AIRSYS-P-SC-CRITICOOL-FC-C201309V01.

CRITICOOL FC
Cooling Capacity:107kW~1571kW

Free Cooling Capacity:119kW~1753kW


5, The high degree of automation of the buildings
Introduction accommodating the high-tech equipment, requires chiller
also has advanced automatic control level and short range
As business evolves, data center problems are increasing and remote monitoring capabilities, and is able to ensure
and the pressure and challenges faced by data center the good communication and Coordination with various
managers are growing. In the rapid expansion of the data models of chilled water type room air-conditioning.
center, the most prominent issue is the energy 6, As room air conditioners need to ensure precise indoor
consumption. Data center energy consumption, on the temperature and humidity control for the high-tech
one hand is low energy efficiency, on the other hand is equipment room, Chillers as chilled water source supplied
growing very fast. Therefore, building a green data center to the air conditioners are required to ensure constant
with energy-saving and environment-friendly features has high-precision outlet water temperature control too.
become the consensus of the data center construction The chillers for comfort air conditioning purpose are unable
and users as well as the equipment suppliers. For the to meet the requirement of precision air conditioners as the
energy consumption of the data center in the future, cold source.
AIRSYS specially developed CRITICOOL-FC, a naturally Thus the precision chiller is developed in conformity with
cooled data center air-cooled chiller. the global computer revolution and the telecommunications
CRITICOOL-FC series of dedicated data center air-cooled revolution to provide the reliable and precise cold source
chiller, is designed for data center room, program- for the strict environment required by the high-tech
controlled switch room, computer room and other high - equipment.
precision high - tech equipment locations requiring
precision environment control and has high reliability in CRITICOOL-FC series of air-cooled chiller for data center
line with the technical requirements as special cold use is the achievement of AIRSYS in this particular area
source. after more than 10 years of research and development.
Computer room air conditioning are mainly direct
CRITICOOL-FC series data center air-cooled chiller
evaporative cooling and chilled water cooling. However,
equipped with a variety of models with cooling capacity of
there are many limitations and inconveniences in the
114kW ~ 1493kW, cold range, all models, plus a variety of
installation, operation and maintenance of the direct
options to meet the needs of different users. All units run
evaporative cooing unit, which can only be used in the
by the computer control system monitoring and
small and scattered flat room. In the high-rise building,
management, through the communication interface can
centralized, large-scale computer room, the use of the
be centralized monitored, and have local multi-unit and
chilled water chiller with the special chilled water unit is
cluster control functions via the host system. It is also
the best choice. Due to the special requirements of high-
compatible with all dynamic environmental monitoring
tech equipment such as program-controlled switches and
systems and most BMS intelligent building systems on the
computers for air environment quality, chilled water type
market today. The dedicated CRITICOOL-FC data center
room air conditioners have the following special
has been fully installed and tested in the factory and has
requirements for chiller units:
been filled with refrigerants and refrigeration oils. The end
user Only need to carry on the connection of the
1, High reliability
waterway and the electric circuit, thus the time of on-site
2, Continuous operation, 24 hours a day, 365 days a year installation and debugging is reduced.

3, Steady operation in low temperature while providing Evaporator working conditions:


adequate chilled water +5 ℃ minimum outlet water temperature
4, In winter and transition season room temperature -8 ℃ minimum outlet water temperature by adding Glacial
difference between indoor and outdoor is great, outdoor refrigerant solution
natural cold source is a good choice
-15 ℃ minimum outlet water temperature by adding
, which requires the chiller has a natural cooling function to
glacial refrigerant solution and BRINE kit
save unnecessary power consumption, reduce operating
+20 ℃ maximum water inlet temperature
costs and extend unit life.

2
Unit Identification

Code for Custom Design:3 alphabetic and


numerical code
Separator Character: “.

Refrigerant Type
R134=R134a
R407=R407c
R22=R22

Compressor quantity

Compressor type:
V-Dual Screw Compressor

Model and Capaicty (kW)

3
Features
Continuous running
Free cooling
365 days a year, 24 hours a day continuous uninterrupted
Patented three-way adjustment technology can realize the
operation. State-of-the-art computerized control system fully
"free cooling" function of the chiller. the free cooling coils are
and automatically monitors the operation status of each
made of special copper tube aluminum-made fins and steel
component of the unit and issues a pre-alarm of potential
plating base of anodized aluminum alloys or sprayed with
faults through the computer expert diagnosis system.
epoxy resin; Thus, the operation cost will be greatly reduced
Corrosion and rust prevention units are all made of anti-
and the service life of such unit will be extended
corrosion and anti-rust materials to adapt to work in a variety
considerably as well. Computer control system according to
of outdoor environments. Galvanized steel base with epoxy
the outdoor ambient temperature and indoor load
resin. The top of the unit is made of stainless steel, with a
requirements automatically regulate the water proportion
clamped-in partition at the bottom and noise and vibration
into the cooling coil, make full use of natural cold source.
isolation material inside. Aluminum frame and panels made
CRITICOOL-FC series dedicated data center air-cooled
of galvanized steel coated PVC.
chiller save running costs by 10% to 60% than the
Reasonable design and easy maintenance Unit design is
comfortable central air-conditioning chiller. It greatly reduces
reasonable, compact structure, easy maintenance;
the operating cost and greatly extends the service life of the
compressor, electric control cabinet, control system and
unit.
related refrigeration components are installed in a separate
space separated from the airflow. All closed system panel
Low-temperature starting and operation
can be disassembled, the unit can work under normal
With the advanced systematic design, special liquid impact
maintenance conditions.
prevention compressor and continuous & stepless
regulating condensing airflow, it will ensure that the system
Compressor
will be stable under high-pressure operation. Low pressure
Compressors are the world famous brand compressor,
start-up control program of the compressor prevents start-
which can realize the cooling regulation of 15%~ 100%.
up liquid shock. Sound system configuration design ensures
high stability under harsh working conditions. In winter -
Electric Control Cabinet
40 ℃, CRITICOOL-FC dedicated to computer room air
The electric control cabinet is installed on the front of the
conditioning can still be started and run normally. (Operation unit, and the door is equipped with a security main switch
at lower ambient temperature requires special measures to and computer control system. Each load is equipped with its
ensure the normal operation of the unit, if necessary, please own air switch, fuse, and contactor. Users no longer need to
contact our technical department.) set up special distribution cabinets for each unit

High reliability Noise control


Designed for data center, telecommunications, aerospace, The low-noise unit compressor is installed within the
nuclear and other high-tech industries. All components independent and closed space of the unit so that the
undergo a rigorous testing. Design and manufacturing influence of the noise is reduced to the lowest. The unit uses
process standards are much higher than the standards of low noise fans which have exterior rotor blades and
comfort central air conditioning unit. The product is designed aluminum motor integrated for smooth operation and low
as a single system or as a dual system. When the system is noise. Micro control system regulates fan speed
dual system, one system fails and the other system still has automatically according to the condensing pressure, greatly
50% cooling supply. During one system operation, reduces the noise of the unit.
maintenance personnel can repair another system. When
there are more than one data center precision chiller Control of water pump (optional function)
working as a dedicated cooling source, the multiple units 1 to 2 pumps can be installed in the unit without changing
can achieve local group control function, each unit can work the volume of the unit. The work of the water pump is
as back up for each other to ensure the high reliability of the controlled by the computer. Users are not required to
data center requirements. configure the pump room. This function can help user

4
realize the automatic unmanned management of the unit. compressor start times and operation time and so on. The
When the unit starts up, the unit controller first orders the control system has alarm memory function.
pump to start, then starts the unit and no one needs to
start the pump. This option is more important for users who
have insufficient site.
Main display function
Function of ice storage (optional function) Temperature display
Standard double water temperature setting point, in the - In and out of the water temperature at
premise that the unit is not modified, automatically adjust the same time
the outlet water temperature to 4 ℃ / - 8 ℃ (ice storage - Ambient temperature display working status display
conditions) Compressor working status
- condensing fan working status graphic display
Quality management system(ISO9001)
- Manual working status display module provides a huge
Products through design, development, manufacturing,
data storage space, can store the unit operating data such
installation and after-sales service are fully in accordance
as temperature, humidity, high and low hydraulic pressure,
with ISO9001 quality certification system.
etc. The time depends on the sampling interval. And the
data can be uploaded to the monitoring computer for data
Factory tests
analysis purposes.
All the AIRSYS products are fully tested before delivery.
Working pressure display
Each refrigeration and safety component is strictly tested
- Compressor high / low / hydraulic pressure accumulated
and calibrated, filled with refrigerant and refrigeration oil.
working time display
The unit is in a condition ready for operation.
- Compressor refrigeration working time display
- number of compressor starts
- Unit working hours
Alarm display
- The text shows the last 10 alarms and also shows the
year / month / day / hour / minute of the alarm
- Maintenance Guide: A simple analysis of the causes of
the alarm, the specific location and solutions
The main alarm and protection functions
Computer control system for the entire unit provides
comprehensive and accurate alarm and protection, and
fundamentally avoid the damage caused to the unit due to
harsh environment or improper operation.
Condensate fan overload protection
Avoid damage to fan motor due to three-phase voltage
imbalance or phase loss.
Compressor operating high pressure dual protection
High pressure sensors and high pressure protection switch
provide double protection for compressor discharge

Computer control system pressure.


Compressor low pressure or low oil level alarm
The computer control system of this series of products is
Mainly to prevent bad conditions, due to low pressure or
jointly developed with Carol, Italy, has a number of
lack of oil which lead to burn of the compressor.
adjustable control parameters, working status indication
Compressor motor overload alarm
and alarm information. Operating parameters can be read
To prevent damage caused by unbalanced three-phase
directly from the computer control interface, like high and
voltage, low voltage or phase loss.
low pressure, oil pressure, current, voltage, temperature,
Compressor oil heater fault alarm
water temperature, outdoor unit working hours, the

5
Automatic detection of the working condition of the electric
Remote network monitoring and
oil heaters, automatic alarm in case of electrical heater
failure to prevent compressor oil loss and liquid group control
compression caused by the low oil temperature. Independent centralized monitoring system
High / low outlet water temperature alarm (IntelliVision2000 system)
Prevent damage to the unit caused by the abnormal water IntelliVision2000, an independent Chinese monitoring
temperature. system developed independently by AIRSYS, has powerful
Low water flow alarm networking monitoring capabilities, with a powerful network
Prevent the system from working under abnormal with flexible and varied forms of connection, and can
conditions due to low or interrupted water flow. monitor at the same time all intelligent control air
Sensor fault alarm conditioning products. IntelliVision2000 run on an ordinary
The computer monitors the pressure and temperature PC, straight league or with the help of modem on the
sensors used by the unit, terminates its operation remote device monitoring and management, all operation
immediately and gives an alarm once there is a failure. parameters of the unit, running state and the alarm can be
High / low supply voltage alarm timely and quickly reflected in the monitor screen. Through
Continuous monitoring of the supply voltage, once beyond authorization user can even remotely turn on or off the
the set range, immediately terminate the unit and issue a unit, modify operation parameters and reset the alarm unit.
corresponding alarm. This unit can be connected to AIRSYS service center, or
the related data sent to repair center where the
experienced engineers can help solve the problems to
Special function shorten the maintenance time, reduce maintenance cost.
AIRSYS provides an open communication protocol for the
Random start
third party to develop monitoring and control system, and
After the unit is powered on, the computer will delay 2 ~ 6
integrate to the BA system, also realize local and group
seconds to start the unit, to avoid power failure recovery,
control function through the upper machine. At the same
and impact to the grid due to multiple units start-up at the
time IntelliVision2000 systems also provide standard
same time.
ACCESS database for the third party to ACCESS the data.
Evaporator start pressure control
In order to avoid compressor oil compression and further
oil loss caused by excessive evaporation pressure when
starting the compressor, the liquid circuit solenoid valve
repeatedly opens and stops several times in response to
the expansion pressure within 2 minutes after starting the
compressor, Until the compressor runs smoothly.
Automatic switch of compressor start-up sequence
According to the length of operation time, the control
system automatically switch start up sequence to extend
the life of the entire unit.
Password protection function
2-level password protection, to prevent illegal modification
of operating parameters, to avoid the unit in abnormal
conditions.
Automatic regulation of outlet water temperature
According to the indoor load changes (lower),
automatically increase the temperature of the water, up to
5 ℃.

6
Remote network monitoring schematic
Wireless connection types Local area network connection type

7
In the mechanical cooling mode, the three-way valve 5 in
Free cooling unit working logic
the figure below is normally opened in the A position and
CRITICOOL-FC series air-cooled chiller has three kinds of
closed in the B position. Backwater directly enters into the
working mode:
evaporator.
Mechanical cooling mode
Partial free cooling mode
Partial free cooling mode
Once the air temperature drops below the return water
Free cooling mode
temperature by 2 ℃, the valve 5 is opened in the B
The unit airflow is organized through a water / air heat
exchanger, followed by a condenser coil. position while A is closed, the water directly enters into the
Backwater is sent to the evaporator before the first use of free cooling coil, is cooled by the outdoor air prior to
outdoor cooling. This precooling stage (free cooling) can evaporator.
use external air to save energy and reduce compressor During the partial cooling mode, the first return water is
workload. In the computer control system management, pre-cooled by free cooling coil, and then cooled by
when the inlet air temperature is lower than the return evaporator driven by compressor system.

water temperature by at least 2 ℃, the free cooling system Free cooling mode
During free cooling mode, the cooling comes only from free
will start to work.
cooling coil.
Mechanical cooling mode

8
Percentage of free cooling functions involved in cooling When the temperature is 2 ℃ lower than the return water
work Basis:
- Ambient air temperature temperature, the trigger point in this area is determined by

- Return water temperature the heat load and outdoor temperature.

- Total cooling load The compressor's trigger point and the fan's trigger point

When the outdoor temperature changes, the relationship can be anywhere in this area. During the transition from
between the cooling capacity of the free cooling system normal to free cooling mode, the compressor continues to
and the compressor cooling capacity. Assume that the operate from the current operating point while decreasing
chilled water from CRITICOOL-FC unit is 5 ° C and the its capacity gradually. From the normal mode of operation
return water temperature is 10 ° C. We can see that when
to the free cooling mode of operation, the fan speed
the required cooling capacity is equal to the rated cooling
capacity, all the free cooling is basically achieved at -3 ° C. increases from the current operating point to the maximum.
And compared with other similar products, this set of The figures below are three typical cities, the equipment at
system can be part of the free cooling function between - full load work, the energy savings compared to one year.
3 ℃ ~ 8 ℃, so as to maximize the use of free cold source. Energy is saved not only in winter but also in summer as
Cooling capacity control during free cooling mode long as the outdoor temperature is 2 ° C below the return
CRITICOOL-FC unit control system has different working water temperature
mode between the free cooling and normal operation.
During normal operation, the CRITICOOL-FC unit, like a Shi Jia Zhuang
Winter Average
normal unit, controls the water temperature by controlling
the capacity of the compressor. Condensation control is
realized by reducing the unit air volume to achieve through
the computer-controlled system to directly drive the
electronic regulator and steplessly adjust the condensing
fan speed.
During free cooling, the control system triggers a free
cooling system when the inlet air temperature is 2 ° C 1
below the return water temperature: the 3-way valve is fully
open and the fan is running at maximum speed for
maximum cooling. Instead of relying on the fan, the Haerbin
condensate control relies on a pressure valve that Winter Average
regulates the condensing pressure by regulating the
coolant in the condensing coil. If the cooling capacity is too
high, the control system will reduce the capacity of the
compressor linearly and, if necessary, switch off the
compressor.
If the capacity is still above the required cooling capacity
when the compressor is switched off, the control system
1
will gradually reduce the fan capacity until all the fans have
been switched off. If the fan is fully closed, the cooling
capacity is still higher than the required cooling capacity as
Shen Yang
the strong wind blows naturally cooling coils, this situation Winter Average
may occur, the control system gradually closes the valve
that controls the natural cooling until the natural cooling
coil is completely bypassed.
The same goes for the transition from a free cooling mode
of operation to a normal mode of operation (mechanical
cooling), except in the opposite order.
Free cooling trigger point 1

9
Technical Data
CRITICOOL-FC.A MD R134a
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2

Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C

Cooling Capacity
Cooling Capacity(1)
kW 328 377 412 466 541 656 705 754 824 878 932 1082 1344 1571
Cooling Capacity(2) kW 364 418 457 517 600 728 783 837 915 975 1035 1201 1492 1744

Free Cooling(3) kW 366 421 460 519 603 732 786 841 919 979 1040 1207 1499 1753

Free Cooling(4) kW 368 423 462 522 606 735 790 845 924 984 1045 1213 1507 1761

Refrigerant R134a

Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 97.7 112.1 122.0 137.2 156.2 195.4 209.8 224.2 244.0 259.2 274.4 312.4 388.8 456.5

Current(1) A 170.9 194.4 207.2 231.5 271.8 341.8 365.3 388.8 414.3 438.6 463.0 543.6 663.6 779.3

Power input(2) kW 99.4 114.1 124.1 139.6 158.9 198.8 213.5 228.1 248.3 263.7 279.2 317.8 395.6 464.4

Current(2) A 176.8 201.1 214.4 239.5 281.3 353.7 378.0 402.3 428.7 453.9 479.1 562.6 686.7 806.4

Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series

Startup current
A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102

Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
Water flow(1) m3/h 56.4 64.8 70.9 80.1 93.0 112.8 121.3 129.7 141.7 151.0 160.3 186.1 231.2 270.2
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2

Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354

Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350

Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600

Net kg 3930 4290 4455 5330 6240 7860 8180 8650 8890 9620 11720 13700 14600 16500
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

10
CRITICOOL-FC.A MD R407c
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2

Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C

Cooling Capacity
Cooling Capacity(1)
kW 312 373 404 470 557 624 685 746 808 874 931 1115 1271 1493
Cooling Capacity(2) kW 346 414 448 522 619 692 760 829 897 970 1034 1237 1411 1657

Free Cooling(3) kW 348 416 451 525 622 696 764 833 901 975 1039 1244 1418 1665

Free Cooling(4) kW 350 418 453 527 625 699 768 837 906 980 1044 1250 1425 1674

Refrigerant R407c

Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 97.5 116.2 126.1 142.8 170.5 195.0 214.2 232.6 251.9 266.8 291.3 347.9 370.3 441.9

Current(1) A 176.7 214.7 227.0 257.0 299.7 353.2 391.7 429.4 453.9 484.7 524.4 611.2 706.5 843.9

Power input(2) kW 99.2 118.2 128.3 145.3 173.5 198.4 217.9 236.6 256.3 271.5 296.4 354.0 376.7 449.6

Current(2) A 182.8 222.2 234.8 266.0 310.1 365.5 405.3 444.4 469.7 501.6 542.6 632.5 731.0 873.3

Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series
Startup current

A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102

Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
water flow(1) m3/h 53.6 64.2 69.5 80.9 95.9 107.3 117.8 128.4 138.9 150.4 160.1 191.7 218.6 256.8
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2

Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354

Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
Width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350

Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600

Net kg 3780 4140 4305 5130 6240 7560 7880 8350 8590 9270 11320 13300 14100 16000
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

11
CRITICOOL-FC.A MD R22
Model 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2

Cabinet number M6A M6C M6C M8B M10B M12A M12B M12C M12C M14B M16B M18B M20B M24C

Cooling Capacity
Cooling Capacity(1)
kW 315 377 408 475 563 630 692 754 816 883 941 1126 1284 1508
Cooling Capacity(2) kW 350 418 453 527 625 699 768 837 906 980 1044 1250 1425 1674

Free Cooling(3) kW 351 421 455 530 628 703 772 841 910 985 1049 1256 1432 1682

Free Cooling(4) kW 353 423 457 533 631 706 776 845 915 990 1054 1262 1440 1691

Refrigerant R22

Compressor
number
n. 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Power input(1) kW 95.6 113.9 123.6 140.0 167.2 191.2 210 228 247 261.6 285.6 341.1 363.0 433.2

Current(1) A 173.2 210.5 222.5 252.0 293.8 346.3 384 421 445 475.2 514.1 599.3 692.6 827.4

Power input(2) kW 97.3 115.9 125.8 142.4 170.1 194.5 213.7 232.0 251.3 266.2 290.6 347.0 369.3 440.7

Current(2) A 179.2 217.8 230.2 260.8 304.0 358.4 397.4 435.7 460.5 491.7 532.0 620.1 716.7 856.2

Capacity regulation n. 4 4 4 4 4 8 8 8 8 8 8 8 8 8
series

Startup current
A 356.7 478 478 660 749 713 835 956 956 1138 1320 1498 1765 1765
Maximum current A 285 328 328 401 461 570 450 621 579 622.8 758 887 974 1102

Fan
Axil fan number n. 6 6 6 8 10 12 12 12 12 14 16 18 20 24
Air flow m3/h 116000 144000 144000 192000 240000 232000 262000 288000 288000 336000 384000 432000 480000 540000
Power kW 9 13.2 13.2 17.6 22 18 22.2 26.4 26.4 30.8 35.2 39.6 44 52.8
Current A 28.8 27 27 36 45 38.4 46.2 54 54 63 70 81 90 108
Refrigerant-water
heat exchanger
water flow(1) m3/h 54.2 64.8 70.2 81.7 96.8 108.4 119.0 129.7 140.4 151.9 161.8 193.7 220.8 259.4
Pressure drop(1) kPa 47.1 46.9 55 30.5 46.6 46.6 55 76.2 80 75 65 76 75 76.2

Water volume l 95 135 135 222 222 222 206 206 206 252 252 295 295 354

Dimension and
Weight
Length mm 3410 3710 3710 4790 5870 6450 6750 7050 7050 8130 9210 10290 11370 14100
Width mm 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350 2350

Height mm 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600 2600

Net kg 3780 4140 4305 5130 6240 7560 7880 8350 8590 9270 11320 13300 14100 16000
weight(options
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

12
CRITICOOL-FC.A LN R134a
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1

Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13

Cooling Capacity
Cooling Capacity(1) kW 107 133 170 242 328 377 412 466 541 672 785
Cooling Capacity(2) kW 118 148 189 269 364 418 457 517 600 746 872
Free Cooling(3) kW 119 149 190 270 366 421 460 519 603 750 876
Free Cooling(4) kW 120 149 191 272 368 423 462 522 606 753 881
Refrigerant R134a

Compressor
number
n. 1 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 34.0 41.2 52.1 73.4 97.7 112.1 122.0 137.2 156.2 194.4 228.2
Current(1) A 57.3 68.7 87.8 124.1 170.9 194.4 207.2 231.5 271.8 331.8 389.7
Power input(2) kW 34.6 41.9 53.0 74.7 99.4 114.1 124.1 139.6 158.9 197.8 232.2
Current(2) A 59.3 71.1 90.8 128.4 176.8 201.1 214.4 239.5 281.3 343.4 403.2
Capacity n. 4 4 4 4 4 4 4 4 4 4 4
regulation series

Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
current
Fan n.
Axil fan number 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 18.4 22.9 29.2 41.7 56.4 64.8 70.9 80.1 93.0 115.6 135.1
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1940 2080 2310 2700 3875 4400 5600 5860 6850 7300 8250
not included)

Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2

Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2

Cooling Capacity
Cooling Capacity(1) kW 340 412 494 538 656 754 932 1082 1344 1571
Cooling Capacity(2) kW 377 457 548 597 728 837 1035 1201 1492 1744
Free Cooling(3) kW 379 460 551 600 732 841 1040 1207 1499 1752
Free Cooling(4) kW 381 462 554 603 735 845 1045 1213 1507 1761
Refrigerant R134a

Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 112.8 128.0 148.2 167.2 195.4 224.2 274.4 312.4 388.8 456.5
Current(1) A 207.1 230.4 267.1 293.8 341.8 388.7 463.0 543.6 663.6 779.3
Power input(2) kW 114.8 130.2 150.8 170.1 198.8 228.1 279.2 317.8 395.5 464.4
Current(2) A 214.3 238.4 276.4 304.0 353.7 402.2 479.1 562.6 686.7 806.4
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series

Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28

13
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 58.5 70.9 85.0 92.5 112.8 129.7 160.3 186.1 231.2 270.2
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4960 6100 6460 7560 7850 8800 11320 13300 14100 16000
not included)

(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

14
CRITICOOL-FC.A LN R407c
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1

Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13

Cooling Capacity
Cooling Capacity(1) kW 114 137 176 243 312 373 404 470 557 636 746
Cooling Capacity(2) kW 126 152 196 269 346 414 448 522 619 705 829
Free Cooling(3) kW 127 152 197 271 348 416 451 525 622 709 833
Free Cooling(4) kW 128 153 198 272 350 418 453 527 625 713 837
Refrigerant R407c

Compressor 1
number
n. 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 41.2 49.9 57.2 75.6 97.5 116.2 126.1 142.8 170.5 181.5 216.6
Current(1) A 71.2 86.3 105.4 136.3 176.7 214.7 227.0 257.0 299.7 346.3 413.7
Power input(2) kW 41.9 50.7 58.2 76.9 99.2 118.2 128.3 145.3 173.5 184.6 220.4
Current(2) A 73.7 89.3 109.0 141.0 182.8 222.2 234.8 266.0 310.1 358.3 428.1
Capacity regulation n. 4 4 4 4 4 4 4 4 4 4 4
series

Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum current A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
Fan
Axil fan number n. 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 19.6 23.5 30.3 41.7 53.6 64.2 69.5 80.9 95.9 109.3 128.4
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1840 1980 2210 2550 3725 4250 5400 5660 6650 7050 8000
not included)

Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2

Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2

Cooling Capacity
Cooling Capacity(1) kW 366 416 497 557 624 746 941 1115 1271 1493
Cooling Capacity(2) kW 407 462 552 619 692 829 1044 1237 1411 1657
Free Cooling(3) kW 409 464 554 622 696 833 1049 1244 1418 1665
Free Cooling(4) kW 411 466 557 625 699 837 1054 1250 1425 1674
Refrigerant R134a

Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 115.1 130.6 151.2 170.5 195.0 232.4 285.6 341.1 363.0 433.2
Current(1) A 211.2 235.0 272.4 299.7 353.2 429.5 514.1 599.3 692.6 827.4
Power input(2) kW 117.1 132.8 153.8 173.5 198.4 236.4 290.6 347.0 369.3 440.7
Current(2) A 218.6 243.2 281.9 310.1 365.5 444.5 532.0 620.1 716.7 856.2
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series

Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000

15
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 63.0 71.5 85.5 95.9 107.3 128.4 161.8 191.7 218.6 256.8
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4760 5900 6160 7260 7550 8500 11320 13300 14100 16000
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

16
CRITICOOL-FC.A LN R22
Model 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1

Cabinet number S7 S7 S7A S8 T9A T9A T9A T11 T12 T12 T13

Cooling Capacity
Cooling Capacity(1) kW 115 138 178 245 315 377 408 475 563 642 754
Cooling Capacity(2) kW 128 153 198 272 350 418 453 527 625 713 837
Free Cooling(3) kW 128 154 199 273 351 421 455 530 628 716 841
Free Cooling(4) kW 129 155 200 275 353 423 457 533 631 720 845
Refrigerant R22

Compressor
number
n. 1 1 1 1 1 1 1 1 1 1 1
Power input(1) kW 40.4 48.9 56.1 74.1 95.6 113.9 123.6 140.0 167.2 177.9 212.4
Current(1) kW 69.8 84.6 103.3 133.6 173.2 210.5 222.5 252.0 293.8 339.5 405.6
Power input(2) kW 41.1 49.8 57.1 75.4 97.3 115.9 125.8 142.4 170.1 181.0 216.1
Current(2) kW 72.2 87.5 106.9 138.2 179.2 217.8 230.2 260.8 304.0 351.3 419.7
Capacity regulation n. 4 4 4 4 4 4 4 4 4 4 4
series

Startup current A 146 146 234 296 356.7 478 478 660 749 882 882
Maximum current A 120.8 120.8 171 207.5 285 328 328 401 461 478 551
Fan
Axil fan number n. 4 4 4 5 6 8 8 10 12 12 14
Air flow m3/h 52000 52000 66000 82500 118000 132000 132000 175000 210000 216000 252000
Power kW 6 6 8.8 11 13.2 17.6 17.6 22 26.4 26.4 30.8
Current A 12.8 12.8 18 22.5 27 36 36 45 54 54 63
Refrigerant-water
heat exchanger m3/h
water flow(1) 19.8 23.7 30.6 42.1 54.2 64.8 70.2 81.7 96.8 110.4 129.7
Pressure drop(1) kPa 33.2 31.9 33.2 31.9 47.1 46.9 55 30.5 46.6 46.6 76.2
Water volume l 35 49 58 88 95 135 135 222 222 222 252
Dimension and
Weight
Length mm 3600 3600 4355 5170 4980 4980 4980 6490 7480 7480 8470
Width mm 1420 1420 1420 1420 2370 2370 2370 2370 2370 2370 2370
Height mm 2280 2280 2280 2280 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 1840 1980 2210 2550 3725 4250 5400 5660 6650 7050 8000
not included)

Model 400V2 450V2 500V2 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2

Cabinet number T9A T11 T11 T12 T12 T13 T11*2 T12*2 T12*2 T13*2

Cooling Capacity
Cooling Capacity(1) kW 370 420 502 563 630 754 950 1126 1284 1508
Cooling Capacity(2) kW 411 466 557 625 699 837 1055 1250 1425 1674
Free Cooling(3) kW 413 469 560 628 703 841 1060 1256 1432 1682
Free Cooling(4) kW 415 471 563 631 706 845 1065 1262 1440 1691
Refrigerant R134a

Compressor
number
n. 2 2 2 2 2 2 2 2 2 2
Power input(1) kW 112.8 128.0 148.2 167.2 191.2 227.8 280.0 334.4 355.9 424.7
Current(1) A 207.1 230.4 267.1 293.8 346.3 421.1 504.0 587.5 679.0 811.2
Power input(2) kW 114.8 130.2 150.8 170.1 194.5 231.8 284.9 340.2 362.1 432.1
Current(2) A 214.3 238.4 276.4 304.0 358.4 435.8 521.5 607.9 702.6 839.4
Capacity regulation n. 8 8 8 8 8 8 8 8 8 8
series

Startup current A 468 530 592 653 713 671 925 992 1036 1765
Maximum current A 342 379 415 493 570 621 758 887 974 1102
Fan
Axil fan number n. 8 10 10 12 12 14 20 24 24 28
Air flow m3/h 132000 175000 175000 210000 210000 252000 350000 420000 432000 504000

17
Power kW 17.6 22 22 26.4 26.4 30.8 44 52.8 52.8 61.6
Current A 36 45 45 54 54 63 90 108 108 126
Refrigerant-water heat
exchanger
water flow(1) m3/h 63.6 72.2 86.3 96.8 108.4 129.7 163.4 193.7 220.8 259.4
Pressure drop(1) kPa 45 30 30.5 46.6 46.6 76.2 46.6 46.6 46.6 76.2
Water volume l 135 222 222 222 222 270 444 444 444 504
Dimension and
Weight
Length mm 4980 6490 6490 7480 7480 8470 13780 15760 15760 18440
Width mm 2370 2370 2370 2370 2370 2370 2370 2370 2370 2370
Height mm 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540
Net weight(options kg 4760 5900 6160 7260 7550 8500 11320 13300 14100 16000
not included)
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

18
Mechanical Cooling Capacity/ Compressor input power correction factor table
Gas/water heat exchanger outlet water
temperature℃
5 6 7 8 9 10 11 12 13 14 15

27 1.035/0.85 1.055/0.86 1.106/0.87 1.127/0.88 1.171/0.89 1.203/0.90 1.233/0.91 1.271/0.92 1.317/0.93 1.352/0.94 1.375/0.95
29 1.016/0.88 1.038/0.89 1.071/0.90 1.111/0.91 1.138/0.92 1.172/0.93 1.218/0.94 1.244/0.95 1.291/0.96 1.315/0.97 1.353/0.98

31 0.988/0.91 1.020/0.92 1.053/0.93 1.077/0.94 1.121/0.95 1.157/0.96 1.188/0.97 1.216/0.98 1.251/0.99 1.290/1.00 1.331/1.01
境 33 0.960/0.95 1.002/0.96 1.036/0.97 1.061/0.98 1.096/0.99 1.125/1.00 1.159/1.01 1.202/1.02 1.224/1.03 1.265/1.04 1.298/1.05
温 35 0.941/0.98 0.967/0.99 1.000/1.00 1.044/1.01 1.071/1.02 1.110/1.03 1.129/1.05 1.174/1.06 1.197/1.07 1.240/1.08 1.264/1.09
度 37 0.932/1.01 0.948/1.02 0.982/1.03 1.010/1.04 1.054/1.05 1.078/1.06 1.114/1.07 1.145/1.08 1.170/1.09 1.202/1.10 1.240/1.11
39 0.903/1.05 0.930/1.06 0.964/1.07 0.993/1.08 1.020/1.09 1.046/1.10 1.083/1.11 1.117 /1.12 1.143/1.13 1.177/1.14 1.217/1.15
41 0.884/1.08 0.912/1.09 0.937/1.10 0.958/1.11 1.003/1.13 1.030/1.14 1.053/1.15 1.088/1.17 1.116/1.18 1.152/1.19 1.182/1.20
43 0.855/1.11 0.875/1.12 0.909/1.13 1.941/1.14 0.969/1.15 0.998/1.16 1.037/1.17 1.060/1.18 1.089/1.19 1.147/1.21
1.126/1.20
45 0.826/1.15 0.856/1.16 0.891/1.17 0.923/1.18 0.952/1.19 0.981/1.20 1.007/1.21 1.031/1.22 1.061/1.23 1.101/1.24 1.123/1.25
47 0.806/1.18 0.838/1.19 0.872/1.20 0.888/1.21 0.917/1.22 0.948/1.23 0.976/1.24 1.002/1.25 -- / -- -- / -- -- / --
(1) Cooling rated conditions: outdoor temperature 35 ℃, chilled water outlet temperature 7 ℃, chilled water inlet temperature 12 ℃;
(2) Cooling rated conditions: outdoor temperature 35 ℃, water supply temperature 10 ℃, return water temperature 16 ℃;
(3) Free cooling rated conditions: outdoor temperature 2 ℃, water temperature 10 ℃, return water temperature 16 ℃;
(4) Free cooling rated conditions: outdoor temperature 1 ℃, water temperature 9 ℃, return water temperature 14 ℃; unit working power: 3φ / 380V / 50Hz,
neutral (zero line) line needed.

Water Flow Data


Refrigerant-water heat exchanger water flow
Model(MD) 350V1 400V1 450V1 500V1 600V1 700V2 750V2 800V2 890V2 950V2 1000V2 1200V2 1400V2 1600V2

Maximum water m3/h 73.3 84.3 92.1 104.1 120.9 146.7 157.6 168.6 184.2 196.3 208.4 241.9 300.5 351.3
flow

Model(LN) 130V1 150V1 200V1 250V1 350V1 400V1 450V1 500V1 600V1 700V1 800V1 400V2 450V2 500V2

Maximum water flow m3/h 25.7 30.9 39.8 54.8 70.4 84.3 91.2 106.2 125.9 143.6 168.6 82.7 93.9 112.2
Model(LN) 600V2 700V2 800V2 1000V2 1200V2 1400V2 1600V2

Maximum water m3/h 125.9 140.9 168.6 212.4 251.8 287.1 337.2
flow

19
upper unit as shown in the picture below. Due to an
Power requirements
Supply voltage: 380V-3φ-50Hz Supply voltage tolerance: increase of the pump weight, the unit with built-in pump
380V ± 10% has center of gravity offset and need to use φ80 hole on
Power supply: Neutral (zero line), 3-phase 4-wire or 5-wire the lifting ring fixed on the base. The unit with S cabinet
uses φ60 holes on the lifting ring.

Installation spacing
The unit should be installed in a well-ventilated place.Many
units parallel to the same direction should ensure the
installation of two units spacing, the minimum installation
spacing and cabinet size, as follows
Cabinet Number S7-S8 T9,M6-M8 T11,M10 T12,M12
Installation space 1.5 2 2.5 3
side by side
(meter)
Cabinet Number T13 M14-M16 M18-M20 M24
Installation space 3.5 4 5 6
side by side
(meter)

Other installation considerations


This unit is a specialized central air conditioning unit which
Maintenance space needs be sure to be installed by a professional installation
Unit should be left around the appropriate operation and team. The installation process should comply with local
maintenance space, it is recommended the free distance is laws and regulations.
not less than 1.5 meters.
A well-ventilated location should be selected to install the
unit to ensure the unit can reach full cooling capacity.
Installation base Do not install the unit in a corrosive gas discharge area or
The unit installed foundation must be strong, smooth, not other polluting air emissions area.
more than 1/1000 of the slope. To avoid distortion of the
Unit inlet pipe should be installed with water filter, inlet and
unit and rupture of the copper cooling system and unit
outlet pipes should be installed with water pressure gauge,
failure. The unit should be properly installed with vibration
external pipe and unit connections should have soft joints.
isolation or vibration isolator. MD compact unit should be
installed with the bracket or column under the unit so that To ensure the safe operation of the unit, be sure to install
the lower part of the unit has 0.5 m of ventilation space the water flow switch according to the electrical wiring and
(see below) (For any assistance in the detailed design, unit chain. The bypass pipe and bypass valve and drain
please feel free to contact AIRSYS) valve should be installed between the external water inlet
pipe of the unit to facilitate external pipe cleaning and flow
regulation.
Cut-off valve should be installed at the inlet and outlet of
the unit. After cleaning the external piping and confirming
that the water pressure meets the requirements of the unit,
it is needed to open the stop valve and pour water into the
unit. After the installation is completed, it needs to be sure
to inform the company or the company's designated
professional service team to complete the unit's first boot
Unit Lifting service. The service is free except for a special agreement.
AIRSYS will not be responsible for all the consequences
Standard unit lifting uses wire and rings for hoisting. To
caused by the boot. For detailed installation instructions,
prevent condenser deformation, the wire rope bracket
please refer to the unit installation instructions
should be added and mounted properly with the wire and

20
Pump work directly from the unit control, to avoid improper
Pump Kit (optional)
use of pumps and units and realize fully automated
AIRSYS heat pump unit can be installed with 1 or 2 pumps
management.
within the unit without changing the size of the unit. For the
Remove the pump installation costs and civil construction
roof area not enough or for the easy installation,
costs.
maintenance and other considerations, this option is very
Piping all use high-quality rubber insulation for thermal
important for the use of units.
insulation.
Save the limited space occupied by the pump on the roof.
The pump noise and vibration are significantly reduced.
No need to set up a separate distribution pump for the
pump and the corresponding control device.
automatically switches pump start-up order to balance
pump kit code is PU, end user can choose a single pump working hours. If the pump in operation fails, the control
or double pump according to the need. system immediately switches on another pump.
Single pump-PU ... / 1 Pump main components
The unit is equipped with a water pump. The work of the 1 or 2 Centrifugal or Ducted Pumps / Water Shut-off Valves
pump is completely computer controlled. / Check Valves / Water Flow Switches (1 per Pump)
Double pump-PU ... / 2 Hydrometer / Constant Pressure Water Tanks (optional) /
The unit is equipped with 2 pumps. 1 pump work during Water Safety Valves(optional) / Direct- Computer-driven
normal work, while the other is in standby mode. According electrical components.
to the two pump working hours computer control system

Technical data
Single Pump PU3/1 PU4/1 PU5/1G PU6/1 PU7/1 PU8/1 PU9/1

Dual Pump PU3/2 PU4/2 PU5/2G PU6/2 PU7/2 PU8/2 PU9/2

Water flow

Minimum m3/h 10 30 40 50 75 75 75
Maximum m /h
3
70 55 75 100 150 150 50
Pump head

@ Minimum kPa 225 235 220 260 275 340 385


waterflow
@Maximum kPa 150 185 180 190 200 280 330
waterflow
Power input kW 4 4.1 5.5 7.5 11 15 18.5
Rated current A 8.9 8.9 11.2 15.3 22.8 30 37
PU.../1 kg 210 255 290 320 410 418 430
net weight
PU.../2 kg 260 300 350 390 500 516 540
Net weight

* If the above pump flow, lift can not meet the requirements, please contact AIRSYS technical department.
* Due to the internal space constraints of the unit, the selected pump group must be confirmed by AIRSYS technical department.

21
Dimensions
CRITICOOL-FC.M6 dimension(mm)
CRITICOOL-FC.A.MD

Model 350V1 400V1 450V1

Cabinet number M6A M6C M6C

A 3410 3710 3710

B 1335 1485 1485

1-2 φDN Stainless 200 200 200


steel clamp
4 φ 21 21 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 350V1 400V1 450V1


S 725 725 705
T 645 705 685
U 645 725 705
X 605 725 705
Y 705 705 685
Z 605 705 685
Total weight 3930 4290 4170

22
CRITICOOL-FC.M8B dimensions(mm)
CRITICOOL-FC.A.MD

Model 500V1

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 500V1

S 875

T 950

U 845

X 845

Y 950

Z 865

Total weight 5530

23
CRITICOOL-FC.M10B Dimensions(mm)
CRITICOOL-FC.A.MD

Model 600V1

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 600V1

S 930

T 850

U 850

V 930

S1 680

T1 680

U1 680

V1 640

Total weight 6240

24
CRITICOOL-FC.M12 Dimensions(mm)
CRITICOOL-FC.A.MD

Model 700V2 750V2 800V2 890V2

Cabinet number M12A M12B M12C M12C

A 6450 6750 7050 7050

B 1520 1670 1670 1670

C 945 870 1020 1020

1-2 φDN Stainless steel 200 200 200 200


clamp
4 φ 21 21 21 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 700V2 750V2 800V2 890V2


S S1 1150 1190 1275 1295
T T1 1110 1150 1225 1265
U U1 1110 1150 1225 1265
V V1 1110 1150 1225 1265
Total weight 7860 8180 8650 8890

25
CRITICOOL-FC.M14B Dimensions(mm)
CRITICOOL-FC.A.MD

Model 950V2

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD
Model 950V2

U1 943
V1 923
W1 923
X1 943
Y1 923
Z1 923
W2 1018
X2 1003
Y2 1018
Z2 1003
Total weight 9620

26
CRITICOOL-FC.M16B Dimensions(mm)
CRITICOOL-FC.A.MD

Model 1000V2

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 1000V2

U1 790

V1 988

W1 1038

X1 1088

Y1 1038

Z1 1038

U2 1023

V2 1023

W2 998

X2 1023

Y2 973

Z2 700

Total weight 11720

27
CRITICOOL-FC.M18B Dimensions(mm)
CRITICOOL-FC.A.MD

Model 1200V2

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD
Model 1200V2

U1 990
V1 1212
W1 1262
X1 1342
Y1 1262
Z1 1262
U2 1147
V2 1147
W2 1092
X2 1147
Y2 1097
Z2 740
Total weight 13700

28
CRITICOOL-FC.M20B Dimensions(mm)
CRITICOOL-FC.A.MD

Model 1400V2

1-2 φDN Stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A.MD

Model 1400V2

U1 1065

V1 1245

W1 1275

X1 1395

Y1 1245

Z1 1275

U2 1275

V2 1245

W2 1195

X2 1275

Y2 1245

Z2 1145

Total weight 14600

29
CRITICOOL-FC.M24C Dimensions(mm)
CRITICOOL-FC.A.MD

Model 1600V2
Cabinet number M24C
A 14100
B1 1670
B2 1670
C 1670
D 1850
E 5150
F 2600
1-2 φDN Stainless steel clamp 200
4 φ 21

B System
Weight(kg)
CRITICOOL-FC.A.MD
Model 1600V2

S1 S2 1145
T1 T2 1135
U1 U2 1135
V1 V2 1135
W1 W2 1175
X1 X2 1135
Y1 Y2 1135
Z1 Z2 1105
Total weight 16500

30
CRITICOOL-FC.S7 Dimensions(mm)
CRITICOOL-FC.A LN

Model 130V1 150V1

1~2 φDN Stainless steel 80 80


clamp
4 φ 20 20

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery heat


exchangers are for optional accessories; The
unit needs 1.5 meters of maintenance space
around.

Weight(kg)
CRITICOOL-FC.A LN

Model 130V1 150V1


U 180 205
V 345 370
W 345 370
X 250 275
Y 385 405
Z 385 405
Total weight 1840 1980

31
CRITICOOL-FC.S7A Dimensions(mm)
CRITICOOL-FC.A LN

Model 200V1

1~2 φDN Stainless steel clamp 100


4 φ 20

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery heat


exchangers are for optional accessories; The
unit needs 1.5 meters of maintenance space
around.

Weight(kg)
CRITICOOL-FC.A LN

Model 200V1

U 195

V 400

W 400

X 275

Y 445

Z 395

Total weight 1910

32
CRITICOOL-FC.S8 Dimensions(mm)
CRITICOOL-FC.A LN

Model 250V1

1~2 φDN Stainless steel clamp 125


4 φ 20

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery heat


exchangers are for optional accessories; The
unit needs 1.5 meters of maintenance space
around.

Weight(kg)
CRITICOOL-FC.A LN

Model 250V1

U 205

V 505

W 505

X 275

Y 555

Z 505

Total weight 2550

33
CRITICOOL-FC.T9A Dimensions(mm)
CRITICOOL-FC.A LN

Model 350V1 400V1 450V1 400V2

1-2 ΦDN Stainless steel 125 150 150 150


clamp
4 Φ 21 21 21 21

Rear

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery heat


exchangers are for optional accessories; The
unit needs 1.5 meters of maintenance space
around.

Weight(kg)
CRITICOOL-FC.A LN

Model 350V1 400V1 450V1 400V2


U 810 905 905 1010
V 810 905 905 970
W 250 340 340 400
X 805 890 890 1010
Y 805 890 890 970
Z 245 340 340 400
Total weight 3725 4250 4250 4760

34
CRITICOOL-FC.T11 Dimensions(mm)
CRITICOOL-FC.A LN

Model 450V2 500V1 500V2

1-2 ΦDN Stainless steel 150 150 150


clamp
4 Φ 21 21 21

Rear

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery heat


exchangers are for optional accessories;
The unit needs 1.5 meters of
maintenance space around.

Weight(kg)
CRITICOOL-FC.A LN

Model 450V2 500V1 500V2


U 1025 1140 1245
V 1025 1140 1235
W 400 550 600
X 1025 1140 1235
Y 1025 1140 1235
Z 400 550 610
Total weight 4900 5660 6160

35
CRITICOOL-FC.T12 Dimensions(mm)
CRITICOOL-FC.A LN

Model 600V1 700V1 600V2 700V2

1-2 ΦDN Stainless steel 200 200 200 200


clamp
4 Φ 21 21 21 21

Rear

1.Water inlet pipe

2.Water outlet pipe

3.Electrical inlet hole

4.Base hole

Note: the pump and heat recovery


heat exchangers are for optional
accessories; The unit needs 1.5 meters
of maintenance space around.

Weight(kg)
CRITICOOL-FC.A LN

Model 600V1 700V1 600V2 700V2


U 1320 1455 1435 1525
V 1320 1415 1415 1505
W 685 655 780 745
X 1320 1415 1415 1505
Y 1320 1455 1435 1525
Z 685 655 780 745
Total weight 6650 7050 7260 7550

36
CRITICOOL-FC.T13 Dimensions(mm)
CRITICOOL -FC.A.STD

Model 800V1 800V2

1-2 ΦDN Stainless steel clamp 200 200


4 Rear Φ 21 21

Weight(kg)
CRITICOOL-FC.A LN

Model 800V1 800V2


S 1445 1320
T 1445 1570
U 555 680
V 555 680
W 1445 1570
X 1445 1570
Y 555 680
Z 555 430
Total weight 8000 8500

37
CRITICOOL-FC.T11*2 Dimensions(mm)
CRITICOOL -FC.A.STD

Model 1000V2

1~2 φDN Stainless steel clamp 150*2


4 φ 21

Weight(kg)
CRITICOOL-FC.A LN
Model 1000V2
U 1140
V 1140
W 550
X 1140
Y 1140
Z 550
Total weight 11320

38
CRITICOOL-FC.T12*2 Dimensions(mm)
CRITICOOL-FC.A LN

Model 1200V2 1400V2

1-2 ΦDN 锈钢卡箍 200*2 200*2


4 Φ 21 21

Weight(kg)
CRITICOOL-FC.A LN

Model 1200V2 1400V2


U 1320 1455
V 1320 1415
W 685 655
X 1320 1415
Y 1320 1455
Z 685 655
Total weight 13300 14100

39
CRITICOOL-FC.T13*2 Dimensions(mm)
CRITICOOL-FC.A LN

Model 1600V2

1~2 φDN stainless steel clamp 200


4 φ 21

Weight(kg)
CRITICOOL-FC.A LN

Model 1600V2

S 1445

T 1445

U 555

V 555

W 1445

X 1445

Y 555

Z 555

Total weight 8000

40
41