Professional Documents
Culture Documents
Accuracy of Inductive Voltage Transformer in The Presence of Voltage High Harmonics
Accuracy of Inductive Voltage Transformer in The Presence of Voltage High Harmonics
Abstract: In the paper the issue of determining the voltage mainly defined by the voltage drop on the impedance of the
transformer’s (VT) accuracy when operating with distorted primary winding (the impedance of the secondary winding in
signals is presented. In the measuring system specially designed
high impedance differential amplifier and wide frequency voltage most conditions in negligible) and the magnetic properties of
divider were used. This enabled the possibility for utilization of its magnetic core. VT metrological properties for higher
the determined values of the composite error for evaluation of the frequencies are also dependent on equivalent capacities
accuracy of VTs in condition of transformation of sinusoidal between VT’s terminals resulting from both windings and
signals as well as distorted voltages. Comparison of determined insulation systems [8-9].
values of composite errors for transformation of sinusoidal and
distorted voltages allows to designate the additional
transformation errors of tested VTs in the presence of voltage II. THE MEASURING SYSTEM
high harmonics. Obtained results of measurements indicate that The rated voltages of both tested VTs primary windings are
for transformation of distorted voltages tested VTs are
characterized by lower transformation accuracy than for power 2000 V rms, while secondary windings are 100 V rms. Both
network frequency sinusoidal signal for which they were designed. VTs are 0,5 accuracy class [10]. Rated apparent power of the
Moreover, the results of measurements shown the increase of the VT type UDZ 24 is 100 VA and model VT is 25 VA for each
measured values of the composite error with the increase of the of two secondary windings. Only one secondary winding
transformed voltage distortion. during the tests was loaded. Magnetic cores of tested VTs are
manufactured from cold-rolled steal sheets type ET4. Used
I. INTRODUCTION
measuring system is presented in Fig. 1.
In condition of distorted voltage transformation voltage
transformers (VTs) are characterized by lower transformation
accuracy than for power network frequency sinusoidal signals
for which they were designed [1-4]. In accordance with the
IEEE C57.13 standard the transformation accuracy of the VT
may be determined by the transformer correction factor (TCF)
[5]. In the IEC standards equivalent parameter for determining
the accuracy, the composite error, is defined but only for
current transformers [6]. In accordance with the definition
presented in this standard under steady-state conditions,
composite error is the rms value of the difference between the
instantaneous values of the primary current and the Figure 1. Measuring system: SVT - Supplying Voltage
instantaneous values of the actual secondary current multiplied Transformer; VTUT - Voltage Transformer Under Test;
by the rated CT current ratio. The composite error for PACPS - Programmable AC Power Source; HIDA – High
sinusoidal current is equal vector sum of the current error and impedance differential amplifier; WFVD - Wide Frequency
the phase displacement. The level of primary voltage distortion Voltage Divider, DPM - Digital Power Meter, P1, P2 – input
in accordance with the limits given in standard [7] should not terminals of the VT's; S1, S2 – outputs terminals of the VT's;
exceed 8%. Then used distorted signal contains only 3rd and in1, in2 – inputs of the DPM.
5th harmonics and no significant increase of the measured
composite error was detected. In order to enable further Programmable AC power supply with supplying VT was
analysis primary voltages with higher total harmonic distortion used to provide 1600 V, 2000 V and 2400 V (80%, 100% and
(THDU) levels equal 20%, 30% and 43% were used. 120% of rated primary voltage) to tested VTs. To avoid the
The main parts of the voltage transformer are its magnetic increase of the reactive component of the load for higher
core, winding system and insulation. The parameters of the frequency components of distorted primary voltage secondary
magnetic core are specified by the magnetization windings of tested VTs were loaded with resistors (power
characteristics and active power losses. The accuracy of VT is factor 1). It was verified with a comparative analysis of voltage
errors and phase displacements for transformation of sinusoidal Not without the significance is the influence of the supplying
voltage of frequency 50 Hz that both VTs were able to operate VT on the shape of the test signal. Therefore, THDU levels of
with accuracy class 0.5 for active load power equal 25% and the Programmable AC power supply are set to ensure proper
100% of rated apparent power. During the tests composite for tests THDU levels of the primary voltage. Distortion of the
error is measured as a rms value of the difference between the voltage during the tests is measured by the digital power meter
instantaneous values of the secondary voltage of tested VT and through the reference wide frequency voltage divider.
the output voltage of the reference wide frequency voltage
divider for 80%, 100% and 120% of rated primary voltage and III. THE ACCURACY OF TESTED VTS FOR TRANSFORMATION OF
25% and 100% of rated active power of the secondary winding. THE 50 HZ SINUSOIDAL VOLTAGES
The output voltage of the 1/20 wide frequency voltage divider In order to assess the correctness of measurements the
was used as a reference voltage. The change of the voltage results of calculation of the composite error on the basis of the
ratio and the increase of the output voltage phase shift of the measurements of the voltage error and phase displacement for
divider with the increase of the sinusoidal input voltage sinusoidal voltages of frequency 50 Hz were used. The
frequency are negligible in frequency range from 50 Hz to composite error of a current transformer is the rms value of the
1.25 kHz (25h). Tested transformer’s output and voltage difference between the instantaneous values of the primary
divider’s output, were compared using a precise, high current and the instantaneous values of the actual secondary
impedance, differential amplifier and milivolt meter. The current multiplied by the rated transformation ratio [6]. This
device provided 900 MΩ isolation between the inputs and was formula for VT is described by equation (1) [11].
able to ensure the measurement accuracy of the difference
between two sinusoidal signals with precision not worst than T
1% in the frequencies range from 50 Hz to 20 kHz. 100 1
Simultaneously, the entire measuring system was monitored by
c
U1 T 0 ( Ku2 u1 )2 dt (1)
a digital power meter equipped with two probes, one connected
to the output of the voltage divider, the other to the output of
where: K- rated voltage ratio; u1,u2- instantaneous primary and
the VTUT. During the laboratory studies tested VTs are
secondary voltage; U1- primary voltage rms value, T- period
supplied with the sinusoidal and distorted primary voltages.
For sinusoidal signals on the basis of the voltage error and
The level of distortion is selected in order to required value of
phase displacement it is possible to calculate the values of the
the THDU factor: 8%, 20%, 30% or 43%. Primary voltage
composite error, when substituting following equations:
harmonics spectrum analysis for THDU levels equal a) 8% and
b) 43% are presented in Fig. 2.
u1 U1 2 sin t (2)
U
u2 U 2 (1 ) 2 sin(t ) (3)
100
U, - voltage error and phase displacement of the VT.
In table I VT type UDZ 24 current error and phase
displacement measured by the bridge circuit for testing the
accuracy of instrument transformers and calculated composite
error for transformation of sinusoidal primary current of
frequency 50 Hz are presented.
TABLE I
VT TYPE UDZ24 VOLTAGE ERROR, PHASE DISPLACEMENT AND
COMPOSITE ERROR FOR TRANSFORMATION OF
THE SINUSOIDAL PRIMARY VOLTAGE OF FREQUENCY 50 HZ
V. CONCLUSION
The usage of the high impedance differential amplifier and
wide frequency voltage divider enable measurements of the
composite error and estimation of the influence of the voltage
distortion on the accuracy of the inductive voltage transformers.
Obtained results of measurements indicate that the primary
voltage distortion caused deterioration of the accuracy of
transformation in case of both tested inductive VTs. This is
caused by the increased reactance of the primary winding for
higher frequency components of the distorted voltage and
decrease of the VT magnetic core permeability as resulting
from its magnetization characteristic for higher magnetic flux
density. Therefore, the accuracy of inductive VTs decreases
with the increase of the distortion level of the primary voltage.
Moreover, the increase of the secondary winding load and/or
primary voltage rms value causes further deterioration of the
inductive VT accuracy.
REFERENCES
[1] M. Kaczmarek, "An attempt to determine the accuracy of transformation of
sinusoidal signals of frequencies 50 Hz and higher through voltage transformers"
(printed in polish), Prz. Elektrotech., vol. 11b, pp. 233-236, 2012.