UPS Clearances: Size Unit A3 MM Scale NTS

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

0 1 2 3 4 5 6 7 8 9

UPS Clearances

Lifting Eyes
B Option

A Back clearance 100 mm


B Front clearance needed to allow correct door opening 850 mm
C Maximum door opening angle 120°
D Top clearance 300 mm

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-08 GA_ABB_PWL_DPA_60-80_R_BCE Power Protection SA General Information drawing number
User JTrottmann Via Luserte Sud 9 UPS Clearance 4NWD003333
date 2016-09-08 CH-6572 Quartino page 1
Switzerland 2
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

Footprint
A Lifting Eyes
Option

B B

SECTION B-B
FEET POSITION
1783

31 532 63 532 63 532 31


31

100
E
732

593
793

100
31

100 393 202 393 202 393 100


Ø 12.5
F
NUMBER OF FEET = 12
SINGLE FOOT AREA = 10000 mm2
Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-09 GA_ABB_PWL_DPA_60-80_R_BCE Power Protection SA General Information drawing number
User JTrottmann Via Luserte Sud 9 Footprint 4NWD003333
date 2016-09-09 CH-6572 Quartino page 2
Switzerland 1 3
Proved Mbirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

Views and Dimensions

FRONT VIEW

RIGHT VIEW UPS A INCOMING UPS B LEFT VIEW BACK VIEW


Lifting Eyes
BYPASS
Option

2200
D
100

800 600

E 838 1800

Color RAL7035
Deg.of protection IP31
UPS cable entry Bottom
Weight Refer to TDS
Overall dimensions 2200x1800x800mm HxWxD

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-09 GA_ABB_PWL_DPA_60-80_R_BCE ABB Schweiz AG General Arrangement drawing number
User JTrottmann Power Protection SA Views and Dimensions 4NWD003333
date 2016-09-09 Brown Boveri Platz 3 page 3
CH-5400 Baden 2 4
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

A Top View
Lifting Eyes
Option

TOP VIEW

120° 120° 120°

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-09 GA_ABB_PWL_DPA_60-80_R_BCE ABB Schweiz AG General Arrangement drawing number
User JTrottmann Power Protection SA Top View 4NWD003333
date 2016-09-09 Brown Boveri Platz 3 page 4
CH-5400 Baden 3 5
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

A Bottom Cable Entry


Lifting Eyes
Option

A A

D SECTION A-A
BOTTOM CABLE ENTRY

673

683
Legend:

E
80
55

Zone of Bottom

70
=
Cable Entry

109 150 90 150 205 390 205 150 90 150 109

1797

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-09 GA_ABB_PWL_DPA_60-80_R_BCE ABB Schweiz AG General Arrangement drawing number
User JTrottmann Power Protection SA Bottom Cable Entry 4NWD003333
date 2016-09-09 Brown Boveri Platz 3 page 5
CH-5400 Baden 4 6
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

Full Front View Doors Open


A
UPS A INCOMING UPS B +U1 Frame UPS A
Lifting Eyes BYPASS +U2 Frame INCOMING BYPASS
Option +U3 Frame UPS B
-A1 UPS module 1
-A2 UPS module 2
-Q40 Battery circuit breaker, 4P equipped with AUX contact
-Q60 Maintenance bypass switch, 3P equipped with AUX contact
+U1 +U2 +U3 -Q93 Output switch, 3P, equipped with AUX contact, UPS A
-Q95 Output switch, 3P, equipped with AUX contact, UPS B
-Q92 Input bypass switch, 3P, equipped with AUX contact, UPS A
-Q94 Input bypass switch, 3P, equipped with AUX contact, UPS B
B -Q1 Input circuit breaker, 3P, equipped with thermomagnetic trip and AUX contact, UPS A
-Q2 Input circuit breaker, 3P, equipped with thermomagnetic trip and AUX contact, BYPASS
-Q4 Input circuit breaker, 3P, equipped with thermomagnetic trip and AUX contact, UPS B
-A1 -A2 -A1 -A2
SLOT1 Network for Communication, (SNMP, Modbus) -A65
SLOT2 Network for Communication, (SNMP, Modbus) -A66
-A64 Customer Input/Output Dry Port
-A60 Customer Input/Output Dry Port
-Q93 -Q95

C
-Q60

-Q92 -Q94

-Q1 -Q2 -Q4

Battery Breaker -Q40 Battery Breaker -Q40


D
Communication Interface -A60 Communication Interface -A60
Communication Interface -A64 Communication Interface -A64
Slot for Network Slot for Network
Communication Communication

Frame Fans
Option

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-09 GA_ABB_PWL_DPA_60-80_R_BCE ABB Schweiz AG General Arrangement drawing number
User JTrottmann Power Protection SA Front View Doors Open 4NWD003333
date 2016-09-09 Brown Boveri Platz 3 page 6
CH-5400 Baden 5 7
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

Full Front View With Open Terminals


A UPS A INCOMING UPS B -X40 Battery terminal
Lifting Eyes BYPASS -X1 Rectifier input terminal
Option -X2 Bypass input terminal
-X3 System output terminal
-X4 Rectifier input terminal
-X5 Neutral terminal, UPS A
-X6 Earth-Bar (PE)
+U1 +U2 +U3 -X7 Neutral terminal, UPS B

-X1
D -X2 -X4

-X5 -X7

-X40 -X40
-X3

E -X6

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-12 GA_ABB_PWL_DPA_60-80_R_BCE ABB Schweiz AG General Arrangement drawing number
User JTrottmann Power Protection SA Front View (Terminals) 4NWD003333
date 2016-09-12 Brown Boveri Platz 3 page 7
CH-5400 Baden 6 8
Proved MBirrer No. pages 8
0 1 2 3 4 5 6 7 8 9

A BOTTOM VIEW

UPS Power Module

BACK VIEW RIGHT VIEW FRONT VIEW LEFT VIEW

Power
Plug

810.5
Power Module
Service Panel

D
200.5

TOP VIEW

757.5

707.5

743.5
E

Module Fans

Scale Size Unit

NTS A3 mm

ABB
change date name date 2016-09-12 GA_ABB_PWL_DPA_60-80_R_BCE Power Protection SA General Arrangement drawing number
User JTrottmann Via Luserte Sud 9 Module 4NWD003333
date 2016-09-12 CH-6572 Quartino page 8
Switzerland 7
Proved MBirrer No. pages 8