Download as pdf or txt
Download as pdf or txt
You are on page 1of 222

DIRECT DESIGN

METHOD
“DDM”

The University of Lahore,


Civil Engineering Department 1
Islamabad Campus
Types of Two-way Slab Systems

The University of Lahore,


Civil Engineering Department 2
Islamabad Campus
Types of Two-way Slab Systems

The University of Lahore,


Civil Engineering Department 3
Islamabad Campus
Types of Two-way Slab Systems

The University of Lahore,


Civil Engineering Department 4
Islamabad Campus
Conventional Slab with Beam Floor System

The University of Lahore,


Civil Engineering Department 5
Islamabad Campus
The University of Lahore,
Civil Engineering Department 6
Islamabad Campus
Types of Two-way Slab Systems

The University of Lahore,


Civil Engineering Department 7
Islamabad Campus
Area Vs Line Element
Analysis
Unlike beams and columns, slabs are two
dimensional members. Therefore their analysis except
one-way slab (load distribution in one direction only)
systems is relatively difficult.

Design
Once the analysis is done, the design is carried
out in the usual manner. So no problem in design.

The University of Lahore,


Civil Engineering Department 8
Islamabad Campus
Load Transfer Path For Gravity Loads

• Mechanism and path must be found to transfer these loads to


the “Supports” through a Medium

• All type of Gravity Loads can be represented as:


– Point Loads
– Line Loads
– Area Loads
– Volume Loads

The University of Lahore,


Civil Engineering Department 9
Islamabad Campus
The University of Lahore,
Civil Engineering Department 10
Islamabad Campus
Load Transfer to Beams in Two-Way Slab

The University of Lahore,


Civil Engineering Department 11
Islamabad Campus
Conventional Approach

• For Wall Supported Slabs


– Assume load transfer in One-Way or Two-Way manner
– Uniform, Triangular or Trapezoidal Load on Walls

• For Beam Supported Slabs


– Assume beams to support the slabs in similar ways as walls
– Design slabs as edge supported on beams
– Transfer load to beams and design beams for slab load

• For Flat-Slabs or Columns Supported Slabs


– Assume load transfer in strips directly to columns

The University of Lahore,


Civil Engineering Department 12
Islamabad Campus
Simplified Load Transfer

To Lines To Points To Lines and Points

Transfer of Area Load


The University of Lahore,
Civil Engineering Department 13
Islamabad Campus
Gravity Load Transfer Paths

Single Path Single Path Dual Path


Slab On Walls Slab on Columns Slab On Beams,
Beams on Columns

The University of Lahore,


Civil Engineering Department 14
Islamabad Campus
Gravity Load Transfer Paths

Mixed Path Complex Path Three Step Path


Slab On Walls Slab on Beams Slab On Ribs
Slab On Beams Slab on Walls Ribs On Beams
Beams on Walls Beams on Beams Beams on Columns
Beams on Columns

The University of Lahore,


Civil Engineering Department 15
Islamabad Campus
Stiffness Based Load Sharing

The University of Lahore,


Civil Engineering Department 16
Islamabad Campus
Stiffness Based Load Sharing

Small Stiffness – Less Share

The University of Lahore,


Civil Engineering Department 17
Islamabad Campus
Stiffness Based Load Sharing

Slab T = 200 mm
Beam Width, B = 300 mm
Beam Depth, D
a) 300 mm
b) 500 mm
c) 1000 mm

The University of Lahore,


Civil Engineering Department 18
Islamabad Campus
Moment Distribution in Beam-Slab

Effect of Beam Size on


Moment Distribution

a) Beam Depth = 300 mm

c) Beam Depth = 1000 mm


b) Beam Depth = 500 mm
The University of Lahore,
Civil Engineering Department 19
Islamabad Campus
Moment Distribution in Slab Only

Effect of Beam Size on


Moment Distribution

a) H = 300 mm

c) H = 1000 mm
The University of Lahore,
Islamabad Campus
Civil Engineering Department b) H = 500 mm 20
Moment Distribution in Beams Only

Effect of Beam Size on


Moment Distribution

a) H = 300 mm

c) H = 1000 mm
The University of Lahore,
Civil Engineering Department
b) H = 500 mm 21
Islamabad Campus
Moment Distribution in Slabs Only

Effect of Beam Size on Moment Distribution

a) H = 300 mm b) H = 500 mm c) H = 1000 mm


The University of Lahore,
Civil Engineering Department 22
Islamabad Campus
The Design Strip Concept

In DDM instead of panels, Frames are analyzed

The University of Lahore,


Civil Engineering Department 23
Islamabad Campus
The University of Lahore,
Civil Engineering Department 24
Islamabad Campus
The University of Lahore,
Civil Engineering Department 25
Islamabad Campus
The Design Strip Concept

Design Strip Middle Strip

Column Strip

Middle Strip
Design Strip

The University of Lahore,


Civil Engineering Department 26
Islamabad Campus
(1) General Description
In reinforced concrete buildings, a basic and common type of
floor is the slab-beam-girder construction. As shown in Fig.1(a),
the shaded slab area is bounded by the two adjacent beams on
the sides and portions of the two girders at the ends.

Fig.1(a)

The University of Lahore,


Civil Engineering Department 27
Islamabad Campus
(1) General Description

When the length of this area is two or more times its width, almost
all of the floor load goes to the beams, and very little, except some
near the edge of the girders, goes directly to the girders. Thus the
slab may be designed as a one-way slab, with the main
reinforcement parallel to the girder and the shrinkage and
temperature reinforcement parallel to the beams. The deflected
surface of a oneway slab is primarily one of single curvature.

The University of Lahore,


Civil Engineering Department 28
Islamabad Campus
(1) General Description
When the ratio of the long span
L to the short span S as shown
in Fig.1(b) is less than about 2,
the deflected surface of the
shaded area becomes one of
double curvature.
Fig.1(b)
The floor load is carried in both directions to the four supporting beams around
the panel; hence the panel is a two-way slab. Obviously, when S is equal to L,
the four beams around a typical interior panel should be identical; for other
cases the long beams take more load than the short beams.

The University of Lahore,


Civil Engineering Department 29
Islamabad Campus
(1) General Description
Both the flat slab and flat plate floors shown in Figs.2(b) and
2(a) are characterized by the absence of beams along the interior
column lines, but edge beams may or may not he used at the
exterior edges of the floor.

Fig.2(a)
The University of Lahore,
Islamabad Campus
Civil Engineering Department
Fig.2(b) 30
(1) General Description
Flat slab floors differ from flat plate floors in that flat slab floors provide
adequate shear strength by having either or both of the following: (a)
drop panels (i.e., increased thickness of slab) in the region of the
columns; or (b) column capitals (i.e., tapered enlargement of the upper
ends of columns).

In flat plate floors a uniform slab thickness is used and the shear
strength is obtained by the embedment of multiple-U stirrups or
structural steel devices known as shearhead reinforcement within the
slab of uniform thickness. Relatively speaking, flat slabs are more
suitable for larger panel size or heavier loading than flat plates.

The University of Lahore,


Civil Engineering Department 31
Islamabad Campus
The University of Lahore,
Civil Engineering Department 32
Islamabad Campus
Methods for Design of Two Way Slab

The following methods are used for the design of two


way slabs.
 Moment Coefficient method of 1963 ACI Code
 Direct Design Method
 Equivalent Fame Method
 Strip Method
 Yield Line Theory

The University of Lahore, Civil Engineering Department 33


Islamabad Campus
Limitations of DDM ACI Code 13.6.1

The University of Lahore,


Civil Engineering Department 34
Islamabad Campus
The University of Lahore, Civil Engineering Department 35
Islamabad Campus
Fundamental Steps of DDM ACI R 13.6

• Determination of total factored static moment, Mo

• Distribution of total factored static moment into positive and


negative moment.

• Distribution of positive and negative moment into column strip


and middle strip.

• Calculation of reinforcement and detailing of steel.

The University of Lahore, Civil Engineering Department 36


Islamabad Campus
(2) General Design Concept of ACI Code
The basic approach to the design of two-way floor systems involves
imagining that vertical cuts are made through the entire building along
lines midway between the columns. The cutting creates a series of
frames whose width lies between the centerlines of the two adjacent
panels as shown in Fig.3.
The equivalent frame so obtained is used to determine the moments by
either direct design method (DDM) or equivalent frame method (EFM).

Fig.3
The University of Lahore,
Civil Engineering Department 37
Islamabad Campus
The University of Lahore,
Civil Engineering Department 38
Islamabad Campus
Longitudinal Rigid Frames

Transverse Rigid Frames

The University of Lahore,


Civil Engineering Department 39
Islamabad Campus
(2) General Design Concept of ACI Code
The resulting series of rigid frames, taken separately in the
longitudinal and transverse directions of the building, may be
treated for gravity loading floor by floor as would generally be
acceptable for a rigid frame structure consisting of beams and
columns, in accordance with ACI.

A typical rigid frame would consist of (1) the columns above and
below the floor, and (2) the floor system, with or without beams,
bounded laterally between the centerlines of the two panels (one
panel for an exterior line of columns) adjacent to the line of
columns.

The University of Lahore,


Civil Engineering Department 40
Islamabad Campus
(2) General Design Concept of ACI Code
Thus the design of a two-way floor system (including two-way
slab, flat slab, and flat plate) is reduced to that of a rigid frame;
hence the name “Equivalent Frame Method.”

As in the case of design of actual rigid frames consisting of


beams and columns, approximate methods of analysis may be
suitable for many usual floor systems, spans, and story heights.
For gravity load only and for floor systems within the specified
limitations, the moments and shears on these equivalent frames
may be determined (a) approximately using moment and shear
coefficients prescribed by the “Direct Design Method”, or
The University of Lahore,
Civil Engineering Department 41
Islamabad Campus
(2) General Design Concept of ACI Code

(b) by structural analysis in a manner similar to that for actual


frames using the special provisions of the "equivalent frame
method”. An elastic analysis (such as by the equivalent frame
method) must be used for lateral load even if the floor system
meets the limitations of the direct design method for gravity load.

The equivalent rigid frame is the structure being dealt with


whether the moments are determined by the "direct design
method (DDM)" or by the "equivalent frame method (EFM)."
These two ACI Code terms describe two ways of obtaining the
longitudinal variation of bending moments and shears.
The University of Lahore,
Civil Engineering Department 42
Islamabad Campus
(2) General Design Concept of ACI Code

When the "equivalent frame method" is used for obtaining the


longitudinal variation of moments and shears, the relative stiffness
of the columns, as well as that of the floor system, can be
assumed in the preliminary analysis and then reviewed, as is the
case for the design of any statically indeterminate structure.
Design moment envelopes may be obtained for dead load in
combination with various patterns of live load, In lateral load
analysis, moment magnification in columns due to sidesway of
vertical loads must be taken into account as prescribed in ACI.

The University of Lahore,


Civil Engineering Department 43
Islamabad Campus
(2) General Design Concept of ACI Code
Once the longitudinal variation in factored moments and
shears has been obtained, whether by ACI "DDM" or "EFM,"
the moment across the entire width of the floor system being
considered is distributed laterally to the beam, if used, and to
the slab. The lateral distribution procedure and the remainder
of the design is essentially the same whether "DDM" or "EFM"
has been used.

The University of Lahore,


Civil Engineering Department 44
Islamabad Campus
(3) Total Factored Static Moment Mo
Consider two typical interior panels ABCD and CDEF in a two-
way floor system, as shown in Fig.4. Let L1 and L2 be the panel
size in the longitudinal and transverse directions, respectively.

Fig.4
Fig.5
The University of Lahore,
Civil Engineering Department 45
Islamabad Campus
L1 Longitudinal Span

L2 Transverse Span

Ln Longitudinal Clear
Span

The University of Lahore,


Civil Engineering Department 46
Islamabad Campus
(3) Total Factored Static Moment
Let lines 1-2 and 3-4 be centerlines of panels ABCD and CDEF,
both parallel to the longitudinal direction. Isolate as a free body
[see Fig.5] the floor slab and the included beam bounded by the
lines 1-2 and 3-4 in the longitudinal direction and the transverse
lines 1’-3’ and 2’-4’ at the faces of the columns in the transverse
direction. The load acting on this free body [see Fig.6] is wuL2 per
unit distance in the longitudinal direction. The total upward force
w uL 2L n
acting on lines 1’-3' or 2'-4' is , where wu is the factored load
2
per unit area and Ln is the clear span in the longitudinal direction
between faces of supports.
The University of Lahore,
Civil Engineering Department 47
Islamabad Campus
(3) Total Factored
Static Moment

If Mneg and Mpos are the


numerical values of the Fig.6
total negative and
positive bending
moments along lines 1‘-3'
and 5-6, then moment
Fig.7
equilibrium of the free
body of Fig.7 requires
W u L 2 L2n
M neg  M pos  (1)
8 Fig.8
The University of Lahore,
Civil Engineering Department 48
Islamabad Campus
(3) Total Factored Static Moment
For a typical exterior panel, the negative moment at the interior
support would be larger than that at the exterior support. The
maximum positive moment would occur at a section to the left of
the mid-span, as shown in Fig.11.

Fig.10

Fig.9

Fig.11
The University of Lahore,
Civil Engineering Department 49
Islamabad Campus
(3) Total Factored Static Moment
In practical design, it is customary to use Mpos at midspan for
determining the required positive moment reinforcement.

For this case,


M neg ( left )  M neg ( right ) w u L 2 L2n
 M pos  (2)
2 8
A proof for Eq.(2) can be obtained by writing the moment
equilibrium equation about the left end of the free body shown in
Fig.9

W uL 2L n  L n   Ln 
M neg ( left )  M pos     V midspan   (3 )
2  4   2 

The University of Lahore,


Civil Engineering Department 50
Islamabad Campus
(3) Total Factored Static Moment
and, by writing the moment equilibrium equation about the right
end of the free body shown in Fig.10,
W uL 2L n  L n   Ln 
M neg ( right )  M pos     V midspan   (4)
2  4   2 

Equation(2) is arrived at by adding equations (3) and (4) and


dividing by 2 on each side. Eq.(2) may also be obtained, as shown
in Fig.11, by the superposition of the simple span uniform loading
parabolic positive moment diagram over the trapezoidal negative
moment diagram due to end moments.

The University of Lahore,


Civil Engineering Department 51
Islamabad Campus
(3) Total Factored Static Moment
w uL 2L2n
ACI- uses the symbol M0 to mean 8
and calls M0 the total
factored static moment. It states, Absolute sum of positive and
average negative factored moments in each direction shall not be
less than M0"; or
M neg ( left )  M pos ( right )  w u L 2 L2n 
 M pos  M 0   (5 )
2  8  in which
wu = factored load per unit area
Ln = clear span in the direction moments are being determined,
measured face to face' of supports (ACI), but not less than 0.65L1
L1 = span length in the direction moments are being determined, measured
center to center of supports
L2 = transverse span length, measured center to center of supports

The University of Lahore,


Civil Engineering Department 52
Islamabad Campus
(3) Total Factored Static Moment
Equations (1) and (2) are theoretically derived on the basis that
Mneg(left), Mpos, and Mneg(right) occur simultaneously for the same live
load pattern on the adjacent panels of the equivalent rigid frame defined
in Fig.3.

If the live load is relatively heavy compared with dead load, then
different live load patterns should be used to obtain the critical positive
moment at midspan and the critical negative moments at the supports.
In such a case, the "equal" sign in Eqs.(1) and (2) becomes the
"greater" sign. This is the reason why ACI states "absolute sum . . . shall
not be less than Mo" as the design requirement.

The University of Lahore,


Civil Engineering Department 53
Islamabad Campus
(3) Total Factored Static Moment
To avoid the use of excessively small values of Mo in the case of short
spans and large columns or column capitals, the clear span Ln to be
used in Eq.(5) is not to be less than 0.65L1 (ACI).

When the limitations for using the direct design method are met, it is
customary to divide the value of Mo into Mneg into Mpos, if the restraints at
each end of the span are identical (Fig.4 to 8); or into [Mneg(left) +
Mneg(right)]/2 and Mpos if the span end restraints are different (Fig.9 to
11). Then the moments Mneg(left), Mneg(right), and Mpos must be
distributed transversely along the lines 1‘-3', 2‘-4', and 5-6, respectively.
This last distribution is a function of the relative flexural stiffness
between the slab and the included beam.
The University of Lahore,
Civil Engineering Department 54
Islamabad Campus
Procedure for computation of longitudinal moments

The procedure for computing the longitudinal moments by the


"direct design method" may be summarized:
(1) Check limitations 1 through 5 for the “Direct Design Method
listed in Section-7. If they comply, and the slab is supported on
beams, follow Steps 2 through 6 given below. For slabs not
supported on beams, proceed to Step 6.

(2) Compute the slab moment of inertia Is

 t3 
Is   L 2   (15 )
 12 
The University of Lahore,
Civil Engineering Department 55
Islamabad Campus
Procedure for computation of longitudinal moments

(3) Compute the longitudinal beam (if any) moment of inertia Ib


(4) Compute the Stiffness Ratio , flexural stiffness of beam
section to flexural stiffness of a width of slab bounded laterally by
centerlines of adjacent panels (if any) on each side of the beam.

E cb I b
  ( 16 )
E cs I s

L 21 L 22
(5) Check that the ratio 1
to lies between 0.2 and 5.0 for the
2
cases where the slab is supported by beams.

The University of Lahore,


Civil Engineering Department 56
Islamabad Campus
Procedure for computation of longitudinal moments

w u L 2 L 2n
(6) Compute the total static moment M o  as stated by
8
Eq.2. Ln is not to be taken less than 0.65L1. For flat slabs, Eq.8
should preferably by used for computing Mo.
(7) Obtain the three critical ordinates on the longitudinal moment
diagrams for the exterior and interior spans using Figs.19 to 24.

The University of Lahore,


Civil Engineering Department 57
Islamabad Campus
Assignment # 1
• Design the two way slab panels 1,2,3 & 4 (Slab
with Beam Example) shown in Fig-1 using the
ACI Co-efficient Method and also calculate the
total steel area in Tons.

The University of Lahore,


Civil Engineering Department 58
Islamabad Campus
Two way floor system for slab with beams
Figure-1 shows a two-way slab floor with a total area of 12,500 sq ft. It
is divided into 25 panels with a panel size of 25 ft x 20 ft. Concrete
strength is and steel yield strength is fy=40,000 psi. Service
f c  3000 psi
live load is to be taken as 120 psf. Story height is 12 ft. The preliminary
sizes are follows: slab thickness is 6.5 in.; long beams are 14  28 in.
Overall; short beams are 12  24 in. overall; upper and lower columns
are 15  15 in. The four kinds of panels (corner, long-sided edge, short-
sided edge, and interior) are numbered 1, 2, 3, and 4 in Fig.-1.
Determine the total factored static moment in a loaded span in each of
the four equivalent rigid frames whose widths are designated A, B, C
and D in Fig.2.
The University of Lahore,
Civil Engineering Department 59
Islamabad Campus
Given data

Fig.-1
The University of Lahore,
Civil Engineering Department 60
Islamabad Campus
For two way slab (with beams), the total factored static moment in a
loaded span in each of the four equivalent rigid frame whose widths
are designated A, B, C and D in Fig.2

Fig.-2
The University of Lahore,
Civil Engineering Department 61
Islamabad Campus
The factored load wu per unit floor area is

wu=1.4wD +1.7wL

=1.4(6.5)(150/12) +1.7(120)

=114 + 204 =318 psf


ACI states that Ln shall extend from face to face of columns, capitals or
walls.
2
1 1  15 " 
For frame A, M o  wu L2 L2n  0.31820 ' 25 '   448 ft  kips
8 8  12 

For frame B, Mo = 224 ft-kips


2
1 1  15 " 
For frame C, M o  wu L2 Ln  0.31825 20 
2
  349 ft  kips
8 8  12 

For frame D, Mo = 175 ft-kips


The University of Lahore,
Civil Engineering Department 62
Islamabad Campus
Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab

When beams are used along the column lines in a two-way floor
system, an important parameter affecting the design is the relative
size of the beam to the thickness of the slab. This parameter can
best be measured by the ratio α of the flexural rigidity (called flexural
stiffness by the AC1 Code) EcbIb of the beam to the flexural rigidity
ECSIS, of the slab in the transverse cross-section of the equivalent
frame shown in Fig.14,15&16. The separate moduli of elasticity Ecb
and Ecs, referring to the beam and slab, provide for different strength
concrete (and thus different Ec values) for the beam and slab.

The University of Lahore,


Civil Engineering Department 63
Islamabad Campus
Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab

Fig.14

Fig.15
The University of Lahore,
Civil Engineering Department
Fig.16 64
Islamabad Campus
COLUMN STRIP AND MIDDLE STRIP

 Column Strip. (ACI Code 13.2.1) C.S. is defined by a slab


width on each side of a column centre line, equal to ¼ of
the smaller panel dimension L1 or L2 (smaller of 0.25L1
and L2); including beams, if present; where
L1= Span length, centre to centre of support in the
direction moments are being determined.
L2= Span length, centre to centre of support in the
direction perpendicular to L1.
 Middle Strip. (ACI Code 13.2.2) the portion of the panel
between two column strips defines the middle strip
(M.S). M.S. are assumed to be supported on C.S.
The University of Lahore,
Civil Engineering Department 65
Islamabad Campus
COLUMN STRIP AND MIDDLE STRIP

The University of Lahore,


Civil Engineering Department 66
Islamabad Campus
COLUMN STRIP AND MIDDLE STRIP

The University of Lahore,


Civil Engineering Department 67
Islamabad Campus
COLUMN STRIP AND MIDDLE STRIP

The University of Lahore,


Civil Engineering Department 68
Islamabad Campus
 Beams. (ACI Code 13.2.4).
Beams are defined to include that part of the slab on each side of the
beam extending a distance equal to the projection of the beam above
or below the slab (whichever is greater ) but not greater than four
times the slab thickness. For interior beam,be= 2 [( h – hf ) ≤ 4hf ]+bw

The University of Lahore,


Civil Engineering Department 69
Islamabad Campus
The University of Lahore,
Civil Engineering Department 70
Islamabad Campus
Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab

The moments of inertia Ib and Is refer to the gross sections of the


beam and slab within the cross-section of Fig.16. ACI permits the
slab on each side of the beam web to act as a part of the beam,
this slab portion being limited to a distance equal to the projection
of the beam above or below the slab, whichever is greater, but not
greater than four times the slab thickness, as shown in Fig.17.

Fig.17

The University of Lahore,


Civil Engineering Department 71
Islamabad Campus
Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab

More accurately, the small portion of the slab already counted in the
beam should not be used in Is, but ACI permits the use of the total width
of the equivalent frame in computing Is. Thus,

E cb I b
  (9 )
E cs I s

[NOTE: When an edge beam is used, its value of α should not be less than 0.80,
otherwise slab thickness of the exterior panel having discontinuous edge should be
increased by 10 % as compared to interior panel. ACI Code 9.5.3.3 (d).]

bw h 3
Ib  k (10 )
12

The University of Lahore,


Civil Engineering Department 72
Islamabad Campus
Moment of Inertia of a Flanged Beam Section about its Centroidal Axis

The University of Lahore,


Civil Engineering Department 73
Islamabad Campus
Ratio of Flexural Stiffnesses of Longitudinal Beam to Slab

In which
2 3
 bE  t   t
  t
   b E
   
t
1    1   4  6    4      1  
 bw  h   h h  bw  h  
k (11)
b  t 
1   E  1 
 bw  h 

where
h = overall beam depth
t =overall slab thickness
bE =effective width of flange
bw = width of web

The University of Lahore,


Civil Engineering Department 74
Islamabad Campus
For other cases, factor K can be found from either the following
formula, table or from the graph.

The University of Lahore,


Civil Engineering Department 75
Islamabad Campus
The University of Lahore,
Civil Engineering Department 76
Islamabad Campus
where

h=overall beam depth

t=overall slab thickness

bE=effective width of flange

bw=width of slab

For the two way slab (with beams), the ratio α of the flexural
stiffness of the longitudinal beam to that of the slab in the
equivalent rigid frame, for all the beams around panels 1, 2, 3,
and 4 in Figure.

The University of Lahore,


Civil Engineering Department 77
Islamabad Campus
Two way floor system for slab with beams

For the two-way slab with beams design problem-1, Compute the
ratio  of the flexural stiffness of the longitudinal beam to that of
the slab in the equivalent rigid frame for all the beams around
panels 1, 2, 3, and 4 in Fig.-3.

The University of Lahore,


Civil Engineering Department 78
Islamabad Campus
(a) B1-B2, Referring to Fig.3, the effective width bE for B1-B2 is the
smaller of 14 + 2 (21.5) = 57 and 14 + 8 (6.5) =66
thus bE = 57 in. Using Eq.11

Fig.-3

The University of Lahore,


Civil Engineering Department 79
Islamabad Campus
Fig.-4

The University of Lahore,


Civil Engineering Department 80
Islamabad Campus
bE 57 t 6. 5
  4.07,   0.232
b w 14 h 28
3
1428 
k  1.774, Ib  1.774  45,400 in.4
12

Using Eq.9, where Ecb=Ecs

1 EcbIb 45400
Is  240 6.53  5490 in.4    8.27
12 EcsIs 5490

The University of Lahore,


Civil Engineering Department 81
Islamabad Campus
(b) B3-B4, Referring to Fig.3, the effective width bE for B3-B4 is
the smaller of 14 + 21.5 =35.5 in. and14 + 4 (6.5) = 40; thus
bE = 35.5 in. Using Eq.11

bE 35.5 t 6. 5
  2.54,   0.232
bw 14 h 28
3
1428 
k  1.484, Ib  1.484  38,000 in.4
12

Using Eq.9, where Ecb=Ecs

1 E cbIb 38,000
Is  120 6.53  2745 in.4    13.83
12 EcsIs 2745

The University of Lahore,


Civil Engineering Department 82
Islamabad Campus
(c) B5-B6, Referring to Fig.4, the effective width bE for B5-B6 is the
smaller of 12 + 2 (17.5) = 47 in. and 12 + 8 (6.5) = 64
thus bE = 47 in. Using Eq.11

bE 47 t 6. 5
  3.92,   0.271
b w 12 h 24
3
1224 
k  1.762, Ib  1.762  24,400 in.4
12

Using Eq.9, where Ecb=Ecs

1 E cbIb 24,000
Is  300 6.53  6870 in.4    3.55
12 EcsIs 6870

The University of Lahore,


Civil Engineering Department 83
Islamabad Campus
(d) B7-B8, Referring to Fig.4, the effective width bE for B7-B8 is
the smaller of 12 +17.5 = 29.5 in. and12 + 4 (6.5) = 38; thus
bE = 29.5 in. Using Eq.11
bE 29.5 t 6.5
  2.46,   0.271
bw 12 h 24
3
1224 
k  1.480, Ib  1.480  20,500 in.4
12
Using Eq.9, where Ecb=Ecs
1 3 EcbIb 20,500
Is    
150 6.5  3435 in.4    5.96
12 EcsIs 3435
The resulting  values for B1 to B8 around panels 1, 2, 3 and 4 are shown
in Fig.4. For the design, the  values vary between 3.55 and 13.83; thus
the equivalent rigid frames have their substantial portion along or close to
the column lines, even though their widths vary from 10 to 25 ft.
The University of Lahore,
Civil Engineering Department 84
Islamabad Campus
Minimum slab thickness for deflection control

To aid the designer, ACI provides a minimum thickness table for


slabs without interior beams, though there can be exterior
boundary beams. For slabs with beams spanning between the
supports on all sides, ACI provides “minimum thickness
equations”. If the designer wishes to use lesser thickness, ACI
permits "if shown by computation that the deflection will not
exceed the limits stipulated in Table." Computation of deflections
must "take into account size and shape of the panel, conditions of
support, and nature of restraints at the panel edges”.
The University of Lahore,
Civil Engineering Department 85
Islamabad Campus
Slab with Beams

Slab without Beams

The University of Lahore,


Civil Engineering Department 86
Islamabad Campus
Minimum slab thickness for deflection control
Slabs Supported on Beams.

Four parameters affect the equations of ACI for slabs supported


on beams on all sides; they are (1) the longer clear span Ln of the
slab panel; (2) the ratio β of the longer clear span Ln to the shorter
clear span Sn; (3) the yield strength fy of the steel reinforcement;
and (4) the average αm for the four α values for relative stiffness of
a panel perimeter beam compared to the slab

In terms of these parameters, ACI requires the following for "slabs


with beams spanning between the supports on all sides.”

The University of Lahore,


Civil Engineering Department 87
Islamabad Campus
Minimum slab thickness for deflection control
Slabs Supported on Beams.
Slabs supported on shallow beams where αm ≤ 0.2.

The minimum slab thickness requirements are the same as for slabs without
interior beams.

Slabs supported on medium stiff beams where 0.2 < αm < 2.0.
 fy 
L n  0 . 8  
For this case,  200 ,000 
Min t  (12 )
36  5  (  m  0 . 2 )
The minimum is not be less than 5 in.

Slabs supported on very stiff beams where αm > 2.0.


 fy 
L n  0 . 8  
For this case,  200 ,000 
Min t  (13 )
36  9 
The minimum is not to be less than 3.5 in.
The University of Lahore,
Civil Engineering Department 88
Islamabad Campus
Minimum slab thickness for deflection control
Slabs Supported on Beams.

Edge beams at discontinuous edges.

For all slabs supported on beams, there must be an edge beam at


discontinuous edges having a stiffness ratio  not less than 0.80,
or the minimum thickness required by Eqs.(12) or (13) "shall be
increased by at least 10 percent in the panel with the
discontinuous edge."

The University of Lahore,


Civil Engineering Department 89
Islamabad Campus
Nominal requirements for slab thickness and size of edge
beams, column capital, and drop panel

Slab Thickness. As discussed in Section-5, ACI Formulas


[Eqs.12&13], along with ACI-Table [Table-1] set minimum slab
thickness for two-way floor systems. In addition, ACI set lower
limits for the minimum value based on experience and practical
requirements. These lower limits for two-way slab systems are
summarized:
Flat plates and flat slabs without drop panels 5 in.
Slabs on shallow interior beams having m < 0.2 5 in.
Slabs without interior beams but having drop panels 4 in.
Slabs with stiff interior beams having m  2.0 3.5 in.
The University of Lahore,
Civil Engineering Department 90
Islamabad Campus
Two way floor system for slab with beams

For the two-way slab with beams problem-1, Determine the


minimum thickness requirement for deflection control; and compare
it with the preliminary thickness of 6.5 in.

The University of Lahore,


Civil Engineering Department 91
Islamabad Campus
The average ratios αm for panels 1, 2, 3, and 4 may be computed from
the α values shown in Fig.4; thus

1
α m for panel 1  (5.96  8.27  3.55  13.83 )  7.90
4
1
α m for panel 2  (3.55  8.27  3.55  13.83)  7.30
4
1
α m for panel 3  (5.96  8.27  3.55  8.27 )  6.51
4

1
α m for panel 4  (3.55  8.27  3.55  8.27)  5.91
4

The University of Lahore,


Civil Engineering Department 92
Islamabad Campus
Since the αm values for all four panels are well above 2, Eq.13
applies. The minimum thickness for all panels, using Ln=24 ft,
Sn=18.83 ft, and fy=40,000 psi, become

 0 .2 f y 
L n  0.8  
 40,000  24121.0
min t    6.07 in.
9L n 924 
36  36 
Sn 18.83

If a uniform slab thickness for the entire floor area is to be used,


the minimum for deflection control is 6.07 in., which compares
well with the 6.5 in. preliminary thickness.
The University of Lahore,
Civil Engineering Department 93
Islamabad Campus
Two way floor system for slab with beams

ASSIGNMENT

For the two-way slab with beams problem-1, Show that the six
limitations of the direct design method are satisfied.

The University of Lahore,


Civil Engineering Department 94
Islamabad Campus
The first four limitations are satisfied by inspection. For the fifth
limitation,
150
service dead load w D  6.5  81 psf
12
service live load w L  120 psf
w L 120
= 2
wD 81
For the sixth limitation, referring to Fig.3&4 and taking L1 and L2 in
the long and short directions, respectively,
Panel 1, L21 625
  56.5
α1 0.5(13.83  8.27)
L22 400
  84.0
α 2 0.5(5.96  3.55)
The University of Lahore,
Civil Engineering Department 95
Islamabad Campus
Panel 2, L21 625
  56.5
α1 0.5(13.83  8.27)

L22 400
  112.7
α 2 3.55

Panel 3, L21 625


  75.6
α1 8.27
L22 400
  84.0
α 2 0.5(5.96  3.55)

L21 625
Panel 4   75.6
α1 8.27
L22 400
  112.7
α 2 3.35
L21 L22
All ratios of to lie between 0.2 and 5.
1  2
The University of Lahore,
Civil Engineering Department 96
Islamabad Campus
Longitudinal Distribution of Moments
Fig.19 shows the longitudinal moment diagram for the Typical
Interior Span of the equivalent rigid frame in a two-way floor
system, as prescribed by ACI.

Fig.19

where l
M o  w u L 2 L2n (15 )
8
The University of Lahore,
Civil Engineering Department 97
Islamabad Campus
The University of Lahore,
Civil Engineering Department 98
Islamabad Campus
Longitudinal distribution of moments
For a span that is completely fixed at both ends, the negative
moment at the fixed end is twice as large as the positive
moment at midspan.
For a typical interior span satisfying the limitations for the direct
design method, the specified negative moment of 0.65Mo is a
little less than twice the specified positive moment of 0.35Mo,
which is fairly reasonable because the restraining effect of the
columns and adjacent panels is definitely less than that of a
completely fixed-ended beam.

The University of Lahore,


Civil Engineering Department 99
Islamabad Campus
Longitudinal distribution of moments
For the exterior span, ACI provides the longitudinal moment
diagram for each of the five categories as described in Fig.20 to
24.

Fig.20 Fig.21

The University of Lahore,


Civil Engineering Department 100
Islamabad Campus
(8) Longitudinal distribution of moments

Fig.23

Fig.22
Fig.24

The University of Lahore,


Civil Engineering Department 101
Islamabad Campus
The University of Lahore,
Civil Engineering Department 102
Islamabad Campus
Longitudinal distribution of moments
The negative moment at the exterior support increases from 0 to
0.65Mo, the positive moment within the span decreases from
0.63Mo to 0.35Mo, and the negative moment at the interior support
decreases from 0.75Mo to 0.65Mo all gradually as the restraint at
the exterior support increases from the case of a masonry wall
support to that of a reinforced concrete wall built monolithically
with the slab.
ACI Commentary states that high positive moments are purposely
assigned into the span since design for exterior negative moment
will be governed by minimum reinforcement to control cracking.
The University of Lahore,
Civil Engineering Department 103
Islamabad Campus
Longitudinal distribution of moments

Regarding the ACI Code suggested moment diagrams of Figs.19


to 24, ACI permits these moments to be modified by 10% provided
the total factored static moment Mo for the panel is statically
accommodated.

The University of Lahore,


Civil Engineering Department 104
Islamabad Campus
Two way floor system for slab with beams

For the two-way slab with beams problem-1, Determine the


longitudinal moments in frames A, B, C, and D. as shown in Fig.2&5.

The University of Lahore,


Civil Engineering Department 105
Islamabad Campus
(a) Check the six limitations for the direct design method. These
limitations have been checked previously.

(b) Total Factored Static Moment Mo

The total factored static moments M0 for the equivalent rigid frames A,
B, C, and D have been computed previously; they are

M0 (frame A) = 448 ft-kips

M0 (frame B) = 224 ft-kips

M0 (frame C) = 349 ft-kips

M0 (frame D) = 175 ft-kips


The University of Lahore,
Civil Engineering Department 106
Islamabad Campus
Fig.-5

The University of Lahore,


Civil Engineering Department 107
Islamabad Campus
Fig.-6

The University of Lahore,


Civil Engineering Department 108
Islamabad Campus
Longitudinal Moments in the frames

The longitudinal moments in frames A, B, C, and D are computed


using Case-2 of Fig.21(DDM) for the exterior span and Fig.19(DDM)
for the interior span. The computations are as shown below, and
the results are summarized in Fig.-5&6.

The University of Lahore,


Civil Engineering Department 109
Islamabad Campus
For Frame A: M0=448 ft-kips

Mneg at exterior support = 0.16(448) =72 ft-kips

Mpos in exterior span = 0.57(448) =255 ft-kips

Mneg at first interior support = 0.70(448) =313 ft-kips

Mneg at typical interior support = 0.65(448) =291 ft-kips

Mpos in typical interior span = 0.35(448) =157 ft-kips


The University of Lahore,
Civil Engineering Department 110
Islamabad Campus
For Frame B: M0=224 ft-kips

Mneg at exterior support = 0.16(224) =36 ft-kips

Mpos in exterior span = 0.57(224) =128 ft-kips

Mneg at first interior support = 0.70(224) =157 ft-kips

Mneg at typical interior support = 0.65(224) =146 ft-kips

Mpos in typical interior span = 0.35(224) =78 ft-kips


The University of Lahore,
Civil Engineering Department 111
Islamabad Campus
For Frame C: M0=349 ft-kips

Mneg at exterior support = 0.16(349) = 56 ft-kips

Mpos in exterior span = 0.57(349) = 199 ft-kips

Mneg at first interior support = 0.70(349) = 244 ft-kips

Mneg at tupical interior support = 0.65(349) =227 ft-kips

Mpos in typical interior span = 0.35(349) =122 ft-kips


The University of Lahore,
Civil Engineering Department 112
Islamabad Campus
For Frame D: M0=175 ft-kips

Mneg at exterior support = 0.16(175) =28 ft-kips

Mpos in exterior span = 0.57(175) =100 ft-kips

Mneg at first interior support = 0.70(175) =123 ft-kips

Mneg at tupical interior support = 0.65(175) =114 ft-kips

Mpos in typical interior span = 0.35(175) =61 ft-kips


The University of Lahore,
Civil Engineering Department 113
Islamabad Campus
Transverse Distribution
Torsional constant ‘C’ of the transverse beam
One important parameter useful for the Transverse Distribution
of the Longitudinal Moment is the Torsional Constant C of the
transverse beam spanning from column to column. Even if there
is no such beam (as defined by projection above or below the
slab) actually visible, for the present use one still should imagine
that there is a beam made of a portion of the slab having a width
equal to that of the column, bracket, or capital in the direction of
the span for which moments are being determined.

The University of Lahore,


Civil Engineering Department 114
Islamabad Campus
Torsion constant ‘C’ of the transverse beam
When there is actually a transverse beam web above or below the
slab, the cross-section of the transverse beam should include the
portion of slab within the width of column, bracket, or capital
described in Fig.26 plus the projection of beam web above or
below the slab. As a third possibility, the transverse beam may
include that portion of slab on each side of the beam web equal to
its projection above or below the slab, whichever is greater, but
not greater than four times the slab thickness. The largest of the
three definitions as shown in Fig.26 may be used.

The University of Lahore,


Civil Engineering Department 115
Islamabad Campus
Torsion constant ‘C’ of the transverse beam

(a) (b) (c)


Fig.26: Definition of cross-sections for transverse beams in torsion
[Projection of slab beyond beam in case (c) is allowed on each
side for interior beam
The University of Lahore,
Civil Engineering Department 116
Islamabad Campus
Torsion constant ‘C’ of the Transverse Beam
The torsional constant C of the transverse beam equals,
 x  x 3 y 
C    1  0 . 63    (17 )
 y  3 
where
x = shorter dimension of a component rectangle
y = longer dimension of a component rectangle

and the component rectangles should be taken in such a way


that the largest value of C is obtained.

The University of Lahore,


Civil Engineering Department 117
Islamabad Campus
Two way floor system for slab with beams

For the two-way slab with beams problem-1, Compute the torsional
constant C for the edge and interior beams in the short and long
directions

The University of Lahore,


Civil Engineering Department 118
Islamabad Campus
Each cross-section shown in Fig.7 may be divided into component
rectangles in two different ways and the larger value of C is to be
used.

Fig.-7
The University of Lahore,
Civil Engineering Department 119
Islamabad Campus
For short direction,

 edge   0.63(6.5)  29.5(6.5)3  0.63(12)  17.5(12)3


C   1    1  
 beam   29. 5  3  17. 5  3
 2325  5725  8050 in4
or

 edge   0.63(6.5)  17.5(6.5)3  0.63(12)  24(12)3


C   1    1 
 beam   17.5  3  24  3
 1230  9470  10,700 in4 Use
The University of Lahore,
Civil Engineering Department 120
Islamabad Campus
For short direction,

 int erior   0.63( 6.5)  47( 6.5)3  0.63(12)  17.5(12)3


C   1    1 
 beam   47  3  17.5  3
 3925  5725  9650 in4
or

 int erior 
C   2(1230)  9470  11,930 in4 Use
 beam 
The University of Lahore,
Civil Engineering Department 121
Islamabad Campus
For long direction,

 edge   0.63(6.5)  35.5(6.5)3  0.63(14)  21.5(14)3


C   1    1 
 beam   35.5  3  21.5  3
 2900  11,600  14,500 in4
or

 edge   0.63(6.5)  21.5(6.5)3  0.63(14)  28(14)3


C   1    1  
 beam   21 .5  3  28  3
 1600  17,500  19,100 in4 Use
The University of Lahore,
Civil Engineering Department 122
Islamabad Campus
For long direction,

 int erior   0.63(6.5)  57( 6.5)3  0.63(14)  28(14)3


C   1    1  
 beam   57  3  28  3
 4800  11,600  16,400 in4
or

 int erior 
C   2(1600)  17,500  20,700 in4 Use
 beam 
The University of Lahore,
Civil Engineering Department 123
Islamabad Campus
Transverse distribution of longitudinal moment

The longitudinal moment


values shown in Figs.19
to 24 are for the entire
width of the equivalent
rigid frame.

Fig.27
Each of these moments is to be divided between the column strip and the two half middle strips as
defined in Fig.27.
The University of Lahore,
Civil Engineering Department 124
Islamabad Campus
The University of Lahore,
Civil Engineering Department 125
Islamabad Campus
M0 to Longitudinal Distribution

Longitudinal to Transverse Distribution

The University of Lahore,


Civil Engineering Department 126
Islamabad Campus
Transverse distribution of longitudinal moment

If the two adjacent transverse spans are each equal to L2, the
width of the column strip is then equal to one-half of L2, or one-half
of the longitudinal span L1, whichever is smaller. This seems
reasonable, since when the longitudinal span is shorter than the
transverse span, a larger portion of the moment across the width
of the equivalent frame might be expected to concentrate near the
column centerline.

The University of Lahore,


Civil Engineering Department 127
Islamabad Campus
(12) Transverse distribution of longitudinal moment
The transverse distribution of the longitudinal moment to column
and middle strips is a function of three parameters, using L1 and
L2 for the longitudinal and transverse spans, respectively:
(1) the aspect ratio L2/L1
E cb Ib
(2) the ratio  1  of the longitudinal beam stiffness to slab
E cs Is
stiffness.
E cb C
(3) the ratio t  of the torsional rigidity of edge beam
2E cs Is
section to the flexural rigidity of a width of slab equal to the
span length of the edge beam.

The University of Lahore,


Civil Engineering Department 128
Islamabad Campus
(12) Transverse distribution of longitudinal moment

According to ACI, the column strip is to take the percentage of


the longitudinal moment as shown in Table-2. As may be seen
from Table-2, only the first two parameters affect the transverse
distribution of the negative moments at the first and typical interior
supports as well as the positive moments in exterior and interior
spans, but all three parameters are involved in the transverse
distribution of the negative moment at the exterior support.

The University of Lahore,


Civil Engineering Department 129
Islamabad Campus
Table-2:Percentage of longitudinal moment in column strip
ASPECT RATIO L2/L1 0.5 1.0 2.0

Negative moment at α1L2/L1 =0 βt=0 100 100 100


exterior support βt2.5 75 75 75
α1L2/L1 > 1.0 βt = 0 100 100 100

βt> 2.5 90 75 45
Positive moment α1L2/L1 =0 60 60 60
α1L2/L1 > 1.0 90 75 45
Negative moment at α1L2/L1 =0 75 75 75
interior support α1L2/L1 > 1.0 90 75 45

The University of Lahore,


Civil Engineering Department 130
Islamabad Campus
Transverse distribution of longitudinal moment
Regarding the distributing percentages shown in Table-2, the
following observations may be made:
(1) In general, the column strip takes more than 50% of the longitudinal
moment.

(2) The column strip takes a larger share of the negative longitudinal
moment than the positive longitudinal moment.
(3) When no longitudinal beams are present, the column strip takes the
same share of the longitudinal moment, irrespective of the aspect ratio.
The column strip width is a fraction of L1 or L2 (0.25L1 or 0.25L2 on each
side of column line), whichever is smaller.

The University of Lahore,


Civil Engineering Department 131
Islamabad Campus
Transverse distribution of longitudinal moment
(4) In the presence of longitudinal beams, the larger the aspect ratio, the
smaller the distribution to the column strip. This seems consistent
because the same reduction in the portion of moment going into the slab
is achieved by restricting the column strip width to a fraction of L1 when
L2/L1 is greater than one.

(5) The column strip takes a smaller share of the exterior moment as the
torsional rigidity of the edge beam section increases.
When the exterior support consists of a column or wall extending for a
distance equal to or greater than three-fourths of the transverse width,
the exterior negative moment is to be uniformly distributed over the
transverse width.
The University of Lahore,
Civil Engineering Department 132
Islamabad Campus
Transverse distribution of longitudinal moment
The procedure for distributing the longitudinal moment across a
transverse width to the column and middle strips may be
summarized as follows:

(1) Divide the total transverse width applicable to the longitudinal


moment into a column strip width and two half middle strip widths,
one adjacent to each side of the column strip. For an exterior
column line, the column strip width is ¼ L1, or ¼ L2, whichever is
smaller; for an interior column line, the column strip width is
Σ(¼ L1 or ¼ L2, whichever is smaller, of the panels on both sides).

The University of Lahore,


Civil Engineering Department 133
Islamabad Campus
Transverse distribution of longitudinal moment
E cb C
(2) Determine the ratio  t  of edge beam torsional rigidity
2E cs Is
to slab flexural rigidity. (The 2 arises from approximating the shear
E cb
modulus of elasticity in the numerator as )
E I 2
(3) Determine the ratio  1  cb b of longitudinal beam flexural
E cs Is
stiffness to slab flexural stiffness.

(4) Divide the longitudinal moment at each critical section into two
parts according to the percentage shown in Table-2: one part to
the column strip width; and the remainder to the half middle strip
for an exterior column line, or to the half middle strips on each
side of an interior column line.
The University of Lahore,
Civil Engineering Department 134
Islamabad Campus
Transverse distribution of longitudinal moment

(5) If there is an exterior wall instead of an exterior column line,


the strip ordinarily called the exterior column strip will not deflect
and therefore no moments act. In this case there can be no
longitudinal distribution of moments; thus there is no computed
moment to distribute laterally to the half middle strip adjacent to
the wall. This half middle strip should be combined with the next
adjacent half middle strip, which itself receives a lateral
distribution in the frame of the first interior column line. The total
middle strip in this situation is designed for twice the moment in
the half middle strip from the first interior column line.
The University of Lahore,
Civil Engineering Department 135
Islamabad Campus
Distribution of moment in column strip to beam and slab

When a longitudinal beam exists in the column strip along the


column centerline, the column strip moment as determined by
the percentages in Table-2 should be divided between the beam
and the slab. ACI states that 85% of this moment be taken by
the beam if αL2/L1 is equal to or greater than 1.0, and for values
of L2/L1 between 1.0 and 0, the proportion of moment to be
resisted by the beam is to be obtained by linear interpolation
between 85 and 0%. In addition, any beam must be designed to
carry its own weight (projection above and below the slab), and
any concentrated or linear loads applied directly on it.
The University of Lahore,
Civil Engineering Department 136
Islamabad Campus
The University of Lahore,
Civil Engineering Department 137
Islamabad Campus
Factored Moments in Beams. ACI Code 13.6.5

 Beams between supports shall be proportioned to resist


85 % of column strip moment if α1L2/L1 > 1.0
 For values of α1L2/L1 between zero and 1.0,linear
interpolation between zero and 85 % shall be done.
 In addition to moments above, beams shall be
proportioned to resist moments caused by concentrated
or linear load applied directly to the beams including
weight of projecting beam stem above or below the slab.

Factored Moments in Middle Strip. ACI Code 13.6.6


 Negative and positive B.M. not resisted by the column
strip shall be resisted by middle strip.
The University of Lahore,
Civil Engineering Department 138
Islamabad Campus
Factored Shear in Beams. ACI Code 13.6.8

 Beams with α1L2/L1 > 1.0 shall be proportioned to resist


shear caused by factored loads on tributary areas which
are bounded by 45 deg lines drawn from the corner of
the panel and the centerlines of the adjacent panels
parallel to the long sides.
 For beams with α1L2/L1 between zero and 1.0, linear
interpolation shall be permitted.
 In addition to shear calculated above, beams shall be
proportioned to resist shear caused by factored loads
applied directly on beams.

The University of Lahore,


Civil Engineering Department 139
Islamabad Campus
The University of Lahore,
Civil Engineering Department 140
Islamabad Campus
Factored Moments in Columns and Walls.
ACI CODE 13.6.9

 Columns and walls built integrally with a slab system shall


resist moments caused by factored loads on the slab
system.

 At an interior support, supporting elements above and


below the slab shall resist the moment specified by the
following equation in direct proportion to their stiffness
unless a general analysis is made.
M=0.07[(wd+0.5wl)L2.L2n - w`d.L`2.L`2n]
Where w`d , L`2 and L`2n . refer to short span.
The University of Lahore,
Civil Engineering Department 141
Islamabad Campus
The University of Lahore,
Civil Engineering Department 142
Islamabad Campus
Two way floor system for slab with beams

For the two-way slab with beams as described in problem-1,


Distribute the longitudinal moments computed for frames A,
B, C, and D [Fig.5&6] into three parts-- for the longitudinal
beam, for the column strip slab, and for the middle strip slab.

The University of Lahore,


Civil Engineering Department 143
Islamabad Campus
(a) Negative moment at the face of exterior support
For Frame A,
L2
 0.80
L1
1  8.27
L
1 2  6.61
L1
C  10,700 in 4
(Torsional Constant of
edge beam in Short Direction )

Mo = 448 kip-ft
(20 x12).(6.5) 3
Is   5490 in 4
12
C 10,700
t    0.98
2I s 2(5490)
The University of Lahore,
Civil Engineering Department 144
Islamabad Campus
(a) Negative moment at the face of exterior support

Table-1 shows the linear interpolation for obtaining the column strip
percentages from the prescribed limits of Table-2(DDM). The total
moment of 72 ft-kips is divided into three parts, 92.6% to column
strip (of which 85% goes to the beam and 15% to the slab) and 7.4%
to the middle strip slab. The results are shown in Table-2

The University of Lahore,


Civil Engineering Department 145
Islamabad Campus
Table-1: Linear interpolation for column strip percentage of
exterior negative moment-frame A

L2 0.5 0.8 1.0


L1

βt=0 100% 100% 100%


L2
1  6.61 βt=0.98 96.1% 92.6% 90.2%
L1
βt≥2.50 90% 81% 75%

The University of Lahore,


Civil Engineering Department 146
Islamabad Campus
(b) Negative moments at exterior face of first interior support
and at face of typical interior support.
Frame A L2
 0.80
L1
L2
1  6.61  1.0
L1

Using the prescribed values in


Table-2(DDM), the proportion of
moment going to the column strip is determined to be 81% by linear
interpolation.
L2 0.5 0.8 1.0
L1
L 90% 81% 75%
1 2  6.61
L1
The University of Lahore,
Civil Engineering Department 147
Islamabad Campus
Table-2: Transverse Distribution of Longitudinal Moments

Frame A
Total width = 20 ft, Column strip width=10 ft, Middle strip width = 10 ft
EXTERIOR SPAN INTERIOR SPAN

EXTERIOR INTERIOR
NEGATIVE POSITIVE NEGATIVE NEGATIVE POSITIVE
Total Moment -72 +255 -313 -291 +157

Moment in beam -57 +176 -216 -200 +108

Moment in column -10 +31 -38 -36 +19


strip slab
Moment in middle -5 +49 -60 -55 +30
strip slab

-72 -313 -291 -291


+255 +157
Moments in A
The University of Lahore, Civil Engineering Department 148
Islamabad Campus
(a) Negative moment at the face of
exterior support.
Frame B,
NOTE :
Moment of Inertia of Slab Is , while calculating
βt, will be same for Both Rigid Frame A and B

L2
 0.80
L1
1  13.83
L2
1  11.1
L1
 t  0.98, the same as for frame A
The column strip moment percentage  92.6%
the same as for frame A

The University of Lahore,


Civil Engineering Department 149
Islamabad Campus
(b) Negative moments at exterior face of first interior support and
at face of typical interior support.
Frame B,
The proportion of
moment is 81% for column strip, the same as for frame A.

L2
 0.80
L1
L2
1  11.1
L1

The University of Lahore,


Civil Engineering Department 150
Islamabad Campus
Table-3: Transverse distribution of longitudinal moments

Frame B
TOTAL WIDTH = 10 ft, COLUMN STRIP WIDTH=5 ft, MIDDLE STRIP WIDTH = 5 ft
EXTERIOR SPAN INTERIOR SPAN

EXTERIOR INTERIOR
NEGATIVE POSITIVE NEGATIVE NEGATIVE POSITIVE
Total Moment -36 +128 -157 -146 +78

Moment in beam -28 +88 -108 -101 +54

Moment in column -5 +16 -19 -17 +9


strip slab
Moment in middle -3 +25 -30 -28 +15
strip slab

-36 -157 -146 -146


+128 +78
Moments in B
The University of Lahore,
Civil Engineering Department 151
Islamabad Campus
(a) Negative moment at the face of exterior support.
Frame C,
L2
 1.25
L1
1  3.55
L2
1  4.44
L1
C  19,100 in 4 (Torsional Constant of
edge beam in Long Direction )
300(6.5) 3
Is 
12
 6870 in 4
C
t 
(2 I s )
19,100

2(6870)
 1.39
The University of Lahore,
Civil Engineering Department 152
Islamabad Campus
(a) Negative moment at the face of exterior support.

Table-4 shows the linear interpolation for obtaining the column strip
percentage from the prescribed limits of Table-2(DDM). The total moment
of 56 ft-kips is divided into three parts, 81.9% to column strip (of which 85%
goes to the beam and 15% to the slab since and 18.1% to
the middle strip slab. The results are summarized in Table-5
L2
1  4.44  1.0
L1
Table-4: Linear interpolation for column strip
percentage of exterior negative moment-frame C
L2/L1 0.5 0.8 1.0

L βt=0 100% 100% 100%


1 2  4.44 βt=1.39 86.1% 81.9% 69.4%
L1
βt≥2.50 75% 67.5% 45%
The University of Lahore,
Civil Engineering Department 153
Islamabad Campus
(b) Negative moments at exterior face of first interior support
and at face of typical interior support.
Frame C,
Using the prescribed values in
Table-2(DDM), the proportion of
moment going to the column strip is determined to be 67.5% by
linear interpolation:
L2
 1.25
L1
L2
1  4.44
L1 L2 1.0 1.25 2.0

L1
L 75% 67.5% 45%
1 2  4.44
L1

The University of Lahore,


Civil Engineering Department 154
Islamabad Campus
Table-5: Transverse Distribution of Longitudinal Moments in Two-
Way Slab with beams
Frame C
TOTAL WIDTH = 25 ft, COLUMN STRIP WIDTH=10 ft, MIDDLE STRIP WIDTH = 15 ft
EXTERIOR SPAN INTERIOR SPAN

EXTERIOR INTERIOR
NEGATIVE POSITIVE NEGATIVE NEGATIVE POSITIVE
Total Moment -56 +199 -244 -227 +122

Moment in beam -39 +114 -140 -130 +70

Moment in column -7 +20 -25 -23 +13


strip slab
Moment in middle -10 +65 -79 -74 +40
strip slab

-56 -244 -227 -227


+199 +122
Moments in C
The University of Lahore,
Civil Engineering Department 155
Islamabad Campus
(a) Negative moment at the face of exterior support.
Frame D,

L2
 1.25
L1
1  5.96
L2
1  7.45
L1
 t  1.39
(the same as for frame C)
The column strip moment percentage  81.9%
(the same as for frame C)
The University of Lahore,
Civil Engineering Department 156
Islamabad Campus
(b) Negative moments at exterior face of first interior support
and at face of typical interior support.
Frame D,
The proportion of
moment is again 67.5% for column strip, the same as for frame C.

L2
 1.25
L1
L2
1  7.47
L1

The University of Lahore,


Civil Engineering Department 157
Islamabad Campus
Table-6: Transverse distribution of longitudinal moments

Frame D
TOTAL WIDTH = 25 ft, COLUMN STRIP WIDTH=10 ft, MIDDLE STRIP WIDTH = 15 ft
EXTERIOR SPAN INTERIOR SPAN

EXTERIOR INTERIOR
NEGATIVE POSITIVE NEGATIVE NEGATIVE POSITIVE
Total Moment -28 +100 -123 -114 +61

Moment in beam -20 +57 -71 -65 +35

Moment in column -3 +10 -12 -12 +6


strip slab
Moment in middle -5 +33 -40 -37 +20
strip slab

-28 -123 -114 -114


+100 +61

Moments in D
The University of Lahore,
Civil Engineering Department 158
Islamabad Campus
(c) Positive moments in exterior and interior spans.
L2
Since the prescribed limits for 1  1.0 are the same for positive
L1
moment and for negative moment at interior support. The
percentage of column strip moment for positive moments in exterior
and interior spans are identical to those for negative moments as
determined in part (b) above.

The University of Lahore,


Civil Engineering Department 159
Islamabad Campus
After calculating Moments, we can find the then Ast required
The University of Lahore,
Civil Engineering Department 160
Islamabad Campus
The University of Lahore,
Civil Engineering Department 161
Islamabad Campus
Design of slab thickness and reinforcement

The thickness of a floor slab must be determined early in


design because the weight of the slab is an important part
of the dead load of the structure. The minimum thickness
can be determined by many factors:

• Shear strength of beamless slabs (usually a controlling


factor); slab must be thick enough to provide adequate
shear strength
• Flexural moment requirement (less often a governing
factor)
• Fire resistance requirements
• Deflection control (most common thickness limitations)

The University of Lahore,


Civil Engineering Department 162
Islamabad Campus
Design of slab thickness and reinforcement
Slab Thickness.

Ordinarily the minimum thickness specified in ACI controls the


thickness for design. Of course, reinforcement for bending moment
must be provided, but the reinforcement ratio  required is usually well
below 0.5max; thus, it does not dictate slab thickness.

The shear requirement for two-way slabs (with beams) may be


investigated by observing strips 1-1 and 2-2 in Fig.28. Beams with
1L2/L1 values larger than 1.0 are assumed to carry the loads acting on
the tributary floor areas bounded by 45° lines drawn from the corners of
the panel and the centerline of the panel parallel to the long side.

The University of Lahore,


Civil Engineering Department 163
Islamabad Campus
Design of slab thickness and reinforcement
Slab Thickness.

Fig.28

The University of Lahore,


Civil Engineering Department 164
Islamabad Campus
Design of slab thickness and reinforcement
Slab Thickness.
If this is the case, the loads on the trapezoidal areas E and F of
Fig.28 go to the long beams, and those on the triangular areas G
and H go to the short beams. The shear per unit width of slab
along the beam is highest at the ends of slab strips 1-1 and 2-2,
which, considering the increased shear at the exterior face of the
first interior support, is approximately equal to

 w uS 
Vu  1.15  (18 )
 2 

The University of Lahore,


Civil Engineering Department 165
Islamabad Campus
Design of slab thickness and reinforcement
Slab Thickness.

If α1L2/L1 is equal to zero, there is, of course, no load on the


beams (because there are no beams). When the value of α1L2/L1
is between 0 and 1.0, the percentage of the floor load going to the
beams should be obtained by linear interpolation. In such a case,
the shear expressed by Eq.18 would be reduced, but the shear
around the column due to the portion of the floor load going
directly to the columns by two-way action should be investigated
as for flat plate floors.

The University of Lahore,


Civil Engineering Department 166
Islamabad Campus
Design of slab thickness and reinforcement
Reinforcement
When the nominal requirements for slab thickness as discussed in
section 6 are satisfied, no compression reinforcement will likely be
required. The tension steel area required within the strip being
considered can then be obtained by the following steps:

factored moment Mu in the strip


(1) required Mn 
(  0.90)
(2)
fy Mn
m  , Rn 
0 . 85 f c bd 2

1  2mR n 

 1 1 , A s   bd
m  fy 
The University of Lahore,

Civil Engineering Department 167
Islamabad Campus
Design of slab thickness and reinforcement
Reinforcement

After obtaining the steel area As required within the strip, a


number of bars may be chosen so that they provide either the
area required for strength or the area required for shrinkage and
temperature reinforcement, which is 0.002bt for grades 40 and 50
steel and 0.0018bt for grade 60. The spacing of reinforcing bars
must not exceed 2 times the slab thickness, except in slabs of
cellular or ribbed construction where the requirement for
shrinkage and temperature reinforcement governs (i.e., 5 times
the slab thickness but not greater than 18 in.).
The University of Lahore,
Civil Engineering Department 168
Islamabad Campus
Design of slab thickness and reinforcement
Reinforcement details in slabs without beams
Fig.29 provides detailed dimensions for minimum extensions required
for each portion of the total number of bars in the column and middle
strips.

For unbraced frames, reinforcement lengths must be determined by


analysis but not less than those prescribed in Fig.29. ACI requires that
the use of “Integrity Steel” which consists of a minimum of two of the
column strip bottom bars passing continuously (or spliced with class A
splice or anchored within support) through the column core in each
direction. The purpose of this integrity steel is to provide some residual
strength following a single punching shear failure.

The University of Lahore,


Civil Engineering Department 169
Islamabad Campus
The University of Lahore,
Fig.29
Islamabad Campus
Civil Engineering Department 170
Design of slab thickness and reinforcement
Corner reinforcement for two-way slab(with beams).
It is well known from plate bending
theory that a transversely loaded slab
simply supported along four edges will
tend to develop corner reactions as
shown in Fig.30, for Fig.30
which reinforcement must be provided. Thus in slabs supported on
beams having a value of  greater than 1.0, special reinforcement
(Fig.31) shall be provided at exterior corners in both the bottom and top
of the slab. This reinforcement (ACI) is to be provided for a distance in
each direction from the corner equal to one-fifth the longer span.
The University of Lahore,
Civil Engineering Department 171
Islamabad Campus
Design of slab thickness and reinforcement
Corner reinforcement for two-way slab(with beams).
The reinforcement in both the top and bottom of the slab must be
sufficient to resist a moment equal to the maximum positive
moment per foot of width in the slab, and it may be placed in a
single band parallel to the diagonal in the top of the slab and
perpendicular to the diagonal in the bottom of the slab, or in two
bands parallel to the sides of the slab.

The University of Lahore,


Fig.31
Islamabad Campus
Civil Engineering Department 172
Design of slab thickness and reinforcement
Crack Control
In addition to deflection control, crack control is the other major
serviceability requirement usually considered in the design of
flexural members. ACI gives criteria for beams and one-way slabs
to ensure distribution of flexural reinforcement to minimize crack
width under service loads.

The University of Lahore,


Civil Engineering Department 173
Islamabad Campus
Design of slab thickness and reinforcement
Crack Control

No ACI Code provisions are given for two-way floor systems;


however, ACI Committee has suggested a formula to predict the
possible crack width in two-way acting slabs, flat slabs, and flat
plates. When the predicted crack width is considered excessive
(there are no ACI Code limits for slabs), the distribution (size and
spacing) of flexural reinforcement may be adjusted to decrease
predicted crack width. Ordinarily crack width is not a problem on
two-way acting slabs, but when steel with fy equal to 60,000 psi or
higher is used, crack control should be considered.
The University of Lahore,
Civil Engineering Department 174
Islamabad Campus
Other Requirements of ACI Code

Detailing of flexural reinforcement for column supported two-way


slabs:
• Maximum spacing and minimum reinforcement requirement:
• Maximum spacing (ACI 8.7.2.2):
• Smax = 2 hf in each direction.
• Minimum Reinforcement (ACI 23.4.3.2):
• Asmin = 0.0018 bhf for grade 60.
• Asmin = 0.002 bhf for grade 40 and 50.

The University of Lahore,


Civil Engineering Department 175
Islamabad Campus
Other Requirements of ACI Code
Splicing:
ACI 8.7.4.2.1 requires that all bottom bars within the column
strip in each direction be continuous or spliced with length equal to 1.0
ld, (For development length see ACI 25.4.2.3 or Nelson 13th Ed, page
172 chapter 5 or mechanical or welded
splices)

Continuity of bars:
At least two of the column strip bars in each direction must
pass within the column core and must be anchored at exterior
supports (ACI 8.7.4.2.2).
The University of Lahore,
Civil Engineering Department 176
Islamabad Campus
Other Requirements of ACI Code

Standard Bar Cut off Points (Practical Recommendation)

Reinforcement should be provided at exterior corners in


both the bottom and top of the slab, for a distance in each
direction from the corner equal to one-fifth the longer span
of the corner panel as shown in figure. The positive and
negative reinforcement should be of size and spacing
equivalent to that required for maximum positive moments
(per foot of width) in the panel (ACI 13.3.6.1)

The University of Lahore,


Civil Engineering Department 177
Islamabad Campus
Two way floor system for slab with beams

Investigate if the preliminary slab thickness of 6.5” in the two-


way slab with beams design example as described in
problem-1, is sufficient for resisting flexure and shear.

The University of Lahore,


Civil Engineering Department 178
Islamabad Campus
For each of the equivalent frames A, B, C and D, the largest bending
moment in the slab occurs at the exterior face of the first interior
support in the middle strip slab. From tables-2,3,5,6, this moment
(Moment/width of Middle strip) is observed to be 60/10, 30/5,
79/15, or 40/7.5 ft-kips per ft. of width in frames A, B, C and D,
respectively. Taking the effective depth to the contact level between
the reinforcing bars in the two directions, and assuming #5 bars.

averaged d =6.50-0.75-0.63=5.12 in.


The largest Rn required is
Mu 6000(12)
Rn  2
 2
 254psi
bd 0.90(12)(5.12)
The University of Lahore,
Civil Engineering Department 179
Islamabad Campus
1  2mRn 
 fy
40,000
  1 1 m    15.686
m  fy 
 0.85 f c 0.853000

1  215.686 254  
 1  1    0.0067
15.686  40,000 

Reinforcement ratio  for this value of Rn is 0.0067, which is well below
0.375 ρ b  0.0139.

Hence excessive deflection should not be expected; this is further


verification of the minimum thickness formula given in ACI.

The factored floor load wu is

wu=1.4wD+1.7wL=318 psf

Since all 1L2/L1 values are well over 1.0, take V from Eq.18(DDM) as
The University of Lahore,
Civil Engineering Department 180
Islamabad Campus
FRAME – A
Reinforcement in Column Strip
(Total width = 20 ft, Column strip width=10 ft, Middle strip width = 10 ft)

Column Strip Column Strip


Exterior Span Interior Span
Exterior -ive Positive Interior -ive Exterior Positive
Mu (k-ft) -10 +31 -38 -36 +19
Effective depth (d) 5.5 5.5 5.5 5.5 5.5
b (in) 120 120 120 120 120
Rn = Mu/Øbd2 36.73 113.87 139.58 132.23 69.79
Steel Ratio (ρ) 0.00092 0.00291 0.00359 0.00340 0.00177
As = ρ.b.d (inc.2/ft) 0.610 1.923 2.370 2.242 1.168
Min. As = 0.002bh 1.56 1.56 1.56 1.56 1.56
As provided 1.56 1.923 2.370 2.242 1.56
Bar No.
#3 #3 #3 #3 #3
No. of Bars 15 18 22 21 15
Spacing
8 “ c/c 6.5 “ c/c 5 “ c/c 5.5 “ c/c 8 “ c/c
(Smax =2 x slab thickness)

The University of Lahore,


Civil Engineering Department 181
Islamabad Campus
FRAME – A
Reinforcement in Middle Strip
(Total width = 20 ft, Column strip width=10 ft, Middle strip width = 10 ft)

Middle Strip Middle Strip


Exterior Span Interior Span
Exterior –ive Positive Interior -ive Exterior Positive
Mu (k-ft) -5 +49 -60 -55 +30
Effective depth (d) 5.5 5.5 5.5 5.5 5.5
b (in) 120 120 120 120 120
Rn = Mu/Øbd2
18.37 179.98 220.39 202.02 110.19
Steel Ratio (ρ) 0.00046 0.00467 0.00577 0.00527 0.00282
As = ρ.b.d (inc.2/ft) 0.304 3.083 3.809 3.477 1.859
Min. As = 0.002bh 1.56 1.56 1.56 1.56 1.56
As provided 1.56 3.083 3.809 3.477 1.859
Bar No.
#3 #3 #4 #4 #3
No. of Bars 15 28 19 18 17
Spacing
8 “ c/c 4 “ c/c 6 “ c/c 6.5 “ c/c 7 “ c/c
(Smax =2 x slab thickness)
The University of Lahore,
Civil Engineering Department 182
Islamabad Campus
1.15w S 1.15(0.318 )(20)
V  u   3.66 kips
u 2 2

' 1
Vc  2 fc b w d  2 3000 (12)(5.12) 1000  6.73 kips

φVc  0.85(6.73) 5.72kips  Vu  3.66kips   ok

Factored shear 3.66 kips is the maximum at strip 1-1 of


Fig.28(DDM); actually the average for all such strips will be
lower.

The University of Lahore,


Civil Engineering Department 183
Islamabad Campus
D
ETAILING R EQUIREMENTS FOR T -W S S
WO AY LAB YSTEMS WITHOUT B
EAMS

The University of Lahore,


Civil Engineering Department 184
Islamabad Campus
The University of Lahore,
Civil Engineering Department 185
Islamabad Campus
The University of Lahore,
Civil Engineering Department 186
Islamabad Campus
Beam size requirement in flexure and shear

The size of the beams along the column centerlines in a two-way slab
(with beams) should be sufficient to provide the bending moment and
shear strengths at the critical sections.
For approximately equal spans, the largest bending moment should
occur at the exterior face of the first interior column where the available
section for strength computation is rectangular in nature because the
effective slab projection is on the tension side. Then with the preliminary
beam size the required reinforcement ratio  may be determined and
compared with 0.75b, the maximum value permitted under ACI. There
is no explicit limit for design according to ACI.

The University of Lahore,


Civil Engineering Department 187
Islamabad Campus
Beam size requirement in flexure and shear
Deflection is unlikely to be a problem with T-sections, but must be
investigated if excessive deflection may cause difficulty.

The maximum shear in the beam should also occur at the exterior face
of the first interior column. The shear diagram for the exterior span may
be obtained by placing the negative moments already computed for the
beam at the face of the column at each end and loading the span with
the percentage of floor load interpolated (ACI) between α1L2/L1=0. and
α1L2/L11.0. The stem (web) bwd should for practicality be sized such
that nominal shear stress
vn =Vu/(bwd) does not exceed about 6 fc at the critical section ‘d’
from the face of support.
The University of Lahore,
Civil Engineering Department 188
Islamabad Campus
Two way floor system for slab with beams

Investigate if the preliminary overall sizes of 1428 in. for the long
beam and 12  24 in for short beam are suitable for the two
way slab.

The University of Lahore,


Civil Engineering Department 189
Islamabad Campus
L2
1
• Since α, or of L1 are considerably larger than 1.0 for all beams spans,
there is to be no reduction of the floor loads going into the beams from the
tributary areas(ACI). As shown in Fig.8, the most critical span is B1 for the
long direction and B5 for the short direction. Actually the load acting on the
clear span of the beam should include the floor load (including the weight
of stem itself and or any other loads) directly over the beam stem width
plus floor load on the tributary areas bounded by the 45o lines from the
corner of the panel. Also for practical purpose it is acceptable to consider
the shear due to floor load at the face of column equal one-half of the floor
load on the tributary areas between column centerlines , as shown in fig.8.

The University of Lahore,


Civil Engineering Department 190
Islamabad Campus
Fig.-8

The University of Lahore,


Civil Engineering Department 191
Islamabad Campus
(a) Size of Long Beam B1.

The negative moments at the face of supports, 57 and 216 ft-Kips, are
taken from the table-2 , frame A
1421.5 
weight of beam stem  150  314 lb / ft
144
1
max imum negative moment  1.40.31423.752  216
10
 25  216  241 ft  kips
b  14 in. d  28  2.5 assume one layer of steel  25.5 in.
Mu 24112,000 
Rn  2
 2
 353 psi
b w d 0.9014 25.5 

1  2mR n 
 fy 40,000
 1 1 m    15.686
m  fy 
 0.85fc 0.853000 

1  215.686 353  

The University of Lahore,
1 1   0.0095
15.686 
Islamabad Campus 40,000
Civil Engineering Department
 192
(a) Size of Long Beam B1.
from figure which is well below 0.75b =0.027. Perhaps the beam
size should be reduced. From Fig.8

Total factored load on B1= 6.36(15) = 95.4 Kips


1
max Vu  1.15 (1.4) ( stem wt )( span / 2)  (Total Factored load on Beam)
2
( Moment Difference)

Clear Span
23.75 1 216  57
max Vu  1.151.40.314  95.4  
2 2 23.75
 6.0  47.7  6.7  60.4 kips
Vu 60,400
vn    200 psi  3.7 f c OK
bw d 0.851425.5
The University of Lahore,
Civil Engineering Department 193
Islamabad Campus
(b) Size of short beam B5.

The negative moments at the face of supports, 39 and 140 ft-Kips, are
taken from the table-2 , frame C
1217.5
Weight of beam stem  150  219 lb / ft
144
1
Maximum negative moment  1.40.21918.752  140
10
 11  140  151 ft  kips
b  12 in. d  24  2.5 assume one layer of steel   21.5 in.
Mu 15112,000
Rn    363 psi
bw d 2 0.901221.52

1  2 mRn 
 fy 40,000
 1 1 m    15 .686
m  fy 
 0.85 f c 0.853000 

1  215 .686 363  


  1 1   0.0098
15 .686  40,000 
The University of Lahore,
Civil Engineering Department 194
Islamabad Campus
(b) Size of short beam B5.
from figure which is well below 0.75b =0.027. Perhaps the beam
size should be reduced. From Fig.8

total factored load on B5= 6.36(10) = 63.6 Kips


18.75 1 140  39
max Vu  1.151.4 0.219   63.6  
2 2 18.75
 3.3  31.8  5.4  40.5 kips
Vu 40,500
vn    185 psi  3.4 fc OK
b w d 0.8512 21.5 

Size of beams in both the long and short directions should


probably be reduced; the nominal stress vn is well below 6 fc at
the face of support and is even lower at d therefrom.
The University of Lahore,
Civil Engineering Department 195
Islamabad Campus
ASSIGNMENT # 2
Analysis results of the slab shown below using DDM are presented next. The
slab supports a live load of 60 psf. Superimposed dead load is equal to 40 psf.
All columns are 12″ square. Take fc′ = 3 ksi and fy = 40 ksi.

The University of Lahore,


Civil Engineering Department 196
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 197
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 198
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 199
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 200
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 201
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 202
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 203
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 204
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 205
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 206
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 207
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 208
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 209
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 210
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 211
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 212
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 213
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 214
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 215
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 216
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 217
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 218
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 219
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 220
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 221
Islamabad Campus
SAMPLE SOLVED EXAMPLE

The University of Lahore,


Civil Engineering Department 222
Islamabad Campus

You might also like