Fire Pump Test Electric 2010
Fire Pump Test Electric 2010
ALCAN MTY
Conferred With Title Tested By Date
POR NFPA-25 CAP. 8.3.4 LA PRESION NO DEBERA CAER POR MAS DEL
5%.
Pump Data Rated Net Head (psi) Rated Flow % 90% Flow 50% FLOW
Rated Flow (US gpm): 3500 164 0% 0%
Rated Pressure (psi): 135 141 100% 90% 157
Rated Speed (RPM): 1770 125 150% 135%
RPM Suct. Presion (psi) Disch.Presion (psi) Net Head Flow RPM Adj. Net Head RPM Adj. Flow % of rated P % of rated Flow
180
160
Field Test Results
140 Column A
120
100
80
60
40
20 CURVA DE ACUERDO A: N. F. P. A. - 20
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110% 120% 130% 140% 150% 160%
Percent Rated Flow
Prepared by IME. Luis Felipe Serrano, FTech Services Office Printed 12/16/2020 503403046.xls