. In winter -
Electric Control Cabinet
40 ℃, CRITICOOL-FC dedicated to computer room air
The electric control cabinet is installed on the front of the
conditioning can still be started and run normally. (Operation unit, and the door is equipped with a security main switch
at lower ambient temperature requires special measures to and computer control system. Each load is equipped with its
ensure the normal operation of the unit, if necessary, please own air switch, fuse, and contactor. Users no longer need to
contact our technical department.) set up special distribution cabinets for each unit
4
realize the automatic unmanned management of the unit. compressor start times and operation time and so on. The
When the unit starts up, the unit controller first orders the control system has alarm memory function.
pump to start, then starts the unit and no one needs to
start the pump. This option is more important for users who
have insufficient site.
Main display function
Function of ice storage (optional function) Temperature display
Standard double water temperature setting point, in the - In and out of the water temperature at
premise that the unit is not modified, automatically adjust the same time
the outlet water temperature to 4 ℃ / - 8 ℃ (ice storage - Ambient temperature display working status display
conditions) Compressor working status
- condensing fan working status graphic display
Quality management system(ISO9001)
- Manual working status display module provides a huge
Products through design, development, manufacturing,
data storage space, can store the unit operating data such
installation and after-sales service are fully in accordance
as temperature, humidity, high and low hydraulic pressure,
with ISO9001 quality certification system.
etc. The time depends on the sampling interval. And the
data can be uploaded to the monitoring computer for data
Factory tests
analysis purposes.
All the AIRSYS products are fully tested before delivery.
Working pressure display
Each refrigeration and safety component is strictly tested
- Compressor high / low / hydraulic pressure accumulated
and calibrated, filled with refrigerant and refrigeration oil.
working time display
The unit is in a condition ready for operation.
- Compressor refrigeration working time display
- number of compressor starts
- Unit working hours
Alarm display
- The text shows the last 10 alarms and also shows the
year / month / day / hour / minute of the alarm
- Maintenance Guide: A simple analysis of the causes of
the alarm, the specific location and solutions
The main alarm and protection functions
Computer control system for the entire unit provides
comprehensive and accurate alarm and protection, and
fundamentally avoid the damage caused to the unit due to
harsh environment or improper operation.
Condensate fan overload protection
Avoid damage to fan motor due to three-phase voltage
imbalance or phase loss.
Compressor operating high pressure dual protection
High pressure sensors and high pressure protection switch
provide double protection for compressor discharge
5
Automatic detection of the working condition of the electric
Remote network monitoring and
oil heaters, automatic alarm in case of electrical heater
failure to prevent compressor oil loss and liquid group control
compression caused by the low oil temperature. Independent centralized monitoring system
High / low outlet water temperature alarm (IntelliVision2000 system)
Prevent damage to the unit caused by the abnormal water IntelliVision2000, an independent Chinese monitoring
temperature. system developed independently by AIRSYS, has powerful
Low water flow alarm networking monitoring capabilities, with a powerful network
Prevent the system from working under abnormal with flexible and varied forms of connection, and can
conditions due to low or interrupted water flow. monitor at the same time all intelligent control air
Sensor fault alarm conditioning products. IntelliVision2000 run on an ordinary
The computer monitors the pressure and temperature PC, straight league or with the help of modem on the
sensors used by the unit, terminates its operation remote device monitoring and management, all operation
immediately and gives an alarm once there is a failure. parameters of the unit, running state and the alarm can be
High / low supply voltage alarm timely and quickly reflected in the monitor screen. Through
Continuous monitoring of the supply voltage, once beyond authorization user can even remotely turn on or off the
the set range, immediately terminate the unit and issue a unit, modify operation parameters and reset the alarm unit.
corresponding alarm. This unit can be connected to AIRSYS service center, or
the related data sent to repair center where the
experienced engineers can help solve the problems to
Special function shorten the maintenance time, reduce maintenance cost.
AIRSYS provides an open communication protocol for the
Random start
third party to develop monitoring and control system, and
After the unit is powered on, the computer will delay 2 ~ 6
integrate to the BA system, also realize local and group
seconds to start the unit, to avoid power failure recovery,
control function through the upper machine. At the same
and impact to the grid due to multiple units start-up at the
time IntelliVision2000 systems also provide standard
same time.
ACCESS database for the third party to ACCESS the data.
Evaporator start pressure control
In order to avoid compressor oil compression and further
oil loss caused by excessive evaporation pressure when
starting the compressor, the liquid circuit solenoid valve
repeatedly opens and stops several times in response to
the expansion pressure within 2 minutes after starting the
compressor, Until the compressor runs smoothly.
Automatic switch of compressor start-up sequence
According to the length of operation time, the control
system automatically switch start up sequence to extend
the life of the entire unit.
Password protection function
2-level password protection, to prevent illegal modification
of operating parameters, to avoid the unit in abnormal
conditions.
Automatic regulation of outlet water temperature
According to the indoor load changes (lower),
automatically increase the temperature of the water, up to
5 ℃.
6
Remote network monitoring schematic
Wireless connection types Local area network connection type
7
In the mechanical cooling mode, the three-way valve 5 in
Free cooling unit working logic
the figure below is normally opened in the A position and
CRITICOOL-FC series air-cooled chiller has three kinds of
closed in the B position. Backwater directly enters into the
working mode:
evaporator.
Mechanical cooling mode
Partial free cooling mode
Partial free cooling mode
Once the air temperature drops below the return water
Free cooling mode
temperature by 2 ℃, the valve 5 is opened in the B
The unit airflow is organized through a water / air heat
exchanger, followed by a condenser coil. position while A is closed, the water directly enters into the
Backwater is sent to the evaporator before the first use of free cooling coil, is cooled by the outdoor air prior to
outdoor cooling. This precooling stage (free cooling) can evaporator.
use external air to save energy and reduce compressor During the partial cooling mode, the first return water is
workload. In the computer control system management, pre-cooled by free cooling coil, and then cooled by
when the inlet air temperature is lower than the return evaporator driven by compressor system.
water temperature by at least 2 ℃, the free cooling system Free cooling mode
During free cooling mode, the cooling comes only from free
will start to work.
cooling coil.
Mechanical cooling mode
8
Percentage of free cooling functions involved in cooling When the temperature is 2 ℃ lower than the return water
work Basis:
- Ambient air temperature temperature, the trigger point in this area is determined by
- Total cooling load The compressor's trigger point and the fan's trigger point
When the outdoor temperature changes, the relationship can be anywhere in this area. During the transition from
between the cooling capacity of the free cooling system normal to free cooling mode, the compressor continues to
and the compressor cooling capacity. Assume that the operate from the current operating point while decreasing
chilled water from CRITICOOL-FC unit is 5 ° C and the its capacity gradually. From the normal mode of operation
return water temperature is 10 ° C. We can see that when
to the free cooling mode of operation, the fan speed
the required cooling capacity is equal to the rated cooling
capacity, all the free cooling is basically achieved at -3 ° C. increases from the current operating point to the maximum.
And compared with other similar products, this set of The figures below are three typical cities, the equipment at
system can be part of the free cooling function between - full load work, the energy savings compared to one year.
3 ℃ ~ 8 ℃, so as to maximize the use of free cold source. Energy is saved not only in winter but also in summer as
Cooling capacity control during free cooling mode long as the outdoor temperature is 2 ° C below the return
CRITICOOL-FC unit control system has different working water temperature
mode between the free cooling and normal operation.
During normal operation, the CRITICOOL-FC unit, like a Shi Jia Zhuang
Winter Average
normal unit, controls the water temperature by controlling
the capacity of the compressor. Condensation control is
realized by reducing the unit air volume to achieve through
the computer-controlled system to directly drive the
electronic regulator and steplessly adjust the condensing
fan speed.
During free cooling, the control system triggers a free
cooling system when the inlet air temperature is 2 ° C 1
below the return water temperature: the 3-way valve is fully
open and the fan is running at maximum speed for
maximum cooling. Instead of relying on the fan, the Haerbin
condensate control relies on a pressure valve that Winter Average
regulates the condensing pressure by regulating the
coolant in the condensing coil. If the cooling capacity is too
high, the control system will reduce the capacity of the
compressor linearly and, if necessary, switch off the
compressor.
If the capacity is still above the required cooling capacity
when the compressor is switched off, the control system
1
will gradually reduce the fan capacity until all the fans have
been switched off. If the fan is fully closed, the cooling
capacity is still higher than the required cooling capacity as
Shen Yang
the strong wind blows naturally cooling coils, this situation Winter Average
may occur, the control system gradually closes the valve
that controls the natural cooling until the natural cooling
coil is completely bypassed.
The same goes for the transition from a free cooling mode
of operation to a normal mode of operation (mechanical
cooling), except in the opposite order.
Free cooling trigger point 1
9
Technical Data
CRITICOOL-FC.A MD R134a
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2
Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C
Cooling Capacity
Cooling Capacity(1)
kW 328 377 412 466 541 656 705 754 824 878 932 1082 1344 1571
Cooling Capacity(2) kW 364 418 457 517 600 728 783 837 915 975 1035 1201 1492 1744
Free Cooling(3) kW 366 421 460 519 603 732 786 841 919 979 1040 1207 1499 1753
Free Cooling(4) kW 368 423 462 522 606 735 790 845 924 984 1045 1213 1507 1761
Refrigerant R134a
Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 97.7 112.1 122.0 137.2 156.2 195.4 209.8 224.2 244.0 259.2 274.4 312.4 388.8 456.5
Current(1) A 170.9 194.4 207.2 231.5 271.8 341.8 365.3 388.8 414.3 438.6 463.0 543.6 663.6 779.3
Power input(2) kW 99.4 114.1 124.1 139.6 158.9 198.8 213.5 228.1 248.3 263.7 279.2 317.8 395.6 464.4
Current(2) A 176.8 201.1 214.4 239.5 281.3 353.7 378.0 402.3 428.7 453.9 479.1 562.6 686.7 806.4
Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series
Startup current
A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102
Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
Water flow(1) m3/h 56.4 64.8 70.9 80.1 93.0 112.8 121.3 129.7 141.7 151.0 160.3 186.1 231.2 270.2
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2
Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354
Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350
Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600
Net kg 3930 4290 4455 5330 6240 7860 8180 8650 8890 9620 11720 13700 14600 16500
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
10
CRITICOOL-FC.A MD R407c
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2
Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C
Cooling Capacity
Cooling Capacity(1)
kW 312 373 404 470 557 624 685 746 808 874 931 1115 1271 1493
Cooling Capacity(2) kW 346 414 448 522 619 692 760 829 897 970 1034 1237 1411 1657
Free Cooling(3) kW 348 416 451 525 622 696 764 833 901 975 1039 1244 1418 1665
Free Cooling(4) kW 350 418 453 527 625 699 768 837 906 980 1044 1250 1425 1674
Refrigerant R407c
Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 97.5 116.2 126.1 142.8 170.5 195.0 214.2 232.6 251.9 266.8 291.3 347.9 370.3 441.9
Current(1) A 176.7 214.7 227.0 257.0 299.7 353.2 391.7 429.4 453.9 484.7 524.4 611.2 706.5 843.9
Power input(2) kW 99.2 118.2 128.3 145.3 173.5 198.4 217.9 236.6 256.3 271.5 296.4 354.0 376.7 449.6
Current(2) A 182.8 222.2 234.8 266.0 310.1 365.5 405.3 444.4 469.7 501.6 542.6 632.5 731.0 873.3
Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series
Startup current
A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102
Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
water flow(1) m3/h 53.6 64.2 69.5 80.9 95.9 107.3 117.8 128.4 138.9 150.4 160.1 191.7 218.6 256.8
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2
Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354
Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
Width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350
Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600
Net kg 3780 4140 4305 5130 6240 7560 7880 8350 8590 9270 11320 13300 14100 16000
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
11
CRITICOOL-FC.A MD R22
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2
Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C
Cooling Capacity
Cooling Capacity(1)
kW 315 377 408 475 563 630 692 754 816 883 941 1126 1284 1508
Cooling Capacity(2) kW 350 418 453 527 625 699 768 837 906 980 1044 1250 1425 1674
Free Cooling(3) kW 351 421 455 530 628 703 772 841 910 985 1049 1256 1432 1682
Free Cooling(4) kW 353 423 457 533 631 706 776 845 915 990 1054 1262 1440 1691
Refrigerant R22
Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 95.6 113.9 123.6 140.0 167.2 191.2 210 228 247 261.6 285.6 341.1 363.0 433.2
Current(1) A 173.2 210.5 222.5 252.0 293.8 346.3 384 421 445 475.2 514.1 599.3 692.6 827.4
Power input(2) kW 97.3 115.9 125.8 142.4 170.1 194.5 213.7 232.0 251.3 266.2 290.6 347.0 369.3 440.7
Current(2) A 179.2 217.8 230.2 260.8 304.0 358.4 397.4 435.7 460.5 491.7 532.0 620.1 716.7 856.2
Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series
Startup current
A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102
Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
water flow(1) m3/h 54.2 64.8 70.2 81.7 96.8 108.4 119.0 129.7 140.4 151.9 161.8 193.7 220.8 259.4
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2
Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354
Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
Width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350
Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600
Net kg 3780 4140 4305 5130 6240 7560 7880 8350 8590 9270 11320 13300 14100 16000
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
12
CRITICOOL-FC.A LN R134a
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1
Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13
Cooling Capacity
Cooling Capacity(1) kW 107 133 170 242 328 377 412 466 541 672 785
Cooling Capacity(2) kW 118 148 189 269 364 418 457 517 600 746 872
Free Cooling(3) kW 119 149 190 270 366 421 460 519 603 750 876
Free Cooling(4) kW 120 149 191 272 368 423 462 522 606 753 881
Refrigerant R134a
Compressor
number
n. 1 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 34.0 41.2 52.1 73.4 97.7 112.1 122.0 137.2 156.2 194.4 228.2
Current(1) A 57.3 68.7 87.8 124.1 170.9 194.4 207.2 231.5 271.8 331.8 389.7
Power input(2) kW 34.6 41.9 53.0 74.7 99.4 114.1 124.1 139.6 158.9 197.8 232.2
Current(2) A 59.3 71.1 90.8 128.4 176.8 201.1 214.4 239.5 281.3 343.4 403.2
Capacity n. 4 4 4 4 4 4 4 4 4 4 4
regulation series
Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
current
Fan n.
Axil fan number 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 18.4 22.9 29.2 41.7 56.4 64.8 70.9 80.1 93.0 115.6 135.1
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1940 2080 2310 2700 3875 4400 5600 5860 6850 7300 8250
not included)
Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2
Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2
Cooling Capacity
Cooling Capacity(1) kW 340 412 494 538 656 754 932 1082 1344 1571
Cooling Capacity(2) kW 377 457 548 597 728 837 1035 1201 1492 1744
Free Cooling(3) kW 379 460 551 600 732 841 1040 1207 1499 1752
Free Cooling(4) kW 381 462 554 603 735 845 1045 1213 1507 1761
Refrigerant R134a
Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 112.8 128.0 148.2 167.2 195.4 224.2 274.4 312.4 388.8 456.5
Current(1) A 207.1 230.4 267.1 293.8 341.8 388.7 463.0 543.6 663.6 779.3
Power input(2) kW 114.8 130.2 150.8 170.1 198.8 228.1 279.2 317.8 395.5 464.4
Current(2) A 214.3 238.4 276.4 304.0 353.7 402.2 479.1 562.6 686.7 806.4
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series
Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28
13
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 58.5 70.9 85.0 92.5 112.8 129.7 160.3 186.1 231.2 270.2
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4960 6100 6460 7560 7850 8800 11320 13300 14100 16000
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
14
CRITICOOL-FC.A LN R407c
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1
Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13
Cooling Capacity
Cooling Capacity(1) kW 114 137 176 243 312 373 404 470 557 636 746
Cooling Capacity(2) kW 126 152 196 269 346 414 448 522 619 705 829
Free Cooling(3) kW 127 152 197 271 348 416 451 525 622 709 833
Free Cooling(4) kW 128 153 198 272 350 418 453 527 625 713 837
Refrigerant R407c
Compressor 1
number
n. 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 41.2 49.9 57.2 75.6 97.5 116.2 126.1 142.8 170.5 181.5 216.6
Current(1) A 71.2 86.3 105.4 136.3 176.7 214.7 227.0 257.0 299.7 346.3 413.7
Power input(2) kW 41.9 50.7 58.2 76.9 99.2 118.2 128.3 145.3 173.5 184.6 220.4
Current(2) A 73.7 89.3 109.0 141.0 182.8 222.2 234.8 266.0 310.1 358.3 428.1
Capacity regulation n. 4 4 4 4 4 4 4 4 4 4 4
series
Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum current A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
Fan
Axil fan number n. 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 19.6 23.5 30.3 41.7 53.6 64.2 69.5 80.9 95.9 109.3 128.4
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1840 1980 2210 2550 3725 4250 5400 5660 6650 7050 8000
not included)
Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2
Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2
Cooling Capacity
Cooling Capacity(1) kW 366 416 497 557 624 746 941 1115 1271 1493
Cooling Capacity(2) kW 407 462 552 619 692 829 1044 1237 1411 1657
Free Cooling(3) kW 409 464 554 622 696 833 1049 1244 1418 1665
Free Cooling(4) kW 411 466 557 625 699 837 1054 1250 1425 1674
Refrigerant R134a
Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 115.1 130.6 151.2 170.5 195.0 232.4 285.6 341.1 363.0 433.2
Current(1) A 211.2 235.0 272.4 299.7 353.2 429.5 514.1 599.3 692.6 827.4
Power input(2) kW 117.1 132.8 153.8 173.5 198.4 236.4 290.6 347.0 369.3 440.7
Current(2) A 218.6 243.2 281.9 310.1 365.5 444.5 532.0 620.1 716.7 856.2
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series
Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000
15
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 63.0 71.5 85.5 95.9 107.3 128.4 161.8 191.7 218.6 256.8
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4760 5900 6160 7260 7550 8500 11320 13300 14100 16000
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
16
CRITICOOL-FC.A LN R22
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1
Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13
Cooling Capacity
Cooling Capacity(1) kW 115 138 178 245 315 377 408 475 563 642 754
Cooling Capacity(2) kW 128 153 198 272 350 418 453 527 625 713 837
Free Cooling(3) kW 128 154 199 273 351 421 455 530 628 716 841
Free Cooling(4) kW 129 155 200 275 353 423 457 533 631 720 845
Refrigerant R22
Compressor
number
n. 1 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 40.4 48.9 56.1 74.1 95.6 113.9 123.6 140.0 167.2 177.9 212.4
Current(1) kW 69.8 84.6 103.3 133.6 173.2 210.5 222.5 252.0 293.8 339.5 405.6
Power input(2) kW 41.1 49.8 57.1 75.4 97.3 115.9 125.8 142.4 170.1 181.0 216.1
Current(2) kW 72.2 87.5 106.9 138.2 179.2 217.8 230.2 260.8 304.0 351.3 419.7
Capacity regulation n. 4 4 4 4 4 4 4 4 4 4 4
series
Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum current A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
Fan
Axil fan number n. 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 19.8 23.7 30.6 42.1 54.2 64.8 70.2 81.7 96.8 110.4 129.7
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1840 1980 2210 2550 3725 4250 5400 5660 6650 7050 8000
not included)
Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2
Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2
Cooling Capacity
Cooling Capacity(1) kW 370 420 502 563 630 754 950 1126 1284 1508
Cooling Capacity(2) kW 411 466 557 625 699 837 1055 1250 1425 1674
Free Cooling(3) kW 413 469 560 628 703 841 1060 1256 1432 1682
Free Cooling(4) kW 415 471 563 631 706 845 1065 1262 1440 1691
Refrigerant R134a
Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 112.8 128.0 148.2 167.2 191.2 227.8 280.0 334.4 355.9 424.7
Current(1) A 207.1 230.4 267.1 293.8 346.3 421.1 504.0 587.5 679.0 811.2
Power input(2) kW 114.8 130.2 150.8 170.1 194.5 231.8 284.9 340.2 362.1 432.1
Current(2) A 214.3 238.4 276.4 304.0 358.4 435.8 521.5 607.9 702.6 839.4
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series
Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000
17
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 63.6 72.2 86.3 96.8 108.4 129.7 163.4 193.7 220.8 259.4
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4760 5900 6160 7260 7550 8500 11320 13300 14100 16000
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
18
Mechanical Cooling Capacity/ Compressor input power correction factor table
Gas/water heat exchanger outlet water
temperature℃
5 6 7 8 9 10 11 12 13 14 15
27 1.035/0.85 1.055/0.86 1.106/0.87 1.127/0.88 1.171/0.89 1.203/0.90 1.233/0.91 1.271/0.92 1.317/0.93 1.352/0.94 1.375/0.95
29 1.016/0.88 1.038/0.89 1.071/0.90 1.111/0.91 1.138/0.92 1.172/0.93 1.218/0.94 1.244/0.95 1.291/0.96 1.315/0.97 1.353/0.98
环
31 0.988/0.91 1.020/0.92 1.053/0.93 1.077/0.94 1.121/0.95 1.157/0.96 1.188/0.97 1.216/0.98 1.251/0.99 1.290/1.00 1.331/1.01
境 33 0.960/0.95 1.002/0.96 1.036/0.97 1.061/0.98 1.096/0.99 1.125/1.00 1.159/1.01 1.202/1.02 1.224/1.03 1.265/1.04 1.298/1.05
温 35 0.941/0.98 0.967/0.99 1.000/1.00 1.044/1.01 1.071/1.02 1.110/1.03 1.129/1.05 1.174/1.06 1.197/1.07 1.240/1.08 1.264/1.09
度 37 0.932/1.01 0.948/1.02 0.982/1.03 1.010/1.04 1.054/1.05 1.078/1.06 1.114/1.07 1.145/1.08 1.170/1.09 1.202/1.10 1.240/1.11
39 0.903/1.05 0.930/1.06 0.964/1.07 0.993/1.08 1.020/1.09 1.046/1.10 1.083/1.11 1.117 /1.12 1.143/1.13 1.177/1.14 1.217/1.15
41 0.884/1.08 0.912/1.09 0.937/1.10 0.958/1.11 1.003/1.13 1.030/1.14 1.053/1.15 1.088/1.17 1.116/1.18 1.152/1.19 1.182/1.20
43 0.855/1.11 0.875/1.12 0.909/1.13 1.941/1.14 0.969/1.15 0.998/1.16 1.037/1.17 1.060/1.18 1.089/1.19 1.147/1.21
1.126/1.20
45 0.826/1.15 0.856/1.16 0.891/1.17 0.923/1.18 0.952/1.19 0.981/1.20 1.007/1.21 1.031/1.22 1.061/1.23 1.101/1.24 1.123/1.25
47 0.806/1.18 0.838/1.19 0.872/1.20 0.888/1.21 0.917/1.22 0.948/1.23 0.976/1.24 1.002/1.25 -- / -- -- / -- -- / --
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.
Maximum water m3/h 73.3 84.3 92.1 104.1 120.9 146.7 157.6 168.6 184.2 196.3 208.4 241.9 300.5 351.3
flow
Model(LN) 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1 400V2 450V2 500V2
Maximum water flow m3/h 25.7 30.9 39.8 54.8 70.4 84.3 91.2 106.2 125.9 143.6 168.6 82.7 93.9 112.2
Model(LN) 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2
Maximum water m3/h 125.9 140.9 168.6 212.4 251.8 287.1 337.2
flow
19
upper unit as shown in the picture below. Due to an
Power requirements
Supply voltage: 380V-3φ-50Hz Supply voltage tolerance: increase of the pump weight, the unit with built-in pump
380V ± 10% has center of gravity offset and need to use φ80 hole on
Power supply: Neutral (zero line), 3-phase 4-wire or 5-wire the lifting ring fixed on the base. The unit with S cabinet
uses φ60 holes on the lifting ring.
Installation spacing
The unit should be installed in a well-ventilated place.Many
units parallel to the same direction should ensure the
installation of two units spacing, the minimum installation
spacing and cabinet size, as follows
Cabinet Number S7-S8 T9,M6-M8 T11,M10 T12,M12
Installation space 1.5 2 2.5 3
side by side
(meter)
Cabinet Number T13 M14-M16 M18-M20 M24
Installation space 3.5 4 5 6
side by side
(meter)
20
Pump work directly from the unit control, to avoid improper
Pump Kit (optional)
use of pumps and units and realize fully automated
AIRSYS heat pump unit can be installed with 1 or 2 pumps
management.
within the unit without changing the size of the unit. For the
Remove the pump installation costs and civil construction
roof area not enough or for the easy installation,
costs.
maintenance and other considerations, this option is very
Piping all use high-quality rubber insulation for thermal
important for the use of units.
insulation.
Save the limited space occupied by the pump on the roof.
The pump noise and vibration are significantly reduced.
No need to set up a separate distribution pump for the
pump and the corresponding control device.
automatically switches pump start-up order to balance
pump kit code is PU, end user can choose a single pump working hours. If the pump in operation fails, the control
or double pump according to the need. system immediately switches on another pump.
Single pump-PU ... / 1 Pump main components
The unit is equipped with a water pump. The work of the 1 or 2 Centrifugal or Ducted Pumps / Water Shut-off Valves
pump is completely computer controlled. / Check Valves / Water Flow Switches (1 per Pump)
Double pump-PU ... / 2 Hydrometer / Constant Pressure Water Tanks (optional) /
The unit is equipped with 2 pumps. 1 pump work during Water Safety Valves(optional) / Direct- Computer-driven
normal work, while the other is in standby mode. According electrical components.
to the two pump working hours computer control system
Technical data
Single Pump PU3/1 PU4/1 PU5/1G PU6/1 PU7/1 PU8/1 PU9/1
Water flow
Minimum m3/h 10 30 40 50 75 75 75
Maximum m /h
3
70 55 75 100 150 150 50
Pump head
* If the above pump flow, lift can not meet the requirements, please contact AIRSYS technical department.
* Due to the internal space constraints of the unit, the selected pump group must be confirmed by AIRSYS technical department.
21
Dimensions
CRITICOOL-FC.M6 dimension(mm)
CRITICOOL-FC.A.MD
Weight(kg)
CRITICOOL-FC.A.MD
22
CRITICOOL-FC.M8B dimensions(mm)
CRITICOOL-FC.A.MD
Model 500V1
Weight(kg)
CRITICOOL-FC.A.MD
Model 500V1
S 875
T 950
U 845
X 845
Y 950
Z 865
23
CRITICOOL-FC.M10B Dimensions(mm)
CRITICOOL-FC.A.MD
Model 600V1
Weight(kg)
CRITICOOL-FC.A.MD
Model 600V1
S 930
T 850
U 850
V 930
S1 680
T1 680
U1 680
V1 640
24
CRITICOOL-FC.M12 Dimensions(mm)
CRITICOOL-FC.A.MD
Weight(kg)
CRITICOOL-FC.A.MD
25
CRITICOOL-FC.M14B Dimensions(mm)
CRITICOOL-FC.A.MD
Model 950V2
Weight(kg)
CRITICOOL-FC.A.MD
Model 950V2
U1 943
V1 923
W1 923
X1 943
Y1 923
Z1 923
W2 1018
X2 1003
Y2 1018
Z2 1003
Total weight 9620
26
CRITICOOL-FC.M16B Dimensions(mm)
CRITICOOL-FC.A.MD
Model 1000V2
Weight(kg)
CRITICOOL-FC.A.MD
Model 1000V2
U1 790
V1 988
W1 1038
X1 1088
Y1 1038
Z1 1038
U2 1023
V2 1023
W2 998
X2 1023
Y2 973
Z2 700
27
CRITICOOL-FC.M18B Dimensions(mm)
CRITICOOL-FC.A.MD
Model 1200V2
Weight(kg)
CRITICOOL-FC.A.MD
Model 1200V2
U1 990
V1 1212
W1 1262
X1 1342
Y1 1262
Z1 1262
U2 1147
V2 1147
W2 1092
X2 1147
Y2 1097
Z2 740
Total weight 13700
28
CRITICOOL-FC.M20B Dimensions(mm)
CRITICOOL-FC.A.MD
Model 1400V2
Weight(kg)
CRITICOOL-FC.A.MD
Model 1400V2
U1 1065
V1 1245
W1 1275
X1 1395
Y1 1245
Z1 1275
U2 1275
V2 1245
W2 1195
X2 1275
Y2 1245
Z2 1145
29
CRITICOOL-FC.M24C Dimensions(mm)
CRITICOOL-FC.A.MD
Model 1600V2
Cabinet number M24C
A 14100
B1 1670
B2 1670
C 1670
D 1850
E 5150
F 2600
1-2 φDN Stainless steel clamp 200
4 φ 21
B System
Weight(kg)
CRITICOOL-FC.A.MD
Model 1600V2
S1 S2 1145
T1 T2 1135
U1 U2 1135
V1 V2 1135
W1 W2 1175
X1 X2 1135
Y1 Y2 1135
Z1 Z2 1105
Total weight 16500
30
CRITICOOL-FC.S7 Dimensions(mm)
CRITICOOL-FC.A LN
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
31
CRITICOOL-FC.S7A Dimensions(mm)
CRITICOOL-FC.A LN
Model 200V1
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
Model 200V1
U 195
V 400
W 400
X 275
Y 445
Z 395
32
CRITICOOL-FC.S8 Dimensions(mm)
CRITICOOL-FC.A LN
Model 250V1
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
Model 250V1
U 205
V 505
W 505
X 275
Y 555
Z 505
33
CRITICOOL-FC.T9A Dimensions(mm)
CRITICOOL-FC.A LN
Rear
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
34
CRITICOOL-FC.T11 Dimensions(mm)
CRITICOOL-FC.A LN
Rear
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
35
CRITICOOL-FC.T12 Dimensions(mm)
CRITICOOL-FC.A LN
Rear
4.Base hole
Weight(kg)
CRITICOOL-FC.A LN
36
CRITICOOL-FC.T13 Dimensions(mm)
CRITICOOL -FC.A.STD
Weight(kg)
CRITICOOL-FC.A LN
37
CRITICOOL-FC.T11*2 Dimensions(mm)
CRITICOOL -FC.A.STD
Model 1000V2
Weight(kg)
CRITICOOL-FC.A LN
Model 1000V2
U 1140
V 1140
W 550
X 1140
Y 1140
Z 550
Total weight 11320
38
CRITICOOL-FC.T12*2 Dimensions(mm)
CRITICOOL-FC.A LN
Weight(kg)
CRITICOOL-FC.A LN
39
CRITICOOL-FC.T13*2 Dimensions(mm)
CRITICOOL-FC.A LN
Model 1600V2
Weight(kg)
CRITICOOL-FC.A LN
Model 1600V2
S 1445
T 1445
U 555
V 555
W 1445
X 1445
Y 555
Z 555
40
41