ONYX® FIRSTVISION Installation Instructions

Equipment to be Installed Recommended Installation Steps


• ONYX® FIRSTVISION Performing the following steps will accomplish mounting
• AMPS-24/E Power Supply the ONYX® FIRSTVISION and the power supply
components, and also the wiring connection between
• BB-100 Cabinet for the AMPS-24/E
them.
• Two 100 Amp-Hour Batteries
Step 1. Mounted the panel on an inside wall of a
building. Building construction and local building
Installation Standards and Codes codes dictate installation parameters. Panel
The ONYX® FIRSTVISION has been designed to comply dimension are shown on the reserve side of this
with standards set forth by the following regulatory document in Figure 1.1.
agencies: Step 2. Mount the AMPS 24/E and the batteries in a BB-
• Underwriters Laboratories Standard UL 864 100 Mounting as described in the AMPS-24/E
Manual.
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527-99 Standard for Control Units for NOTE:It is recommend that power be turned-on to the AMPS
Fire Alarm Systems 24/E and ONYX® Insight after the Ethernet (TCP/IP) Network
• ULC S524 Standard for the Installation of Fire Alarm and the NFN Gateway connections have been made.
Systems
The contents of this document are important and must be Step 3. Open and locate the terminal power strip inside
kept in close proximity to the hardware. If building the ONYX® FIRSTVISION cabinet as shown on
ownership is changed, this document and all other the reserve side of this document in Figure 1.2.
testing and maintenance information must also be Step 4. Wire the AMPS 24/E to the terminal strip on the
passed to the current owner of the facility. A copy of this ONYX® FIRSTVISION cabinet as shown on below.
document is shipped with the ONYX® FIRSTVISION and is
also available from the manufacturer. TB6 provides 1 amp, power-limited, when
the +5V output is not being used. Do not
use the +5V output at the same time.
WARNING:Improper installation, maintenance, or lack of
routine testing could result in system malfunction.

UL 9th Edition Compliance


This product has been certified to comply with the
requirements in the Standard for Control Units and AMPS 24/E
Accessories for Fire Alarm Systems, UL 864 9th Edition.
Operation of this product with products not tested for UL ONYX® FIRSTVISION
864 9th Edition has not been evaluated. Such operation
requires the approval of the local Authority Having
Cabinet
Jurisdiction (AHJ).

NOTE:The AMPS-24/E Power Supply has not received


UL 864 9th Edition certification. Step 5. Refer to ONYX® FIRSTVISION Operating and
Programming Manual (52442) for information
about connecting the ONYX® FIRSTVISION with
building systems.
Environmental Conditions
The ONYX® FIRSTVISION must be installed in the
following environmental conditions:
• Temperature range of 0ºC - 50ºC (32ºF - 120ºF).
• 10-95% humidity non-condensing at 30ºC (86ºF).
• Vibration of 10-50Hz, 0.5G Peak to Peak
• Shock 15G, 11ms maximum

Document 52441 Rev A ECN 04-559 06/06/2005


Figure 1.1 ONYX® FIRSTVISION Dimensions

Figure 1.2 Location of ONYX® FIRSTVISION Terminal Strip

The ONYX® Insight panel is


already internally wired from
the power port to a terminal
back of display strip.

terminal strip

splay
to di

to AMPS

Document 52441 Rev A ECN 04-559 06/06/2005