Cummins

Sync/Load ctrl:

ONAN
0V SG COM Speed gov bias = 2,50 V
5V SG OUT SpeedRegChar = POSITIV
VoutR SpeedGovLowLim = 0V
SpeedGovHiLim = 5V
Cummins
QST30

20 SG COM Sync/Load ctrl:


11 SG OUT Speed gov bias = 5,00 V
VoutR SpeedRegChar = POSITIV

Sync/Load ctrl:
Speed gov bias = 3,50 V
CUMMINS

9 SG OUT SpeedRegChar = POSITIV


QSL9

32 SpeedGovLowLim = 2,5V
SG COM
Vout SpeedGovHiLim = 5V

Sync/Load ctrl:
Speed gov bias = 5,00 V
CUMMINS

03-12 SG COM SpeedRegChar = POSITIV


GCS

03-11 SG OUT SpeedGovLowLim = 2,5V


VoutR SpeedGovHiLim = 7,5V

Barber Colman
Barber Colman
DYNA 8000

Sync/Load ctrl:
2 SG COM Speed gov bias = 6,00 V
9 SG OUT SpeedRegChar = POSITIV
VoutR SpeedGovLowLim = 4V
SpeedGovHiLim = 8V
Barber Colman

2
DYN1 10684

Sync/Load ctrl:
SG COM Speed gov bias = 6,00 V
SG OUT SpeedRegChar = POSITIV
9
VoutR SpeedGovLowLim = 4V
SpeedGovHiLim = 8V

GAC
ESD 5500

Sync/Load ctrl:
G SG COM
GAC

Speed gov bias = 5,00 V


N SG OUT SpeedRegChar = NEGATIV
VoutR SpeedGovLowLim = 4V
SpeedGovHiLim = 6V

IGS-NT, SW-Version 3.0


IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 116