PRIME CONSULTANT:
GENERAL NOTES AND SYMBOLS (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

FIRE ALARM SYMBOLS DRAWING REFERENCE KEY FIRE ALARM SYSTEM GENERAL NOTES
A. MODIFY AND EXTEND THE EXISTING GAMEWELL-FCI SERIES E3 VOICE COMMUNICATION FIRE ALARM SYSTEM INTO THE RENOVATION AND EXPANSION AREAS OF THE TERMINAL IN
FACP GAMEWELL-FCI SERIES E3 VOICE EVACUATION FIRE ALARM PANEL (EXISTING TO REMAIN)
ACCORDANCE WITH 2015 IBC WITH NEW YORK STATE UNIFORM CODE SUPPLEMENT, 2015 IFC WITH NEW YORK STATE SUPPLEMENT, 2013 NFPA 72, AND SPECIFICATION 284621.11.
REFER TO JE ARCHITECTS/ENGINEERS, P.C.
ANN LCD FIRE ALARM ANNUNCIATOR PANEL (EXISTING TO REMAIN) DRAWING/DETAIL NUMBER B. INSTALL WALL-MOUNTED NOTIFICATION APPLIANCES WITH THE BOTTOM OF THE STROBE LENS AT 80" AFF, OR 6" BELOW THE CEILING, WHICHEVER IS LOWER. THE TOP OF ANY NEW 2 PENN PLAZA, SUITE 0603
FCPS FIRE ALARM REMOTE NOTIFICATION POWER SUPPLY PANEL RE:2/F-4.0 2 PANELS SHALL NOT BE INSTALLED HIGHER THAN 60 INCHES ABOVE FINISHED FLOOR LEVEL. NEW YORK, NEW YORK 10121
C. RUN ALL NEW WIRING IN MINIMUM 3/4" CONDUIT.
FCC FIREFIGHTER'S VOICE COMMAND CENTER (EXISTING TO REMAIN)
G D. MOUNT THE OPERABLE PART OF MANUAL PULL STATIONS AT 48" AFF.
G
SHEET NUMBER ON WHICH
P MANUAL FIRE ALARM PULL STATION
DETAIL IS DRAWN SUB CONSULTANT:
E. PROVIDE POWER LIMITED CIRCUITS.
RPS REMOTE POWER SUPPLY

RTS F. DO NOT LOCATE DETECTORS IN DIRECT AIR OR CLOSER THAN 3 FEET FROM AN AIR SUPPLY DIFFUSER.
REMOTE TEST STATION WITH STATUS AND ALARM INDICATOR
G. PROVIDE CONNECTIONS TO THE LIGHT AND POWER SERVICE IN ACCORDANCE WITH 2013 NFPA 72.
PHOTOELECTRIC SMOKE DETECTOR
H. CONTRACTOR TO MATCH EXISTING SYSTEM WIRE SIZE OF INITIATING DEVICE AND SIGNALING LINE CIRUITS.
ADDRESSABLE HEAT DETECTOR, COMBINATION TYPE JACOBS ENGINEERING NEW YORK INC.
I. CONTRACTOR TO MATCH EXISTING SYSTEM WIRE SIZE OF NOTIFICATION APPLIANCE CIRCUITS. 2 PENN PLAZA, SUITE 0603
INFRARED FLAME DETECTOR NEW YORK NEW YORK 10121
J. THE FIVE EXISTING FIRE ALARM ZONES SHALL BE RETAINED IN EXISTING BUILDING AREAS AS FOLLOWS: LOWER WEST CONCOURSE, LOWER EAST CONCOURSE, UPPER TERMINAL
WEST, UPPER TERMINAL EAST, CENTER BAGGAGE AND TICKETING. NEW ALARM ZONES SHALL BE CREATED FOR EXPANSION AREAS AS REQUIRED. CONTRACTOR TO COORDINATE
FIRE ALARM WALL MOUNTED STROBE WITH CLEAR LENS AND WHITE FACEPLATE MARKED "FIRE" (NUMBER INDICATES WITH NFTA.
XX MINIMUM CANDELA)
K. CONTRACTOR SHALL INSTALL ADDITIONAL AMPLIFIERS AS NECESSARY TO SUPPORT LOAD FOR ADDITIONAL SPEAKERS ADDED FOR THIS PROJECT.
FIRE ALARM WALL MOUNTED SPEAKER/STROBE WITH CLEAR LENS AND WHITE FACEPLATE MARKED "FIRE" (NUMBER
INDICATES MINIMUM CANDELA) L. REMOTE TEST SWITCH WITH STATUS/ALARM INDICATORS SHALL BE PROVIDED FOR DUCT SMOKE DETECTORS AND FOR SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES.
XX
FIRE ALARM WALL MOUNTED SPEAKER WITH WHITE FACEPLATE MARKED "FIRE" M. PROVIDE AREA SMOKE DETECTION THROUGHOUT NEW AND RENOVATED AREAS COMMENSURATE WITH THE EXISTING DETECTION SYSTEM IN PUBLIC/CIRCULATION AREAS, STORAGE, AND
UTLITY SPACES WITH DETECTOR SPACING PER NFPA 72.
FIRE ALARM CEILING MOUNTED STROBE WITH CLEAR LENS AND WHITE FACEPLATE MARKED "FIRE" (NUMBER INDICATES
MINIMUM CANDELA) N. CONTRACTOR TO MATCH EXISTING SYSTEM CIRCUIT CLASSIFICATION TO PROVIDE FIRE ALARM SIGNALING LINE CIRCUITS, INITIATING DEVICE CIRCUITS, AND NOTIFICATION APPLIANCE
XX
CIRCUITS COMMENSURATE WITH THE EXISTING BUILDING FIRE ALARM SYSTEM. PROVIDE AUDIBLE-ONLY NOTIFICATION IN SINGLE-PERSON OFFICES.
F FIRE ALARM CEILING MOUNTED SPEAKER/STROBE WITH CLEAR LENS AND WHITE FACEPLATE MARKED "FIRE" (NUMBER F
INDICATES MINIMUM CANDELA) O. PROVIDE ADDRESSABLE CONTROL MODULES TO INITIATE SHUTDOWN OF BAGGAGE AREA CONVEYOR SYSTEM UPON ACTIVATION OF THE BAGGAGE AREA SPRINKLER WATER FLOW SWITCH.
XX PROVIDE RELAYS FOR ACTIVATION OF EXHAUST FANS FOR SMOKE REMOVAL WHERE INSTALLED.
FIRE ALARM CEILING MOUNTED SPEAKER WITH WHITE FACEPLATE MARKED "FIRE"
P. PROVIDE ADDRESSABLE DUCT SMOKE DETECTORS ON THE RETURN SIDE OF AIR HANDLING UNITS OVER 2,000 CFM PER 2015 IMC. IT IS A VIOLATION OF LAW FOR ANY PERSON TO ALTER A DOCUMENT IN
E FIRE ALARM WALL MOUNTED ELECTRIC BELL ASSOCIATED WITH FIRE SPRINKLER RISER WATERFLOW SWITCH ANY WAY, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED
PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. IF THIS
Q. PROVIDE ADDRESSABLE DUCT SMOKE DETECTORS INSTALLED AT EACH STORY WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES AND SERVE ANY PORTION OF A RETURN AIR DOCUMENT BEARING THE SEAL OF AN ENGINEER/ARCHITECT IS
SYSTEM HAVING A DESIGN CAPACITY GREATER THAN 15,000 CFM PER 2015 IMC. LOCATE DUCT SMOKE DETECTORS UP STREAM OF THE CONNECTION BETWEEN THE RETURN AIR RISER AND ALTERED, THE ALTERING ENGINEER/ARCHITECT SHALL AFFIX TO THE
M ANY AIR DUCTS OR PLENUMS. DOCUMENT THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED
BY THEIR SIGNATURE AND THE DATE OF SUCH ALTERATION, AND A
SPECIFIC DESCRIPTION OF THE ALTERATION.
VANE TYPE OR PRESSURE-TYPE WATER FLOW SWITCH WITH ASSOCIATED MONITOR MODULE R. PROVIDE WATERFLOW ALARM SWITCHES AND SUPERVISORY AIR PRESSURE AND VALVE TAMPER MONITORING ON ALL NEW SPRINKLER CONTROL VALVES.
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY FOR
M THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.
S. THESE DOCUMENTS DEPICT A PERFORMANCE LEVEL ENGINEERING DESIGN LAYOUT TO BE UTILIZED AS GUIDANCE FOR THE PLANNING OF THE FIRE ALARM SYSTEM BY THE CONTRACTOR. RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO THIS
TAMPER SWITCH WITH ASSOCIATED MONITOR MODULE PROVIDE COMPLETE DOCUMENTS FOR REVIEW AND APPROVAL FROM THE ENGINEER OF RECORD, THE AUTHORITY HAVING JURISDICTION AND FM GLOBAL PRIOR TO INSTALLATION. INCLUDE PROJECT IS DISCLAIMED.
IN THE SHOP DRAWINGS AND CALCULATIONS ANY ADDITIONAL EQUIPMENT NECESSARY, INCLUDING INITIATING DEVICES AND NOTIFICATION APPLIANCES, TO PROVIDE A COMPLETE
M INSTALLATION AND COMPLY WITH OWNER STANDARDS.
HIGH/LOW AIR PRESSURE SUPERVISORY SWITCH WITH ASSOCIATED MONITOR MODULE
H/L
T. DEMOLISH ALL EXISTING FIRE ALARM INITIATING DEVICES, NOTIFICATION APPLIANCES, AND WIRING IN RENOVATION AREAS PRIOR TO INSTALLATION OF NEW WIRING AND NEW DEVICES
SHOWN ON PLANS.

R RETURN DUCT SMOKE DETECTOR (SUPPLIED BY FIRE ALARM CONTRACTOR; INSTALLED BY MECHANICAL CONTRACTOR)

R ADDRESSABLE CONTROL RELAY EXISTING FIRE ALARM SYSTEM TIE-IN SCHEDULE


E M ADDRESSABLE MONITOR MODULE E
FIRE ALARM TIE-IN SCHEDULE
C ADDRESSABLE CONTROL MODULE
TIE-IN POINT TIE-IN SERVICE AND MATERIAL TIE-IN LOCATION DRAWING
WP INDICATES WEATHER PROOF BACKBOX AND DEVICE RPS-1 RACEWAY / ALUMINUM MECH/ELEC 1N14 FA110
WG WIREGUARD OR LEXAN PROTECTIVE COVER
RPS-2 RACEWAY / ALUMINUM ELEC 1O03 FA111
RPS-3 RACEWAY / ALUMINUM 1Q36 FA112
CONNECT NEW TO EXISTING

UVIR MULTI-SPECTRUM FLAME DETECTOR

D D

Niagara Frontier
Transportation Authority
Serving the Niagara Region

BNIA - BAGGAGE CLAIM


EXPANSION
C C

B B

0 05/21/18 ISSUED FORBIDS


ISSUE FOR BIDS

MARK DATE DESCRIPTION


NFTA PROJECT NO: 10BT1516
DESIGNER PROJECT NO: F8Z94900
FILE NAME: F8Z94900_BUF_FIRE_A360.rvt
DRAWN BY: K. WEBB
CHECKED BY: R. PARK
COPYRIGHT:

SHEET TITLE:
FIRE ALARM GENERAL
A
NOTES AND SYMBOLS A

DRAWING#

FA001
5/10/2018 3:24:07 PM

SHEET# 536 OF 725