Solar Inverters

26E1-E-0047b
String Inverter

Item Specifications Remarks


General Type number PIS-50/500-T PIS-36/380-G PIS-39/415-G
Rated output power 47.5 kVA 36 kVA 39 kVA
Insulation system No isolation transformer inside the inverter
Electric DC input voltage (Max.) DC 1100 V
specifications DC input voltage (operation) DC 200 to 1000 V Nominal power range: TBD
(DC input) Number of DC input branches 8 MPPT: 4
Electric Rated output power 47.5 kVA 36 kVA 39 kVA
specifications Rated output voltage AC 500 V, AC 380 V, AC 415 V,
(AC output) -10 to +10% -10 to +10% -10 to +10%
Rated frequency 50 Hz 50/60 Hz 50 Hz
Number of output phases Three-phase and three-wire Earthing on AC side is impossible
Rated output current 54.9 A Maximum 110%
Output power factor Lead 0.8 to Lag 0.8 Set increment: 0.001
Output current distortion factor (total) 5% or less During nominal output power, 40th
Output current distortion factor (each) 3% or less During nominal output power, 40th
Conversion efficiency (Max.) 99.0% 98.7% 98.8% With efficiency tolelance according to IEC
61683
Conversion efficiency (Euro) 98.5% 98.3% 98.4%
Overload capacity 110%
Noise Not higher than 65 dB
System System protection (OVR, UVR, OFR, UFR)
interconnection Islanding detection (passive) OFF, 10 [°] Detection of voltage phase jump, detection
time limit: within 0.5 s
Islanding detection (active) OFF, ON Frequency feedback method with step
injection, detection time limit: within 0.2 s
Voltage rise suppression function Reactive current compensation, active current output
suppression
FRT GB/T 19964-2012, JEA9701-2019, PEA 2016
Panel structure Installation system Outdoor, Indoor
Applicable IP IP65
Cable lead-in Bottom
Cooling system Natural air cooling
Dimensions (W × D × H) 930 × 260 × 540 mm
Mass 58 kg
Environmental Ambient temperature for operation -25 to +60℃
conditions Relative humidity 0 to 100% Without condensation
Altitude Up to 1000 m
Relevant standard IEC62109-1, IEC62109-2
PEA PEA, IEC61000-4, IEC61000-4,
IEC61727, IEC61727
PDC/12.17,
PGC/01.16,
No.:25/2016/TT-BCT
Communication system RS-485

(※) This product is relased in October 2019. The specifications can be changed without any notice.

Conversion efficiency Output derating characteristics


100 120
Output power / rated power [%]

99
100
98
97 80
Efficiency [%]

96
60
95
94 Vdc=625V 40
93
Vdc=750V 20
92
Vdc=850V
91 0
90 -30 -20 -10 0 10 20 30 40 50 60
0 20 40 60 80 100
Output Power [% ] Ambient temperature [°C]
Central Inverter

Item Specifications Remarks


General Type number PVI1500CJ-3/2500
Rated output power 2500 kVA
Insulation system No isolation transformer inside the inverter
Electric DC input voltage (Max.) DC 1500 V
specifications DC input voltage (operation) DC 915 to 1350 V
(DC input) Number of DC input branches 24 MPPT: 1
Electric Rated output power 2500 kVA
specifications Rated output voltage AC 590 V,
(AC output) -10 to +10%
Rated frequency 50/60 Hz
Number of output phases Three-phase and three-wire Earthing on AC side is impossible
Rated output current 2447 A
Output power factor Lead 0.8 to Lag 0.8 Set increment: 0.01
Output current distortion factor (total) 5% or less During nominal output power, 40th
Output current distortion factor (each) 3% or less During nominal output power, 40th
Conversion efficiency (Max.) 98.7% It does not include control power source,
and is shown with efficiency tolelance
Conversion efficiency (Euro) 98.5%
according to IEC 61683
Overload capacity 100%
Noise Not higher than 80 dB
System System protection (OVR, UVR, OFR, UFR)
interconnection Islanding detection (passive) OFF, 3 to 15 [°] Detection of voltage phase jump, detection
time limit: within 0.5 s
Islanding detection (active) OFF, ON Frequency feedback method with step
injection, detection time limit: within 0.2 s
Voltage rise suppression function Reactive current compensation, active current output
suppression
FRT JEA9701-2019, PEA 2016
Panel structure Installation system Outdoor
Applicable IP IP55
Cable lead-in Bottom
Cooling system Forced Air cooling (Heat sink, AC inductor),
Heat exchanger cooling (others)
Dimensions (W × D × H) 2025 × 1300 × 2594 mm
Mass 4000 kg
Environmental Ambient temperature for operation -20 to +57℃
conditions Relative humidity 4 to 100% Without condensation
Altitude Up to 1000 m
Relevant standard IEC 62109-1, -2, PEA 2016, IEC 61727, JEA9701-2019
Communication system RS-485 Option: Ethernet
(※) This product is relased in October 2019. The specifications can be changed without any notice.

Conversion efficiency*1 Output derating characteristics


100 120
Output power / rated power [%]

98 100
96 80
Efficiency [%]

94 60
92
Vdc=915V 40
90 Vdc=1150V 20
88 Vdc=1350V
0
86 -30 -20 -10 0 10 20 30 40 50 60
0 20 40 60 80 100
Output Power [% ] Ambient temperature [°C]
(*1) This efficiency is TBC.
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : +81-3-5435-7111

Internet address : www.fujielectric.co.jp


Information in this catalog is subject to change without notice. 2020-6(F2020b/E2018)PDF/FOLS Printed in Japan