Design Weather Parameters & Mshgs
Design Weather Parameters & Mshgs
Design Parameters:
32
30
Temperature ( °C )
28
26
24
22
20
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour
Roof 1
Roof Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.150 W/(m²-°K)
Wall
Wall Details
Outside Surface Color Medium
Absorptivity 0.675
Overall U-Value 0.250 W/(m²-°K)
W1 11,26
Window Details:
Detailed Input No
Height 3.30 m
Width 5.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W2 14,18-19,23
Window Details:
Detailed Input No
Height 2.40 m
Width 3.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W3 12-13,15-17,20-22,24-25
Window Details:
Detailed Input No
Height 2.40 m
Width 2.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W4 6,9-10
Window Details:
Detailed Input No
Height 1.60 m
Width 2.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W5 4-5
Window Details:
Detailed Input No
Height 0.80 m
Width 3.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W6 1-3,7-8
Window Details:
Detailed Input No
Height 0.80 m
Width 2.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
W7 27
Window Details:
Detailed Input No
Height 0.80 m
Width 2.00 m
Overall U-Value 2.890 W/(m²-°K)
Overall Shade Coefficient 0.250
D1 1,2,40,41
Door Details:
Gross Area 16.5 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 16.5 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D2 3,33,44-49
Door Details:
Gross Area 4.4 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 4.4 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D3 13,17,20,26
Door Details:
Gross Area 5.0 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D4 18,19,21,22
Door Details:
Gross Area 4.4 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D5 11,12,14-16,
Door Details:
Gross Area 2.2 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D6 23-25,
Door Details:
Gross Area 4.4 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D7 4,5,29,34,35
Door Details:
Gross Area 2.1 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D8 6-10,28,30-32,36-39
Door Details:
Gross Area 1.8 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
D9 42,43
Door Details:
Gross Area 4.4 m²
Door U-Value 2.840 W/(m²-°K)
Glass Details:
Glass Area 0.0 m²
Glass U-Value 2.890 W/(m²-°K)
Glass Shade Coefficient 0.250
Glass Shaded All Day? No
Bed Room 24
1. General Details:
Floor Area 15.8 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 21.0 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.8 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 15.8 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 12.1 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined 1 person as per
OA Requirement 1 100 % of supply air
OA Requirement 2 0.3 L/s
report
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 17.7 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.1 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 12.1 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Corridors 04-10
1. General Details:
Floor Area 43.6 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule 1 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 10.4 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 43.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 43.6 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 31.2 m²
U-Value 0.250 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
Corridors 17-21
1. General Details:
Floor Area 43.6 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage GENERAL: Corridor
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule 1 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 10.4 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 43.6 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 43.6 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Elec room 26
1. General Details:
Floor Area 6.3 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.6 0 0 1
SE 10.4 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.3 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 6.3 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule 1 Latent 133.3 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 31.2 0 0 0
SE 31.2 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 37.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 37.4 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 10.70 W/m² Activity Level Heavy Work
Ballast Multiplier 1.00 Sensible 153.9 W/person
Schedule Schedule 1 Latent 271.1 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 124.8 2 0 2
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 295.0 0 0
5. Infiltration:
Design Cooling 5.00 ACH
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 295.0 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Meat,Fish,Veg. stores
1. General Details:
Floor Area 35.9 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 10.70 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule 1 Latent 133.3 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 52.0 3 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.9 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 35.9 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 760.0 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Restaurant dining room
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 500.0 People
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 156.0 5 0 3
SW 124.8 1 1 2
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 760.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 760.0 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area 760.0 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Restaurant dining room
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 500.0 People
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 156.0 5 0 3
NE 124.8 2 0 2
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 760.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 760.0 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Office 20
1. General Details:
Floor Area 8.9 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage OFFICE: Office space
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 13.0 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.9 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 8.9 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Servery 11
1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 10.70 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule 1 Latent 133.3 W/person
Schedule Schedule 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 36.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 36.0 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Servery 22
1. General Details:
Floor Area 36.0 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 3.8 L/s/person
OA Requirement 2 0.90 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 10.70 W/m² Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule 1 Latent 133.3 W/person
Schedule Schedule 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 36.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 36.0 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Store 19
1. General Details:
Floor Area 12.4 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.0 L/s
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 18.2 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.4 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 12.4 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Tele room 27
1. General Details:
Floor Area 6.1 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 0.0 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Seated at Rest
Ballast Multiplier 1.00 Sensible 67.4 W/person
Schedule Schedule 1 Latent 35.2 W/person
Schedule Schedule 1
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.6 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.1 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 6.1 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Toilets 03
1. General Details:
Floor Area 40.5 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule 1 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 31.2 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 40.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 40.5 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 31.2 m²
U-Value 0.250 W/(m²-°K)
Uncondit. Space Max Temp 23.9 °C
Ambient at Space Max Temp 35.0 °C
Uncondit. Space Min Temp 23.9 °C
Ambient at Space Min Temp 12.8 °C
Toilets 16&23
1. General Details:
Floor Area 49.8 m²
Avg. Ceiling Height 5.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 100 % of supply air
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 10.70 W/m² Activity Level Office Work
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule 1 Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 31.2 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 40.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Slab Floor On Grade
Floor Area 40.5 m²
Total Floor U-Value 0.397 W/(m²-°K)
Exposed Perimeter 0.0 m
Edge Insulation R-Value 0.00 (m²-°K)/W
7. Partitions:
(No partition data).
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Please check
ventilation flow. It
looks very high.
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0.024
4. Central Heating Coil Outlet
5. Supply Fan Outlet
6. Room Air
1
0.022
0.020
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0.024
4. Central Heating Coil Outlet
5. Supply Fan Outlet
6. Room Air 0.022
1
0.020
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 0.024
4. Supply Fan Outlet
5. Room Air
1
0.022
2
0.020
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.2 W/(L/s)
Site Altitude = 24.0 m
1. Outdoor Air
2. Central Cooling Coil Outlet
3. Supply Fan Outlet 0.024
4. Room Air
0.022
1
0.020