Gas Density Monitor Model 233.52.063, With Gas Filling: Applications
Gas Density Monitor Model 233.52.063, With Gas Filling: Applications
Applications
Special features
■■ Temperature-compensated pressure gauge with Bourdon
tube
■■ Suitable for outdoor use
■■ Wetted parts from stainless steel
■■ Local readout with alarm contacts
■■ Hermetically leak-tight, therefore no negative impact by
atmospheric pressure fluctuations and differences in
altitude
Description
Gas density is a crucial operating parameter for high-voltage Conventional pressure gauges are not suitable here as the
switchgear. If the required gas density is not present, safe gas pressure changes depending on the ambient tempera-
operation of the plant cannot be guaranteed. ture, altitude and even atmospheric pressure.
The above factors together can amount up to 20 % of the
The WIKA gas density measuring instruments provide working pressure and thus falsify the measurement signifi-
reliable warnings against dangerously low gas cantly.
concentrations even in extreme environmental conditions. For this reason, all WIKA gas density measuring instruments
If the gas density decreases due to a leakage the magnetic are temperature compensated and hermetically sealed.
snap-action contacts, which are actuated by the pointer,
switch reliably and with repeatable accuracy.
High-voltage test
2 kV, 50 Hz, 1 s (wiring against case)
Electrical connection
Attached cable: length 1 m, with glass bushing
Process connection
G ¼ B according to EN 837, back mount
Stainless steel
Wrench flat 14 mm
Pressure element
Stainless steel, welded
Leak tightness: ≤ 1 · 10-8 mbar · l / s
Test method: spectrometry of helium mass
14012926.03
Alarm contact model 821 Dimensions in mm
X Y Z
Single and double contacts, without galvanic isolation 66.5 36 86
Double contacts, with galvanic isolation 76.5 46 96
Ordering information
Model / nominal size / scale range / process connection / filling pressure / calibration pressure / switch point /
switching function / options
© 2011 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.