S.No Interlock No. Description Proposal/Remarks Equipment / Instrument / Area/Activity

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 8

Equipment / Instrument /

S.No Interlock No. Description Proposal/Remarks


Area/Activity
When Temperature (TE-0104) reaches High
1 I-01 (More than -5 Deg C) then XV-0106/0103 shall Deleted in R4 of P&ID (TCE.7882A-300-PI-
TE-0104 (TE on 10" Dock line 8501)
tapping near PR-101) close

FD-0103 & GD-0103 (Jetty When FD-0103 & GD-0103 Detects, XV- FD and GD shall not be given interlock to close
2 I-02
Detectors) 0106/0103 shall close the valves. It should generate two sets of
alarm (H and HH for each detector), based on
which the panel operator shall operate the
ESD after evaluating the situatuion.

P 101 A/B/C shall trip. Hotter in jetty shall be


given which can be ON when ship activity is in
progerss.(Jetty operator or Loading master
When level in Storage tanks reaches HIGH
LI-0151,0152 -Tank A; LI- shall communicate to Ship CCR to stop the
3 I-03 HIGH, P-103 A/B/C/D/E shall stop,XV-0101 shall
0153,0154 -Tank B ship unloading or press ship ESD on listining
close, & Hooter shall be provided
Hootter. Soft Override for the shall be
provided to facilitate tank pump out and
reduce from HH level.

Ship unloading Operation at refrigerated


condition XV-0105 shall close. T- Valve control shall be independent of
101A in operation: XV-0106 to close, XV-0103 operation and decision shall be on panel
4 I-04 T-101 A/B shall open. operator. Tank to tank changeover cannot be
T-101B in operation: XV-0103 to close, XV- done when ship unloading is in progress.
0106 shall open
FD and GD shall not be given interlock to
FD-0101 & GD-0101 (T-101A) Flame and Gas Detects FD-0101 & GD-0101 (T- close the valves or Trip the equipment. It
5 I-05
FD-0102 & GD-0102 (T-101B) 101A), FD-0102 & GD-0102 (T-101B) should generate two sets of field alarm (H and
HH for each detector), based on which the
panel operator shall operate the ESD after
evaluating the situatuion. DV of the respective
area shall activate on HH of GD and H of FD.
When pressure PT-0151,0152 (T-101 A); PT-
6 I-06 PT-0151,0152 (T-101 A); PT- 0153,0154 (T-101 B) in storage tanks reaches At what pressure
0153,0154 (T-101 B) HIGH HIGH, PCV-0122 shall open and PCV-
0120/0121/XV-0101 shall close.

When pressure PT-0151,0152 (T-101 A); PT-


PT-0151,0152 (T-101 A); PT- P 101 A/B/C shall trip, K 102 A, K 103 A/B shall
7 I-07 0153,0154 (T-101 B) 0153,0154 (T-101 B) in storage tanks reaches trip.
LOW, PCV-0120/0121

When LT-0102 reaches HIGH HIGH P-102A/B


shall start.
8 I-08 LT-0102 -
When LT-0102 reaches LOW LOW P-102A/B
shall trip.

During tank holdup operation XV-0105 shall


9 I-09 Holdup -
close & K-102 shall start by manual.

During ship loading operation

FCV 103 Shall not operate in pressurized


XV-102 shall close,XV-0105 & FCV-0103 shall condition due to supply of hot liquid through
At Pressurized condition FCV to supply tank which will increase BOG in
open
tank. Insteat ITT line can be maintained in
throtelled condition to provide Minimum flow
to pump.

XV-102 & XV-0105 shall close. FCV-0103 shall XV-105 Valve control shall be independent of
At Refrigerated condition operation and decision shall be on panel
open
10 I-10 operator.
10 I-10

XV-0106 shall close, XV-0103 & XV-0105 shall XV-106 Valve control shall be independent of
T-101A in operation
open operation and decision shall be on panel
operator. when T 101A tank is in ship loading
then T 101B tank may recieve liquid from TT

XV-0103 shall close, XV-0106 & XV-0105 shall XV-103 Valve control shall be independent of
T-101B in operation
open operation and decision shall be on panel
operator. when T 101B tank is in ship loading
then T 101A tank may recieve liquid from TT
Truck unloading Operation at P-103 A/B/C/D/E shall start & XV-0101 shall -
pressurized conditions open
XV-0106 shall close, XV-0103 & XV-0105 shall
11 I-11 T-101A in operation -
open
XV-0103 shall close, XV-0106 & XV-0105 shall
T-101B in operation -
open

TT-0107 (Truck loading heater Temperature in TT-0107 goes below 0 Deg C, P-


12 I-12 101 A/B/C shall trip, Truck loading operation to -
outlet line)
stop

Temperature shall be -4 Deg C and this


interlock shall not act as start permissive
TT-0106 (Truck unloading chiller
13 I-13 condition for P-103 A/B/C/D/E. Delay can be
shell side outlet line) Temperature in TT-0106 exceeds -5 Deg C, XV- given between the truck activity start and
0103 & XV-0106 to close, P-103 A/B/C/D/E interlock being in line.
shall trip, Truck unloading operation to stop
Pressure in PT-0122 goes below 0.6 kg/cm2 g,
14 I-14 PT-0112 (Pressure of V-104) -
Compressor K-101A/B shall trip

RAW WATER DISTRIBUTION SYSTEM


HEATER 01 WILL TRIP IF TEMPERATURE OF TT-
TT-2901 2901 EXCEED 33 Deg C Alarm in control room shall be given at 31 Deg
15 I-01
(Temperature of T-103) HEATER 02 WILL TRIP IF TEMPERATURE OF TT- C
2901 EXCEED 34 Deg C
HEATER 01 & 02 WILL TRIP IF LT-2901 REACHES
Alarm in control room shall be given at LOW
16 I-02 LT-2901 (Level of T-103) LL LEVEL, PUMP P-105A/B/C & P-106 A/B WILL
level
ALSO TRIP

COMPRESSED AIR SYSTEM


WHEN PRESSURE IN V-105 REACHES LOW Alarm in control room
17 NEW PRESSURE IN V-105 Alarm in control room, P-101 A/B/C, P-103
WHEN PRESSURE IN V-105 REACHES LOW LOW A/B/C/D/E, K 101 A/B, K-102 A/B, K-103
A/B SHALL TRIP

Alarm in control room, P-101 A/B/C, P-103


IF Z-102 A/B trip due to low cooling water flow
18 NEW Z-102 A/B through the condenser A/B/C/D/E, K 101 A/B, K-102 A/B, K-103
A/B SHALL TRIP
SOP. Interlock not required
Only Set point. Interlock not required

Only Set point. Interlock not required

Only Set point. Interlock not required

SOP. Interlock not required

SOP. Interlock not required

SOP. Interlock not required


SOP. Interlock not required

SOP. Interlock not required

SOP. Interlock not required

SOP. Interlock not required

SOP. Interlock not required

Interlock not required.