This document provides a design summary for the concrete diaphragm shear design of the Zapata de Futuro Hospital de Nueco Chimbote project based on ACI 318-19 code. The design checks the minimum reinforcement ratios and shear capacity against the factored in-plane shear load of 25 kips/ft. Both checks were satisfactory, confirming the diaphragm design is adequate with the 6-inch thick diaphragm reinforced with #5 bars at 12 inches on center.
This document provides a design summary for the concrete diaphragm shear design of the Zapata de Futuro Hospital de Nueco Chimbote project based on ACI 318-19 code. The design checks the minimum reinforcement ratios and shear capacity against the factored in-plane shear load of 25 kips/ft. Both checks were satisfactory, confirming the diaphragm design is adequate with the 6-inch thick diaphragm reinforced with #5 bars at 12 inches on center.
This document provides a design summary for the concrete diaphragm shear design of the Zapata de Futuro Hospital de Nueco Chimbote project based on ACI 318-19 code. The design checks the minimum reinforcement ratios and shear capacity against the factored in-plane shear load of 25 kips/ft. Both checks were satisfactory, confirming the diaphragm design is adequate with the 6-inch thick diaphragm reinforced with #5 bars at 12 inches on center.