Professional Documents
Culture Documents
Paper - QUALITATIVE ANALYSIS OF PARTIAL DISCHARGE RADIO FREQUENCY EMISSION PROPAGATION IN MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
Paper - QUALITATIVE ANALYSIS OF PARTIAL DISCHARGE RADIO FREQUENCY EMISSION PROPAGATION IN MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
A bstract - This paper will review the propagation decision was made to develop suitable sources in-house. Care
characteristics of radio frequency emissions in metal-clad was taken during this work to compare the PD emissions from
medium voltage switchgear. The radio frequency emissions will these devices with "real world" PD emissions from damaged /
be generated using various sources of partial discharge and worn switchgear components. This allowed direct comparisons
measured using a prototype distributed antenna based partial to be made supporting the assertion that the artificial PD sources
discharge detection system. It will be shown that partial produce emissions representative of PD found in switchgear.
discharge sources of varying type and magnitude can be These PD sources were developed to allow simple temporary
detected in the switchgear and that the attenuation of the installation into medium voltage metal-clad switchgear and
emissions between compartments is easily observed in most operation in a laboratory environment, in order to investigate the
cases. In conclusion a partial discharge monitoring and location propagation of the RF emissions from them. To conduct the
system is proposed. measurement of the RF emissions, compact antennas were
installed in each compartment of the switchgear and connected
Index Terms — Partial discharge, Radio frequency, Medium to receiving apparatus. This apparatus is designed to detect the
Voltage Switchgear, Partial discharge fault location emission signature of PD and classify it against an AC reference
voltage. It operates a s a distributed detection system, measuring
I. INTRODUCTION the RF signal level in each compartment with the intention that
the location of the PD be identified purely through the signal
This paper will discuss the investigation of the propagation of level.
radio frequency (RF) energy emanating from partial discharges An evaluation of this equipment was performed using IEC
(PD) within medium voltage metal-clad switchgear. The purpose 15kV medium voltage switchgear. Observations were collected
of this investigation is to support the hypothesis that the location during the exercise for both surface and internal PD sources.
and "strength" of PD can be estimated through RF based Analysis of the collected results was performed using simple
detection techniques. The advantages of this type of system over algorithms to estimate the location of the PD source.
more conventional PD detection systems are expected to be:
a. It requires no direct connection to the high voltage II. DEVELOPMENT & CHARACTERISATION OF
conductors avoiding additional components connected PD SOURCES FOR LOWER VOLTAGE
to the high voltage insulation system. OPERATION.
b. It is potentially a low cost alternative to conventional PD
detection systems. The intention was to investigate the performance of the RF
c. It will identify the switchgear compartment location of based PD detection system in switchgear operating at voltages
the PD source without recourse to a third party. of 11kV upwards. To accomplish this in real world switchgear it
d. It will provide a cost effective system for continuously was beneficial to operate the switchgear at voltages lower than
monitoring switchgear for PD providing the switchgear its rating to ensure that no significant switchgear based PD was
owner with more information to base maintenance present whilst performing the investigation, thereby ensuring the
decisions upon. observed PD was only that introduced for the purpose of this
investigation. To support this requirement, artificial PD sources
The activities undertaken to test a prototype system for RF that replicated the behavior of real PD sources at relatively low
based detection of PD within metal-clad switchgear are voltages were required.
discussed in this paper. It was decided to develop two types of source replicating the
Initial efforts focused upon the acquisition of "controllable" PD physical defects typical of switchgear where surface and internal
sources that would operate at voltages typical of the switchgear discharge are found. Given that the available switchgear sample
in question. Such devices are not readily available therefore the has a nominal voltage of 11 kV, the artificial sources would need
- 186 -
X and Y axis “bin”. The Z-axis in this case is represented by color 50pC. Once its operation became non-continuous a rest period
and intensity. As the number of events in a particular bin of 20 minutes would return it to its original behavior.
increases, so does the brightness of the color (blue = dark, The surface PD source, a s shown in Fig. 4, was constructed
yellow = light) giving the reader a visualization of the PD event from a nylon rod, wrapped in aluminum foil which in turn was
density. The subject of PRPD interpretation is complex, but [4] wrapped in PVC insulation. A section of the foil and insulation
represents an introduction to this topic. was removed to create an air gap with the nylon rod exposed.
The exposed section of nylon operated a s a surface upon which
electrical tracking could occur thereby creating surface PD. This
arrangement is analogous to sources of PD found in switchgear
where the common cause is contaminated insulation. Fig. 5
shows a photograph of the artificial surface PD source discussed
here.
C o n n ectio n point
l.OnC
□ Nylon Rod
O.OnC-
Aluminum Foil C o n n ectio n point
□ PVC insulation
-l.OnC
S e ctio n Ά '
-2.0nC_____________________________________ __________________________________________
- 187 -
period of time. The authors suspect that this phenomena was A pictorial representation of the physical switchgear
due to an increased concentration of ozone in the vicinity of the arrangement and the RF based PD detection system can be
discharge area. seen in Fig. A-1 in Appendix A. A picture showing the front
In summary, the exercise to develop artificial PD sources elevation of the actual switchgear with the antenna cables
suitable for temporary installation into switchgear was installed can be seen in Fig. 8.
considered a success. While these could not be described as
laboratory instruments capable of being used a s reference or
calibration devices, they are more than suitable for the purpose
of this investigation.
III. INVESTIGATION
The detection nodes were connected to an Ethernet network The methodology followed during the testing was:
a. Background PD measurements were made using both
and communicated with a laptop PC to display the detected
the reference system and the RF based system for the
levels of RF. Only 6 detection nodes were available for this test
switchgear in both energised and de-energised states.
and were installed into switchgear section numbers 1 through 5
and 11. The detection system uses the antennas to detect the b. One of the sources was introduced into the
compartment of interest and energised at an
RF pulse generated by each PD event and classifies it in terms
appropriate operating voltage to cause PD. Fig. 2 and
of its phase timing and pulse size. This information is presented,
Fig. 5 show pictures of the sources installed into the
on a per channel and node basis, a s basic statistics and a s a
switchgear ready for energisation.
PRPD graph typical of many PD measurement systems.
- 188
c. The PD emission level was monitored using the
reference system and the applied voltage adjusted in TABLE II
an effort to maintain a relatively constant level of PD SURFACE SOURCE IN SEC. 1 CABLE -900PC
throughout the observation period of at least 2 minutes. T e st 1-2 Mean Event Amplitudes in dB (2min Average)
d. Data comprising the mean PD event amplitude was Section B u sb ar Breaker C able S e c . Mean
collected for each channel of each detection node over
the observation period. This data was used in the Section 1 9 7 12 9
subsequent analysis. Section 2 3 1 0 1
e. Once the observation period had elapsed the Section 3 0 0 0 0
switchgear was de-energised and the background PD
Section 4 5 0 0 2
level checked using both PD detection systems.
Section 5 5 0 0 2
The two source types, internal and surface PD, were cycled Section 11 4 0 0 1
through the three compartments of sections 1 and 2 of the
switchgear. For each variation, the switchgear was energised TABLE III
and data collected a s described above. The rationale behind this INTERNAL SOURCE IN SEC. 1 BREAKER-300PC
is the desire to investigate the RF propagation behavior for both T e st 1-3 Mean Event Amplitudes in dB (2min Average)
the switchgear line-up end compartments and those within the
switchgear line up. After initial tests, it was decided that an Section B u sb ar Breaker C able S e c . Mean
observation period of 2 minutes was sufficient to record data for Section 1 10 10 1 7
representative analysis. Section 2 8 4 1 4
Section 3 5 2 0 2
IV. RESULTS
Section 4 7 4 1 4
The background PD was measured a s 5pC when the Section 5 2 0 1 1
switchgear was energised at its full rated voltage with no artificial Section 11 2 0 0 1
PD source present. When no voltage was applied the PD
measurement was below the measurement threshold of the
Table III shows no difference in the measured signal level
reference instrument. This exercise served to prove that the
between the breaker and busbar compartments in section 1
switchgear was free of significant PD because the artificial
despite the PD source being located in the breaker compartment
sources would be operated at voltage levels lower than the
of section 1.
switchgear’s rating.
The RF based system was used to measure the background TABLE IV
RF noise level of the environment. A measurement of 6dB was SURFACE SOURCE IN SEC. 1 BREAKER -1500PC
recorded irrespective of whether the switchgear was energised.
T e st 1-4 Mean Event Amplitudes in dB (2min Average)
These background measurements were repeated regularly
throughout the test sequence and the measurements verified Section B u sb ar Breaker C able S e c . Mean
that the baseline conditions remained unchanged. Section 1 11 17 15 14
The result tables presented in Table I through Table XII Section 2 7 5 0 4
provides the mean dB level acquired over a 2 minute period for
Section 3 7 3 1 3
each compartment in each instrumented switchgear section.
There is one table for each source location. The shaded bars in Section 4 0 6 1 2
the raw results area of the table gives an indication of the value Section 5 5 1 1 2
relative to the highest value within that table. The section mean
Section 11 5 1 1 2
value is calculated from the 3 raw data results associated with
the section in question.
TABLE V
The PD figure quoted in the title of each table is the
INTERNAL SOURCE IN SEC. 1 BUSBAR-200PC
approximate mean of the PD generated by the source during the
2 minute averaging period a s measured by the reference T e st 1-5 Mean Event Amplitudes in dB (2min Average)
instrument. Section B u sb ar Breaker C able S e c . Mean
TABLE I Section 1 8 5
1 7 1 1
INTERNAL SOURCE IN SEC. 1 CABLE -350PC
Section 2 10 0 1 3
T e st 1-1 Mean Event Amplitudes in dB (2min Average)
Section 3 6 2 1 1 3
Section B u sb ar Breaker C able S e c . Mean
Section 4 6 4 0 3
Section 1 12 11 18 14
Section 5 6 0 0 2
Section 2 12 δ 13 11
Section 11 4 0 0 1
Section 3 8 7 13 9
Section 4 6 6 4 6 Table V shows that the highest level detected in Test 1-5 was in
Section 5 6 1 2 2 3 the busbar compartment of section 2 yet the PD source was
Section 11 5 0 3 3 located in the busbar compartment of section 1.
- 189 -
TABLE VI TABLE X
SURFACE SOURCE IN SEC. 1 BUSBAR -1050PC SURFACE SOURCE IN SEC. 2 BREAKER -1400PC
T e st 1-6 Mean Event Amplitudes in dB (2min Average) T e st 2-4 Mean Event Amplitudes in dB (2min Average)
Section B u sb ar Breaker C able S e c . Mean Section B u sb ar Breaker C able S e c . Mean
Section 1 9 9 3 7 Section 1 4 2 0 2
Section 2 13 2 0 5 Section 2 12 16 9 13
Section 3 8 7 0 5 Section 3 7 5 0 4
m
CD
Section 4 8 10 2 7 Section 4 1 1 5
Section 5 8 7 0 5 Section 5 6 0 0 2
Section 11 4 5 5 5 Section 11 0 0 0 0
Table VI shows that during test 1-6 the highest PD level detected TABLE XI
was in the busbar compartment of section 2 whereas the PD INTERNAL SOURCE IN SEC. 2 BUSBAR -480PC
source was located in the busbar compartment of section 1. It T e st 2-5 Mean Event Amplitudes in dB (2min Average)
also shows an unexpectedly high level of PD in the breaker Section B u sb ar Breaker C able S e c . Mean
compartment of section 4.
1
CD
Section 1 6 0 4
TABLE VII Section 2 13
cn
0 6
INTERNAL SOURCE IN SEC. 2 CABLE -430PC Section 3 4
8 5 0
T e st 2-1 Mean Event Amplitudes in dB (2min Average)
Section 4 10 6 0 5
Section B u sb ar Breaker C able S e c . Mean
Section 5 9 3 1 1 4
Section 1 3 0 6 3
Section 11 1 0 0 0
Section 2 12 10 17 13
Section 3 2 2 0 1 TABLE XII
SURFACE SOURCE IN SEC. 2 BUSBAR -1000PC
Section 4 1 I 1 3 1
T e st 2-6 Mean Event Amplitudes in dB (2min Average)
Section 5 4 0 0 1
Section B u sb ar Breaker C able S e c . Mean
Section 11 4 1 2 2
Section 1 8 10 11 10
TABLE Vili
SURFACE SOURCE IN SEC. 2 CABLE -1000PC
Section 2 23 m 18 18
Section 3 9 11 11
T e st 2-2 Mean Event Amplitudes in dB (2min Average) Section 4 13 13 10 12
1
Section B u sb ar Breaker C able S e c . Mean
CD
Section 5 12 10 10
Section 1 8 1 7 5 Section 11 4 6 5 5
Section 2 18 19 15
Section 3 5 2 1 3 The graph presented in Fig. 9 shows the mean RF event
amplitude recorded by the RF PD detection system plotted
Section 4 0 1 1 1
against the average PD detected by the reference system. The
Section 5 6 1 1 3 RF level plotted was measured within the sam e compartment as
Section 11 2 1 1 1 the location of the artificial source.
TABLE IX V. DISCUSSION
INTERNAL SOURCE IN SEC. 2 BREAKER -230PC
T e st 2-3 Mean Event Amplitudes in dB (2min Average) The results presented in Table I through Table XII show that
the prototype system was able to detect the presence, and
Section B u sb ar Breaker C able S e c . Mean
absence of PD within the switchgear. We see that the level of RF
Section 1 11 11 11 11 detected in each compartment varies, roughly, with proximity to
Section 2 14 18 14 16 the PD source.
Section 3 10 9 4 8 Additionally, from the results presented in Fig. 9, it is shown
there is not a direct correlation between the level of PD as
Section 4 ) 12 7 9 measured by the reference instrument and the level of RF
Section 5 δ |δ 4 7 detected. This further supports the conclusions presented in [5]
Section 11 2 0 1 1 that the behavior of different switchgear compartments and the
location of the PD source within the switchgear line-up have an
effect on the propagation of the RF energy. This was particularly
noticeable in the case of the end section busbar compartment. It
- 190 -
is suspected that the busbar behaves similarly to a wave guide the largest mean event value recorded in the raw results table.
rather than the leaky box behavior of the other compartments. Algorithm 2 used the mean of each sections’ 3 recorded values
to identify the section of switchgear where the source was
located and then identified the highest compartment value from
25 within that section a s the location of the PD source.
Table XIII shows the results of the algorithms when applied to
the acquired data. It can be seen that both algorithms have some
success at correctly identifying the location but that neither is
perfect. Using algorithm 2 the system demonstrated an 83%
20
success rate for the correct identification of the PD source
location.
A particularly notable observation regarding the raw data is
that there is, on occasions, little or no difference in the measured
values between compartments. This behavior is not consistent
with the other tests where appreciable attenuation of the RF
signals occurs between the compartments. During the
c investigation no reason for this inconsistent behavior could be
00
10 identified.
VI. CONCLUSIONS
- 191 -
substation. In 2010, Mr. Bowen accepted a position with Aramco
VII. REFERENCES Services Company a s Power System Technologist. His current
role includes investigating technologies that can be applied by
[1] IEEE Std 1799-2012, IEEE Recommended Practice for Aramco to improve safety, reliability and profitability. Mr. Bowen
Quality Control Testing of External Discharges on Stator has presented at numerous technical seminars for the IEEE
Coils, Bars, and Windings. Houston Section’s Continuing Education on Demand. He is a
[2] S. Rengarajan et al, “Development of an UHF detection professional engineer in the state of Texas and was elevated to
system for partial discharge measurement in transformer the rank of IEEE Fellow for his pioneering work in Safety By
insulation”, Conference Record of the 2008 IEEE Design.
International Symposium on Electrical Insulation, 2008 pp
100-103, 2008.
[3] Jian Li et al, “Resonant Frequency Calculation and Optimal
Design of Peano Fractal Antenna for Partial Discharge
Detection”, International Journal of Antennas and
Propagation, voi. 2012, Article ID 361517, 9 pages, 2012.
[4] D. A. Nattrass, “Partial discharge measurement and
interpretation” IEEE Electrical Insulation Magazine, 1988,
Voi. 4, pages 10-23.
[5] S. M. Hoek et al, “Emission and Propagation Mechanisms of
PD Pulses for UHF and Traditional Measurements”,
International Journal on Electrical Engineering and
Informatics - Voi. 4, No.3, Oct. 2012.
VIII. ACKNOWLEDGMENTS
The authors would like to thank the following people for their
contributions: Peter Codd, Simon Wilson and Graham Earp (EA
Technology)
IX. VITAE
- 192 -
APPENDIX A
S ectio n s 6-10
Fig. A-1 Pictorial representation of switchgear line-up used for this investigation
Notes
1. Antennas installed in each compartment chamber - VCB, Busbar and Cable compartment (The antenna located in
the cable compartment is not shown)
2. Sections 6 through 10 are reduced in width for the clarity of this diagram
- 193 -
- 194 -