FIRE ALARM BATTERY SIZING SANTACRUZ JKC-GCC-MEP-SSC-172002-A1

BATTERY SIZE CALCULATION SSC

S. No. Devices Qty. (Nos.) Current in (mA) Total Current (mA)


1 Multisensor Detector 153 6.5 994.5
2 Heat Detector 0 6.5 0
3 Beacon Light 27 90 2430
4 Response Indicator 151 7 1057
5 Vesda 10 500 5000
6 Smoke Detector 400 6.5 2600
7 Output module 0 6.5 0
8 Input module 44 5 220
9 Addressable Relay Modules 54 6.5 351
10 Fault Isolator 85 17 1445
11 Manual call point 71 7.8 553.8
12 Hooter cum Strobe 59 90 5310
Total current drawn by each device in alarm condition 19961.3
In Ampere 19.9613

Talarm = Maximum time in hours required for the alarm.


Tst.by = Standby time in hours for the system after main failure.
Ialarm = Total alarm current in amps for all alarm device.
IQD = Quiescent current in amps of all devices on the system.
Talarm = (1/2 hour).
Tst.by = (48 hours).
Ialarm = As per table.
IQD = (1 Amp).
F = (1.25). (25% extra for future expansion)

Battery size calculation (Ah) = F x [{Talarm x Ialarm} + {Tst.by x IQD}]


Battery Size in Ampere Hour (Ah) = 1.25 X [(0.5 x 19.9613) + (48 x 1.0)]

72.4758125 Ah
Recommended Battery Size in Ampere Hour (Ah) = 80 Ah

Notes : -
1. We have considered Maximum quiescent current for Fire Alarm Control Panel.
2. Since quiescent current & alarm current is vendor specific input. It may change after finalization of Fire Alarm Control Panel vendor.