The document describes an Automatic Genset Controller (AGC) that controls and protects generators. It can control a single generator or connect multiple AGCs in a power management system. The AGC monitors generator parameters, controls start/stop sequences, provides generator and busbar protections, and has configurable plant operating modes and nominal settings. It displays status, alarms, and logs on a LCD screen and allows remote operation and monitoring.
The document describes an Automatic Genset Controller (AGC) that controls and protects generators. It can control a single generator or connect multiple AGCs in a power management system. The AGC monitors generator parameters, controls start/stop sequences, provides generator and busbar protections, and has configurable plant operating modes and nominal settings. It displays status, alarms, and logs on a LCD screen and allows remote operation and monitoring.
The document describes an Automatic Genset Controller (AGC) that controls and protects generators. It can control a single generator or connect multiple AGCs in a power management system. The AGC monitors generator parameters, controls start/stop sequences, provides generator and busbar protections, and has configurable plant operating modes and nominal settings. It displays status, alarms, and logs on a LCD screen and allows remote operation and monitoring.
The Automatic Genset Controller, AGC, is a control unit
containing all necessary functions for protection and control of a genset. It can be used as a single unit for one genset, or a number of AGCs can be connected in a complete power management system for synchronising projects, islanded or paralleled to the mains. The AGC contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the sunshine proof LCD display. The AGC is a compact all-in- one unit designed for the following applications: Standard plant modes Applications:
Island mode: Power plant with synchronising generators or a
stand-alone generator. Can also be used in critical power plants. Automatic Mains Failure: Critical power/emergency standby plants, black start generator. Fixed power: Power plant with fixed kW set point (including building load). Peak shaving: Power plant where generator supplies peak load demand paralleled to the mains. Load takeover: Plant mode where the load is moved from mains to generator, for example peak demand periods or periods with risk of power outages. Mains power export: Power plant with fixed kW set point (excluding building load). Remote maintenance: Used when the generator has to supply the load while a distribution transformer needs to be disconnected for service. The plant modes are configurable, and it is possible to change the plant mode on the fly both in single and in power management application. Engine control ● Start/stop sequences ● Run and stop coil ● Relay outputs for governor control Generator protection (ANSI) ● 2 x reverse power (32) ● 5 x overload (32) ● 6 x overcurrent (50/51) ● 2 x overvoltage (59) ● 3 x undervoltage (27) ● 3 x over-/underfrequency (81) ● Voltage-dependent overcurrent (51V) ● Current/voltage unbalance (60) ● Loss of excitation/overexcitation (40/32RV) ● Non-essential load/load shedding, 3 levels (I, Hz, P>, P>>) ● Multi-inputs (digital, 4-20 mA, 0-40V DC, Pt100, Pt1000 or RMI) ● Digital inputs Busbar protection (ANSI) 3 x overvoltage (59) ● 4 x undervoltage (27) ● 3 x over frequency (81) ● 4 x underfrequency (81) ● Voltage unbalance (60) 3.1.6 Display ● Prepared for remote mounting ● Push-buttons for start and stop ● Push-buttons for breaker operations M-Logic ● Simple logic configuration tool ● Selectable input events ● Selectable output commands Nominal settings The AGC holds four sets of nominal settings, configured in channels 6001 to 6036. It is possible to switch between the nominal settings 1 to 4, to match different voltages and frequencies. Nominal settings 1 (6001 to 6007) are the nominal settings that are used as default. See paragraph "Switch between the nominal settings" for more information about this feature. The AGC holds two sets of nominal settings for the busbar, configured in channels 6051 to 6063. Each set consists of a nominal as well as a primary and secondary voltage value. The "U primary" and "U secondary" are used to define the primary and secondary voltage values, if any measurement transformers are installed. If no voltage transformer is installed between generator and busbar, select "BB Unom = G Unom" in channel 6054. With this function activated, none of the BB nominal settings will be considered. Instead, the nominal BB voltage will be considered equal to nominal generator voltage. Mode Description: SEMI - The display push-buttons (START, STOP, GB ON, GB OFF) are active and can be used by the operator. - The regulators are also active, i.e., the speed control will bring the generator to nominal speed upon start. - When pushing a breaker button for closing, the AGC will synchronise (if allowed) the breaker. When the breaker closes, the controls stop. TEST - The unit will start the generator, carry out the test sequence (predefined time period) and stop the generator again. Subsequently, the generator will return to AUTO or SEMI-AUTO mode. The mains breaker will remain closed, and the generator breaker will remain open. NOTE: The test running can be: Simple test: Starting the genset without closing the GB; Load test: Parallel to the mains and take load to a predefined value; Full test: Transfer the load to the genset and open the MB. AUTO - The unit will automatically carry out the control type selected (AMF, fixed power, etc.). - The display control push-buttons (START, STOP, GB ON, GB OFF) are disabled. - If the selected running mode is fixed power, mains power export, load takeover or island, timer start/stop (week watch) or binary input, then start/stop can be used. MAN - The display push-buttons (START, STOP) are active and can be used by the operator. - The regulators are not active, i.e. speed (and voltage) control has to take place using binary inputs for UP and DOWN control. - The breakers will be able to open or close at any time. A synchronisation check will always be performed to ensure safe closing of the breakers. BLOCK - The unit will not be able to start. BLOCK mode can be selected during standstill and the password is needed to exit BLOCK mode. If the BLOCK mode is selected while the genset is running, the mode will have no effect until the genset is stopped. To select another mode after the BLOCK mode, the password must be entered.To return to the other display functions from MODE selection, press the BACK push-button. Alarm handling When an alarm occurs, the unit will automatically go to the alarm list for display of the alarm.If reading of the alarms is not desired, use the BACK push-button to exit the alarm list.If you decide to enter the alarm list later, use the INFO push-button to jump directly to the alarm list reading. The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active (that is the alarm condition is still present). Once an alarm is acknowledged and the condition has disappeared, the alarm will no longer be displayed in the alarm list. This means that if there are no alarms, the alarm list will be empty. This display example indicates an unacknowledged alarm. The display can show only one alarm at a time. Therefore, all other alarms are hidden. To see the other alarms, use the and push-buttons to scroll in the display. To acknowledge an alarm, place the cursor (underscore) under "ACK" and then press SEL. To jump to the first (oldest) or the last (most recent) alarm, place the cursor under the selection (FIRST or LAST) and press SEL.
4.2 Log list
The log is divided into three different lists: 1. Events 2. Alarms 3. Battery test The log list contains up to 150 events, the alarm list contains up to 30 historical alarms and the battery test list contains up to 52 historical battery tests. An event is e.g., closing of breaker and starting of engine. An alarm is e.g., overcurrent or high cooling water temperature. A battery test is e.g., test OK or test failed. To enter the log list: 1. Press LOG. 2. Select the list which is needed by using the and push-buttons and press the SEL push-button. 3. To scroll up and down in the list, use the and push-buttons. 4. It is also possible to go to the first (oldest) logging or the last (most recent) logging by placing the cursor 5. (underscore) under the selection (move the cursor using the and push-buttons) and press the SEL 6. push-button.