Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

Yasmeen City: Infrastructure Works

HYDRO PRESSURE TEST RECORD (SECTION 8, PART 4.6.3 QCS 2014)

Test Pack No : 1 Ref No :

Test Location Lusail - Yasmeen City Project - Road 01 & 14 Rev : 00

Drawing No: Date of Issue : 01-07-2019

Preliminary Readings Main Pressure Test Reading

20-140 min @ 6 140-260 min @ 9 260-320 min @ 6


Test Pressure Imposed 00-10 min @ 4 Bar 10-20 min @ 6 Bars Bars Bars Bars Date of Testing: 30-June-2019

Actual time during the test 12:50am 1:15am Listed Below Listed Below Listed Below Pipe Diameter (mm ) :250

Pressure Gauge 1 3.9 bar 6 bar 6.1 bar 9 bar 6.1 bar Pipeline Length :

Pressure Gauge 2 - - - - - Pipeline Material :PE100 HDPE SDR11

Ambient Temperature 0c 34-37 34-37 34-37 34-37 34-37 Required Main Test Pressure : 6 & 9 bar

Calibration Due
Instrument Serial No Certificate No Date

Pressure Gauge 1 180501360322 S1810263.02 43996

Pressure Gauge 2 - - -

Safety Relief valve - - -

Chart Recorded - - -

Main Pressure Test Reading

Start 0.5 hrs 1 hrs 1.5 hrs 2 hrs 2.5 hrs 3 hrs 3.5 hrs 4 hrs 4.5 hrs 5 hrs 5.5 hrs 6 hrs

1:14am 1:49am 2:15am 2:45am 3:28am 3:45am 4:09am 4:40am 5:10am 5:40am 6:10am 6:25am 6:56am
Actual Time During the Test

Pressure Gauge 1 6.1 6.1 6.1 6.1 6.1 6 9 9 9 9 9 6.1 6.15


Readings(Bars)

Pressure Gauge 2 - - - - - - - - - - - - -
Readings(Bars)

34 34 34 34 35 35 35 35 36 36 36 36 37
Ambient Temperature 0C

Amount of Water Added(L)

Actual 6.5 hrs 7 hrs 7.5 hrs 8 hrs 8.5 hrs 9 hrs 9.5 hrs 10 hrs 21 hrs 22 hrs 23 hrs 24 hrs
Time
During the 7:26am
Test

Pressure Gauge 1 6.1


Readings(Bars)

Pressure Gauge 2 -
Readings(Bars)

37
Ambient Temperature 0C

Amount of Water Added(L)

Remarks

Company Contractor Engineer Contractor QA/QC Consultant

Signature
Name khalil labaki Jabin Simpson

Date 6/30/2019 6/30/2019

You might also like