Professional Documents
Culture Documents
DEH Control
DEH Control
002SM(B)-7 PAGE 1 OF 48
overcomes the restriction force of spring and throws the centrifugal stop bolt
outward striking pilot valve trigger which make pilot valve move towards right
and then protection oil is connected with drain to open diaphragm valve rapidly.
Pilot valve of emergency governor that is installed inside front bearing housing is
the control and test device in emergency trip system, and it includes one trip pilot
valve, one test isolation pilot valve, one manual trip lever and one test lever.
Test isolation pilot valve could be used to isolate pilot valve of emergency
governor from LP protection oil header. During oil injection test, test stop valve
could be opened by manual to allow pressure oil coming into the chamber beneath
centrifugal stop bolt through nozzle, and centrifugal stop bolt overcomes the
restriction force of spring flying off.
1.5.4.2 Safety operation device
Safety operation device provides remote reset solenoid valve and reset air cylinder
for unit. When it receives DEH reset signal and air cylinder moves upwards
pushing connecting rod of emergency governor pilot valve, pilot valve of
emergency governor resets.
2 EH system set value
No. Description Set value Remarks
1 EH system pressure 14 MPa
2 EH fluid power unit overflow valve 16.8 MPa
opening pressure
3 HP accumulator nitrogen charging 9.4-9.8MPa
pressure
4 Fire resistant fluid in EH fluid
37-60C
reservoir allowable temperature
5 EH fluid reservoir level switch set Level switch
value acts when
Low EH fluid level alarm 450mm fluid level of
Low low EH fluid level pre-trip 370mm EH fluid
(stop heater) reservoir
Low low EH fluid level trip (stop 230mm reaches to
main oil pump) set value
Low low EH fluid level trip (stop 230mm
main oil pump)
6 Pressure transducer XD/EHP Output current is 4-20mA at
0-21MPa fluid pressure
7 63/HP (high EH fluid pressure 16.2Mpa
alarm)
8 63/MP (start standby oil pump) 11.2Mpa
9 63/LP (low EH fluid pressure alarm) 11.2MPa
10 63-1/LP (low EH fluid pressure trip) 9.8MPa
11 63-2/LP (low EH fluid pressure trip) 9.8Mpa
12 63-3/LP (low EH fluid pressure trip) 9.8Mpa
75D.002SM(B)-7 PAGE 5 OF 48
water pressure shall be between 0.2MPa and 0.5MPa. Water quality shall be
qualified so that scaliness will not happen inside cooler. Cooling water tubing
shall be of F33´4(DN25), the material of which shall be stainless steel.
3.3.1.3 Accumulator assembly installation
Two sets of accumulator assemblies shall be respectively installed on steam
turbine sides on operating floor and their location shall be determined according to
EH oil piping and accessories as well as site situation. HP accumulator location
shall be close to combined main stop/governing valve as much as possible.
3.3.1.4 Diaphragm valve installation
Diaphragm valve shall be fastened by a support and chuck ring and installed at
front bearing housing side. Oil inlet of diaphragm valve upper chamber connects
to mechanic overspeed-manual trip header. Oil inlet and outlet on valve body shall
be respectively connected to AST header and DV header, and the orientation of
inlet/outlet shall be identical with the arrow marked on valve body. AST fluid shall
be connected to inlet of diaphragm valve, while DV fluid shall be connected to
outlet of diaphragm valve.
3.3.1.5 OPC/AST solenoid valve unit installation
OPC/AST solenoid valve unit shall be located nearby front bearing housing. Its
tubing connection refers to 75D.002Q(B)-7 and 75D.328Z(B)-7 and shall be
checked carefully.
3.4 Connection of subassemblies
3.4.1 Cleaning of tubing, tee, elbow and union connection
All stainless steel tubing shall be flushed by steam that is of high temperature
(300°C) and low pressure (1.0Mpa). Steam may come from small boiler. Put outlet
of steam piping into the tubing to be flushed and turn open steam valve to flush
the tubing for one minute. After cooling tubing, tubing inner wall shall be cleaned
by using iron thread packed white cloth until there is no dirty spot on white cloth.
After that, two ends of tubing shall be blocked to prevent dust. Finally, the inner
surface of parts shall be wiped by using white cloth until there is no dirty spot on
the white cloth, and then the parts shall be put into clean plastic bag for standby.
3.4.2 EH oil piping installation
3.4.2.1 Notice of EH oil piping installation
a) Cleanness shall be regarded in EH oil piping installation, which means the
outlet of piping shall be blocked by using sleeve or plastic bag and white cloth
to prevent dust.
b) All connections of EH oil piping shall adopt argon arc welding, and welded
connection quality shall be ensured.
c) Piping wall shall not be damaged during piping bending to avoid crack of
piping wall weak section caused by stress concentration during operation.
d) Cut piping shall be chamfered and deburred to prevent scrap iron and burr
entering piping.
e) The screw cap of union connection must be screwed tightly; otherwise,
75D.002SM(B)-7 PAGE 9 OF 48
F(mm)
Min. bent 80 90 60 50 30 20
radius
R(mm)
Table 1 Min. bent radius of stainless steel seamless pipe
3.4.2.2 Piping installation on zero-meter flat
Refer to 75D.002SM(B)-7 and 75D.328Z(B)-7. The piping connected with EH
fluid reservoir includes return fluid (DP1, DP2), no pressure return fluid (DV1,
DV2), high-pressure fluid (HP), which shall be marked on nameplates at EH fluid
reservoir outlets.
3.4.2.3 Cleaning the tubing on zero-meter flat
The tubing shall be marked and then disassembled and to be flushed with 1.0MPa
pressure, 300°C temperature steam for one minute on zero-meter flat. Steam may
come from small boiler. After being flushed, tubing inlet/outlet shall be blocked or
covered by special plug or plastic bag and iron thread packed white cloth to
prevent dust entrance.
3.4.2.4 Reinstallation of the tubing on zero-meter flat
All tubing shall be reinstalled according to the drawing and the mark after
75D.002SM(B)-7 PAGE 10 OF 48
cleaning. The sealing parts like O-ring, gasket shall be located at position, the
connectors for cleaning but not welded shall be welded and expansion support
shall be fastened.
3.4.2.5 Installation of the tubing on operation floor
Installation of the tubing and expansion support on operation floor shall start from
two RSV actuators and four GV actuators.
Because the actuator will move for the heat expansion of steam section, the
displacement will happen between tubing terminal and tubing support or between
tubing terminals.
All stainless steel tubes adopt argon arc welding. After being cut, the tube ends
shall be cleaned without burr. Tubes could be connected with each other; however,
tube ends shall be chamfered. As indicated in following figure:
Attention: ball valve will be at open position when ball valve handle and valve
body centerline is at superposition; however, ball valve will be at closed position
when ball valve handle is perpendicular to valve body centerline.
l) Please confirm the pumps condition according to the following table:
No. Description Correct condition
75D.002SM(B)-7 PAGE 13 OF 48
c) Change for another jerrican and repeat the mentioned clauses above until EH
fluid reservoir level reaching to high fluid level mark.
d) Pay attention to oil level during filling, and request thermal technology
personnel to set oil level alarm switch at site (the set point shall be in
accordance to EH fluid reservoir bottom). Level switch has four alarm points,
which shall be firstly tested by using ohm scale of multimeter.
e) Refer to control cabinet ER wiring diagram for contact points’ condition (NO
or NC) of two level switchs before oil filling.
Low EH oil level alarm 450mm (drop)
Low-low EH oil level trip alarm 370mm (drop)
Low-low EH oil level trip (stop MOP) 230mm (drop)
Low-low EH oil level trip (stop MOP) 230mm (drop)
f) When oil level is rised, each pair of contact points open/close condition shall
be recorded according to the above specification. Two pairs of contact points’
activity sequence shall be regarded and monitored together. Stop filling,
measure oil level and record oil level height once the contact point acts.
g) When finishing setting lower oil level, the circulating pump could be started
until oil level of EH fluid reservoir reaches to high oil level. During oil filling,
oil level alarm device acting oil level shall be continuously checked and
recorded.
h) For ensuring higher oil level after start, EH fluid reservoir shall be filled to the
highest oil level mark that is 100mm between oil surface and reservoir top (oil
level will be dropped a little bit when system pressure has been established
and accumulator has been filled with oil. When oil level is higher than low oil
level alarm level, EH fluid reservoir shall not be filled with oil).
i) When the temperature is lower than 20°C, heater and circulating pump shall be
pump shall be started also to make whole fluid reservoir being uniformly
heated and to avoid part carbonization. It’s better to start MOP when fluid
reservoir temperature is around 40-50℃, so that the temperature will not be
too low during system oil circulation.
4.4 EH system oil circulation
EH main oil pump could be either local controlled or remote controlled in main
control room, which shall be communicated with each other well.
4.4.1After start button of one MOP being pushed, the oil pump will make scream
and metal bumping noise within seconds (when oil temperature is lower than
20°C), and then oil pump could operate smoothly. The pressure gauge at pump
outlet shall be monitored. The oil pressure may be very low (lower than 0.5MPa)
because of system large return flow, when it shall be checked whether oil leakage
of whole system happens. If leakage happens, the pump shall be stopped
immediately to solve the problem.
4.4.2 If the system is normal, pressure compensator of EH main oil pump shall be
tightened to make pressure rise until it will not rise any more. At this moment, unit
pressure value will not exceed 1.5MPa. It shall be checked again whether system
oil leakage happens; if it happens, the pump shall be stopped to solve the problem,
otherwise the unit shall operate continuously.
4.4.3 If the system is normal, the other EH main oil pump shall also be started and
then system pressure will rise a little bit. The pressure compensators of EH main
oil pump shall be tightened to make pressure rise until it will not rise any more;
however, outlet pressure shall not higher than 3.5Mpa. It shall be paid attention to
that spin length of screw rods of two main oil pumps’ pressure compensators shall
be the same, so that the outlet pressure of two EH main oil pumps could be the
same.
4.4.4 For system piping being flushed, both oil temperature and oil level will drop.
If the pump operates normally, it’s unnecessary to stop the pump; if the oil
temperature is over 20°C, the pump could operate continuously.
4.4.5 Oil thermometer on EH fluid reservoir shall be monitored to check whether
oil temperature rise and heater works normally. Once oil temperature exceeds
50°C, the heater shall be stopped to avoid oil becoming bad.
4.4.6 Meanwhile, it shall be monitored that whether strainer differential pressure
is normal. For big flow flush, large differential pressure alarm may happen, which
is normal phenomenon. However, the differential pressure shall be stable. If the
differential pressure continuously rises, the stainer shall be changed to go on
operating.
4.4.7 Self-circulation system shall also take part in fluid reservoir purifying, and it
shall be monitored whether the filter differential pressure at circulating pump
75D.002SM(B)-7 PAGE 16 OF 48
outlet is stable. The self-circulation loop shall be put into operation until the oil
quality is qualified.
4.4.8 If power plant has purchased standby oil purifier, it should also be put into
operation to shorten the time of oil circulation flush.
4.4.9 Differential pressure stability of filters shall be checked frequently during
system being flushed. System leakage and vibration of oil piping and piping clamp
shall be checked, which shall be adjusted when it’s necessary. It shall be checked
whether partial obstruction happens to the piping; if so, the spring and valve core
of check valve or dump valve of actuator shall be disassembled.
4.4.10 Flushing system until differential pressure of all filters is stable, and inlet
isolation valve of all HP accumulators shall be opened slowly. After system being
flushed for over one hour or few days, isolation valve of HP accumulator shall be
closed (attention: for preventing bladder rupture caused by being draped, before
being flushed the accumulator must be pre-charged with nitrogen, the pressure of
which is normally between 1.0~4.5Mpa).
4.4.11The compressed air in upper chamber of diaphragm valve shall be shut off,
and the air tube shall be separated from diaphragm valve. The tubing under
diaphragm valve shall be flushed for over 10 hours or few days.
4.4.12First samping could be executed after continuous flushing for 7 days with
stable differential pressure, and the cleanness of samping port and sample
container shall be regarded during sampling.
4.4.13 Generally, it takes 15-30 days to flush oil piping to be clean. If the
cleanness of piping is very bad, it may take longer time that shall not be less than
10 days.
4.4.14 Oil flushing shall go on before test result comes out.
4.4.15After the test result is qualified, two main oil pumps shall be stopped and
the reinstallation work could be started.
4.5 Oil sample test
4.5.1 Sampling method: during oil flushing with single pump operation, the
sampling shall be performed at sampling port. Before sampling, sampling port
shall be cleaned and the stop valve shall be opened to release around 500ml oil
(reusable), and then sampling bottle shall be put at sampling port to accept around
100ml oil and finally the stop valve shall be closed.
4.5.2 Sampling shall be executed before starting work in the morning, when the
impurity in the air is quite few.
4.5.3 Sampling bottle that could not be replaced by common bottle must be
specially supplied by oil sample testing department.
4.5.4 Qualification standard of oil sample test: the granularity and acid value of
0.1L oil taken from sampling bottle shall be tested. Two cleanness standards of oil
sample test: higher than grade 5 for NAS standard, higher than grade 2 for SAE
standard.
Granularity index: 5-10 micron grain/100ml 9700
10-25 micron grain/100ml 2680
25-50 micron grain/100ml 380
75D.002SM(B)-7 PAGE 17 OF 48
8) The stop valve shall be closed when the pressure inside HP accumulator
reaches to 9.4-9.8 MPa. The pressure inside accumulator shall be maintained
stable for one minute and then measured, which shall be charged again until
the pressure is stabilized at set value if the pressure is lower than set value.
9) Check whether outlet stop valve of nitrogen container is shut tightly and open
discharge valve of charging tool.
10) The connectors shall be disassembled separately from nitrogen container and
accumulator, and the accumulator shall be covered with air inlet cover.
11) When the next accumulator is being charged, it shall be first charged by using
nitrogen container of lower pressure to save gas.
12) The nitrogen pressure inside accumulator shall be measured each week or
according to actual situation. The set value of 6 HP accumulators’ pressure
shall be 9.6±0.2MPa.
5.1.3.2 LP accumulator nitrogen charging
1) LP accumulators shall be charged using LP nitrogen containers, which have
been used to charge HP accumulators.
2) Oil inlet stop valve of the actuator that is needed to be nitrogen charged shall be
closed.
3) Other steps shall be the same with that of HP accumulator, and the nitrogen
charging pressure shall be 0.35-0.4 MPa.
4) The nitrogen pressure inside accumulator shall be measured each week or
according to actual situation.
5.2 EH system commissioning items and its requirement
5.2.1System proof pressure test
a) Preparation work before proof pressure test
It shall be checked whether system valves have already been located at the
positions described in following table:
No. Valve position Correct
position
1 1#,2# main oil pumps inlet Open
2 1#、2# main oil pumps outlet pressure gauge Open
3 1#、2# main oil pumps outlet Open
4 Circulating pump filling port Close
5 Circulating pump suction port Open
6 1#、2# cooling water inlet Open
7 Regenerating pump suction port Close
8 Vent valve on the top of regenerating device resin Close
filter, cellulose filter
9 Pressure gauge of regenerating device resin filter, Open
cellulose filter
10 Isolation valves of 1#, 2# HP accumulator at pump Close
outlet
75D.002SM(B)-7 PAGE 19 OF 48
overflow valve shall be set to 17.0±0.2Mpa according to 5.2.4 and 5.2.5, and
clamps and supports shall be installed when necessary to avoid oil piping
cracked for big vibration.
6. EH system operation and maintenance
6.1 EH system operation and maintenance
When oil circulation and commissioning of HP fire-resistant fluid system and
turbine oil system are completed, EH control and protection system could be put
into normal operation.
6.1.1 EH pump start condition
If EH fluid supply system operates in low temperature condition (not lower than
20°C), the heater shall be started.
6.1.2 Mutual standby test and operation
When the operator starts one EH pump (pump A) on pump start operation platform
in the control room, he may press mutual standby test switch to start pump B after
pump A operates normally and then press pump B stop button to stop pump B.
After completion of mutual standby test, the standby pump shall be stopped. Then,
EH system has already been in normal working condition.
6.1.3 Perambulatory inspection
The operator shall record the following parameters every one hour.
Parameter Allowable limit scope Record
EH EH system pressure
14.0±0.5Mpa
system
Working oil pump
14.0±0.5Mpa
Pump outlet pressure
14.0±0.5Mpa
Level of EH fluid reservoir 500-730mm
EH fluid temperature of EH
37-60°C
fluid reservoir
System oil leakage none
Filter differential pressure
<0.24Mpa
P3
Filter differential pressure
<0.24Mpa
P4
Turbine System pressure
0.7±0.02Mpa
oil
system Level of oil reservoir
oil reservoir temperature
45-55°C
Pump outlet pressure
System oil leakage none
Diaphragm valve upper
0.7±0.02Mpa
chamber pressure
75D.002SM(B)-7 PAGE 23 OF 48
6.1.5 Reset
Two reset methods: manual and remote control
Remote control: the lights indicated DEH reset and RSV actuator open shall be
lighted by pushing the reset button in control room. If unit fails to be reset, it shall
be checked whether 0.7MPa protection oil pressure has been established in
diaphragm valve upper chamber and whether 20/ASR solenoid valve has been
energized by using iron wire or saw blade. If there is no excitation, the solenoid
valve has not been energized by DEH.
Local control: the reset handle shall be wheeled counterclockwise by hand and
then loosened slowly which make handle back to normal position. If 0.7MPa
protection oil pressure has been established in diaphragm valve upper chamber,
unit successfully resets.
6.1.6 EH alarm and monitor signal
6.1.6.1 Alarm
a) High EH fluid pressure
The signal comes from 63/HP pressure switch inside EH fluid power unit terminal
box ER, which shall be acted when fluid pressure exceeds 16.2MPa. The cause
shall be found out.
b) High EH fluid temperature
The signal comes from WP digital temperature controller. EH fluid temperature
will exceed 50°C once it alarms, and it shall be checked.
c) Low EH fluid temperature
The signal comes from WP digital temperature controller. EH fluid temperature
will be lower than 20°C once it alarms, and the heater shall be put into operation.
d) Low EH fluid level
The signal comes from level switch 71/FL on EH fluid reservoir. When fluid level
is lower than 230mm, EH system could not work. It shall be monitored whether
EH oil piping is cracked and oil sprays when the alarm happens.
e) Low EH fluid level alarm
The signal comes from level switch 71/FL on EH fluid reservoir. When EH fluid
reservoir level is lower than 450mm, the alarm signal will be sent out.
f) Low EH fluid level pre-alarm
The signal comes from level switch 71/FL on EH fluid reservoir. When EH fluid
reservoir level is lower than 370mm, the alarm signal will be sent out.
g) Low EH fluid pressure
The signal comes from 63/LP pressure switch. When it alarms, the possibility of
low EH fluid pressure trip shall be considered.
h) Low EH fluid pressure trip
The signal comes from 63-1,2,3,4/LP pressure switches on EH header. The steam
turbine will trip once it alarms.
i) Large differential pressure of 1# oil pump outlet filter
75D.002SM(B)-7 PAGE 24 OF 48
The signal comes from differential pressure switch 63/MPF-1. It’s normal that it
alarms when fluid temperature is lower than 45°C, while pump A outlet filter shall
and fluid flow sound inside fluid inlet tube could not be heard, servo valve fault
happens; if fluid flow sound inside fluid inlet tube could be heard, dump valve
fault happens. In case that steam valve could be opened, the cable between DEH
cabinet and actuator or valve location control panel fault happens.
6.2.1.2 Failure to close
The connector plug on servo valve shall be disassembled. If actuator could not be
closed, servo valve has been getting stuck that shall be changed; if actuator could
be closed, valve location control panel cable or LVDT fault happens and LVDT
output shall be checked with full travel. Once steam valve stem gets stuck, inlet
stop valve of the actuator shall be closed and dump valve shall be opened.
6.2.1.3 Actuator delay
The filter or servo valve on actuator shall be changed.
They shall be changed every four years or according to the real situation. No
matter O-ring is good or not, it shall be changed for a new one when the sealing
part is damaged.
6.3.7Overflow valve, check valve of EH fluid power unit
It shall be changed every four years or according to real situation.
6.3.8 Actuator
One GV actuator, one ICV actuator, one MSV actuator and one RSV actuator shall
be checked every two years and other valve actuators shall also be checked if
necessary.
6.3.9 EH fluid reservoir
The magnetic filter shall be cleaned every one year and the reservoir shall be
cleaned every four years.
6.3.10 Remarks
The above mentioned time interval is the maintainance interval when the system
and subassemblies operate normally; however, the maitainance interval shall be
modified to satisfy the condition when abnormal operation fault or abnormal
condition happens and the affected subassemblies shall be repaired or replaced if
necessary. We suggest that the customer shall store whole set of replacements to
satisfy maintainance without tripping.
7.Settlement, use and notes of fire-resistant fluid
It includes system first fluid filling and complementary filling, flushing and fluid
refilling after system maintainance and anti-deteropration of fire-resistant fluid
etc.
7.1 Fire-resistant fluid supplier
The fire-resistant fluid applied to EH control system must be fire-resistant pure
phosphate ester hydraulic fluid and satisfy typical characteristic parameters listed
in the attached table.
When purchasing fire-resistant fluid, the customer shall ask the supplier for the
fluid physics characteristics, fire-resistant characteristics, safety use measures,
compatible material, inspection and test method etc. specification and suggestion
and shall obey complete personnel health protection and prevention measures.
For keeping fire-resistant fluid quality invariable at any time to ensure the
performance of EH control system, we suggest that some key parameters of fire-
resistant fluid shall be regularily tested. If the test result exceeds the specified
limitation, the related remedy measures shall be immediately taken. The
inspection shall include (but not limited to the followings):
NUMBERING METHOD
Particle number in each 100 ml fluid
Particle
dia. 5-15 15-25 25-50 50-100
>100
(mm)
class
00 125 22 4 1 0
0 250 44 8 2 0
1 500 89 16 3 1
2 1000 178 32 6 1
3 2000 356 63 11 2
4 4000 712 126 22 4
5 8000 1425 253 45 8
6 16000 2850 506 90 16
7 32000 5700 1012 180 32
8 64000 11400 2025 360 64
9 128000 22800 4050 720 128
10 256000 45600 8100 1440 256
11 512000 91200 16200 2880 512
12 1024000 182400 32400 5760 1024
13 2048000 364800 64800 11520 2050
14 4096000 729600 129600 23050 4100
15 8192000 1459200 259200 46100 8200
16 16384000 2918400 518400 92200 16400
2.5-5 To be determined
5-10 2700 4600 9700 24000 320 8700 12800
00 0 0 To be
10-25 670 1340 2680 5360 107 2140 42000 determined
00 0
25-50 93 210 380 780 151 3130 6500
0
50-100 16 28 56 110 225 430 1000
1 3 5 11 21 41 92
>100
REVISION PAGE
Mark Qty. Page Revised doc. Signature Date Remarks
number number
75D.002SM(B)-7 PAGE 30 OF 48