Professional Documents
Culture Documents
3NJ62 Manual en-US
3NJ62 Manual en-US
Product description 2
Functions 3
SENTRON
Mounting 4
Switch Disconnectors with Fuses,
In-Line Design Configuration 5
3NJ62
Technical specifications 6
System Manual
Dimensional drawings 7
Schematics 8
11/2009
711 6114-02 DS 03
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and
safety instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction................................................................................................................................................ 7
2 Product description .................................................................................................................................... 9
2.1 Overview ........................................................................................................................................9
2.2 Benefits ........................................................................................................................................11
2.3 Application....................................................................................................................................11
2.4 Basic versions ..............................................................................................................................12
2.5 Accessories..................................................................................................................................12
2.6 Design ..........................................................................................................................................13
3 Functions ................................................................................................................................................. 15
3.1 Mode of operation ........................................................................................................................15
3.2 Electronic fuse monitoring............................................................................................................17
3.3 Motorized operation .....................................................................................................................36
3.4 Connection method......................................................................................................................37
3.5 Current transformers and current transformer busbars ...............................................................37
3.6 Ammeters.....................................................................................................................................38
4 Mounting.................................................................................................................................................. 39
4.1 Mounting size 00..........................................................................................................................39
4.2 Mounting size 1 ............................................................................................................................46
4.3 Mounting sizes 2 and 3 ................................................................................................................53
5 Configuration ........................................................................................................................................... 61
5.1 Installation data ............................................................................................................................61
5.2 Rated currents..............................................................................................................................62
5.3 Configuration rules.......................................................................................................................63
6 Technical specifications........................................................................................................................... 65
7 Dimensional drawings.............................................................................................................................. 77
7.1 2-/3-pole switch disconnectors.....................................................................................................77
7.2 4-pole switch disconnectors.........................................................................................................79
7.3 Position of the phases, terminal bolts, and current transformers ................................................80
7.4 Current transformers....................................................................................................................81
7.5 Ammeters.....................................................................................................................................83
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 5
Table of contents
8 Schematics .............................................................................................................................................. 85
8.1 Switching examples .................................................................................................................... 85
8.2 Terminal connection diagram of the multi-function plugs ........................................................... 92
8.2.1 Manually operated switch disconnectors .................................................................................... 92
8.2.2 Switch disconnectors with motorized operating mechanism ...................................................... 92
3NJ62
6 System Manual, 11/2009, 711 6114-02 DS 03
Introduction 1
Purpose of the manual
The "SENTRON 3NJ62 inline switch disconnectors with fuses" manual describes the basic
functions of the switchgear range. It contains information about selection, configuring, and
commissioning.
In addition to the main devices, it also includes details of accessories.
Furthermore, to facilitate configuration, the manual contains dimension drawings, circuit
diagrams, and technical specifications of the switchgear and accessories.
All explanations in the manual regarding sizes 00, 1, 2, and 3 relate to the BS versions.
However, please also refer to the technical specifications in chapter 6, which differ in a few
respects for the two fuse types (LV HRC and BS).
Symbol Meaning
LED illuminated
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 7
Introduction
3NJ62
8 System Manual, 11/2009, 711 6114-02 DS 03
Product description 2
2.1 Overview
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 9
Product description
2.1 Overview
3NJ62
10 System Manual, 11/2009, 711 6114-02 DS 03
Product description
2.2 Benefits
2.2 Benefits
2.3 Application
The plug-in 3NJ62 switch disconnectors with fuses are installed in low-voltage distribution
boards where a minimum amount of space is available for a maximum number of cable
ducts to the power distribution. They can be easily fitted in all common control cabinets
(minimum depth: 400 mm).
The plug-in 3NJ62 switch disconnectors with fuses are available for rated uninterrupted
currents of 160 A to 630 A. LV HRC fuse links according to IEC 60269-1 / EN 60269-1 or BS
fuse links according to BS 88 provide overload and short-circuit protection up to 690 V
AC/440 V DC.
The switch disconnectors can be retrofitted at any time with electronic fuse monitoring
devices, auxiliary switches, an ammeter (48 mm x 48 mm), and up to four current
transformers, with no extra space required. For installation in control cabinets with a depth >
400 mm, the mounting depth of the disconnectors can be increased by 200 mm using a
contact extension. Further installation accessories, such as guide rails and blanking covers
for empty sections, complete the product range.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 11
Product description
2.4 Basic versions
2.5 Accessories
The following accessories are available in addition to the main devices:
● Electronic fuse monitoring devices
● Current transformers
● Ammeters
● Auxiliary switches
● Multi-function plugs
● Terminals
● Terminal covers
● Guide rails
● Blanking covers
● Busbar covers
3NJ62
12 System Manual, 11/2009, 711 6114-02 DS 03
Product description
2.6 Design
2.6 Design
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 13
Product description
2.6 Design
3NJ62
14 System Manual, 11/2009, 711 6114-02 DS 03
Functions 3
3.1 Mode of operation
Operation
The plug-in switch disconnectors are fitted with a snap-action mechanism and are switched
by turning the handle approx. 45°. Once actuated, the handle is folded against the front
panel in the ON or OFF position for safety reasons.
Indication
A unique switch position indication is output by the indicator in the inspection window of the
in-line disconnector (ON "I" = red, OFF "O" = green). The switch position indicator is
mechanically linked to the moving switching contacts.
Voltage test
In the event of a voltage test on the fuse links, the transparent insert in the front panel is
opened.
Personnel safety
The switch disconnectors are type tested according to IEC 60947-3 and have degree of
protection IP41 in the operating state.
The special locking mechanism on the handle ensures that the in-line disconnector must be
switched off before it is possible to open the cover and remove the fuses. A switchgear key
according to DIN 43668 is also required to open the cover.
Disconnection during the switching operation (snap-action mechanism) is implemented
before and after the fuse link. This ensures that, if power is supplied over the busbars or via
the cable connecting side, the fuse links are in a dead state when switched off.
Locking
In the OFF position, the handle can be padlocked (padlock Ø: 6 mm) to protect against
unintentional restarting.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 15
Functions
3.1 Mode of operation
Switch position
OFF ON
"OFF" position, operating lever in OFF position "ON" position, operating lever in OFF position
"OFF" position, operating lever in end position "ON" position, operating lever in end position
3NJ62
16 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
Figure 3-1 3NJ62 size LV HRC1 with electronic fuse monitoring device (EFM 10)
Figure 3-2 3NJ62 size LV HRC1 with electronic fuse monitoring device (EFM 20/25)
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 17
Functions
3.2 Electronic fuse monitoring
3NJ62
18 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
$&7,9(
)$8/7/
)$8/7/
) ) )
)$8/7/
0LFUR
FRQWUROOHU
5HOD\
WARNING
The green LED does not light up if the electronic fuse monitoring device is connected in a
way other than that described above when the infeed is live and more than one fuse is
faulty! In this case, the EFM's internal power supply can no longer be guaranteed (refer to
"Voltage tap for the internal power supply and direction of the incoming supply" below)!
WARNING
If the EFM is built into the 3NJ62 and not all lines of the changeover contact are wired to
the multi-function plug, the exposed cable ends must be electrically insulated.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 19
Functions
3.2 Electronic fuse monitoring
3NJ62
20 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
'LVSOD\
0LFUR
) ) ) FRQWUROOHU
5HOD\
5HOD\
WARNING
The display is not illuminated if the electronic fuse monitoring device is connected in a way
other than that described above when the infeed is live and more than one fuse is faulty! In
this case, the EFM's internal power supply can no longer be guaranteed (refer to "Voltage
tap for the internal power supply and direction of the incoming supply" below)!
WARNING
If the EFM is built into the 3NJ62 and not all lines of the changeover contact are wired to
the multi-function plug, the exposed cable ends must be electrically insulated.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 21
Functions
3.2 Electronic fuse monitoring
Cable designation
3NJ62
22 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 23
Functions
3.2 Electronic fuse monitoring
/
'LVSOD\
0LFUR
FRQWUROOHU
) )
5HOD\
5HOD\
Figure 3-5 3NJ62 size LV HRC 00, internal wiring with EFM 25
WARNING
The display is not illuminated if the electronic fuse monitoring device is connected in a way
other than that described above when the infeed is live and more than one fuse is faulty! In
this case, the EFM's internal power supply can no longer be guaranteed!
WARNING
If the EFM is built into the 3NJ62 and not all lines of the changeover contact are wired to
the multi-function plug, the exposed cable ends must be electrically insulated.
3NJ62
24 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
WARNING
The fuse or the line is not monitored in SETUP mode. Monitoring is only assured in RUN
mode.
If line monitoring is active, the voltage limits are monitored. If one of the voltages exceeds or
falls below the limit, relay 2 drops out providing closed-circuit principle is selected (see
below). The symbol for undervoltage or overvoltage appears on the display.
If a fault occurs, the relays respond according to the selected operating principle after the set
error delay time (Del):
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 25
Functions
3.2 Electronic fuse monitoring
0HP QROLQHPRQLWRULQJDFWLYH
8[\ 8[\
5HOD\ 5HOD\
Lx
5HOD\ 5HOD\
'HO 'HO
/// // /// /// // ///
Lx 5HOD\ 5HOD\
5HOD\ 5HOD\
'HO 'HO
8[\ 8 +\VW 8[\ 8 +\VW
5HOD\ 5HOD\
Ux -y
5HOD\ 5HOD\
'HO 'HO
8[\ !8 +\VW 8[\ !8 +\VW
5HOD\ 5HOD\
Ux-y
5HOD\ 5HOD\
'HO 'HO
RSHQ
FORVHG
3NJ62
26 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
0HP QROLQHPRQLWRULQJDFWLYH
8 8
5HOD\ 5HOD\
L+
5HOD\ 5HOD\
'HO 'HO
8 8 +\VW 8 8 +\VW
5HOD\ 5HOD\
U=
5HOD\ 5HOD\
'HO 'HO
8 !8 +\VW 8 !8 +\VW
5HOD\ 5HOD\
U=
5HOD\ 5HOD\
'HO 'HO
RSHQ
FORVHG
You acknowledge an alarm by simultaneously pressing the Up and Down keys (only if the
memory function is active).
NOTICE
All alarms should be acknowledged, even if they are no longer present!
If several alarms are present, only the alarm with the highest priority is actually displayed. An
alarm for a faulty fuse takes priority over all others (refer to the alarm priorities below).
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 27
Functions
3.2 Electronic fuse monitoring
WARNING
The fuse or the line is not monitored in SETUP mode. Monitoring is only assured in
RUN mode.
3NJ62
28 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 29
Functions
3.2 Electronic fuse monitoring
1)
On 11 41
Del
12 14 42 44
Off
2)
Upper limit exceeded:
No limit violation:
Lower limit undershot:
3) Functions or indication are only active if line monitoring is activated
4) If the memory function is active, the fault indication alternates with the following symbol:
1) 2)
3NJ62
30 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
WARNING
The fuse or the line is not monitored in SETUP mode. Monitoring is only assured in
RUN mode.
● U =: Line-to-line voltage
● Value: Value range (190 V to 510 V)
● TEST 1, TEST 2: Test on relay 1, test on relay 2
● SET?: Setup mode
● Hyst: Hysteresis (fluctuation range) in V (1 V - 20 V, default setting: 5 V)
● Del: Delay time after which a fault is indicated (0.1 to 20 s)
● Mem?: Save yes / no
● NC: Normally closed - closed-circuit principle, i.e. the relay is energized (default setting)
● NO: Normally Open: open-circuit principle
● 1 2? : Contactor 2 responds like contactor 1
● Func 2? : Contactor 2 responds to overvoltage/undervoltage/phase failure
● Error: Fault indication
● RES?: Reset fault indication
● Memory?: Save fault indication yes / no
● L+ , L- : Voltage at the fuse: Lower threshold value undershot
● U= : Line-to-line voltage: Lower threshold value undershot
● U= :Line-to-line voltage: Upper threshold value exceeded
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 31
Functions
3.2 Electronic fuse monitoring
3NJ62
32 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
1)
On 11 41
Del
12 14 42 44
Off
2)
Upper limit exceeded:
No limit violation:
Lower limit undershot:
3) Functions or indication are only active if line monitoring is activated
4) If the memory function is active, the fault indication alternates with the following symbol:
1) 2)
If several alarms are present, only the alarm with the highest priority is actually displayed.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 33
Functions
3.2 Electronic fuse monitoring
Voltage tap for the internal power supply and direction of the incoming supply on all EFMs, taking the
EFM 10 as an example
The EFM electronics are supplied via the phases (L1, L2, L3 or L+, L-) of the main circuit.
The voltage for the internal power supply is always tapped at the fuse holders on the side of
the rear plug-in contacts. Owing to the internal power supply, the electronics are only fully
functional if the 3NJ62 is switched on and at least two phases on the input side are supplied
with power.
① Infeed
② Outgoing feeder
WARNING
The green LED on the EFM 10 does not light up, and the display of the EFM 20 or the EFM
25 is not illuminated, if the electronic fuse monitoring device is connected in a way other
than that described above when the infeed is live and more than one fuse is faulty! In this
case, the EFM's internal power supply can no longer be guaranteed!
3NJ62
34 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.2 Electronic fuse monitoring
WARNING
If the green LED does not light up or the display is not illuminated when the infeed is live
and the EFM is correctly connected, the EFM must be immediately replaced!
Table 3- 1 Number of tripped fuses, electronics active or not active and fault signal as a function of the voltage tap
(infeed side, outgoing side) on the EFM 10/20
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 35
Functions
3.3 Motorized operation
Ma
nu
al
op
era
tio
n
3NJ62
36 System Manual, 11/2009, 711 6114-02 DS 03
Functions
3.4 Connection method
Current transformers
Current transformers are not allowed to be operated at no load because this could lead to
hazardous voltages at the terminals.
If four current transformers are used, the fourth transformer is in phase L3 for size 00, phase
L2 for size 1, or phase L1 for sizes 2 and 3.
If the fourth current transformer has size 00 or 1, the multi-function plug cannot be fitted
because there is not enough space. A current transformer cannot be installed in the N
conductor of 4-pole devices.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 37
Functions
3.6 Ammeters
3.6 Ammeters
According to DIN 43718, an ammeter with dimensions 48 mm x 48 mm can be used to
measure the current. It can be a moving-iron measuring instrument or a bi-metal measuring
instrument.
A holder for ammeters can be ordered as a separate accessory.
3NJ62
38 System Manual, 11/2009, 711 6114-02 DS 03
Mounting 4
4.1 Mounting size 00
Installing the plates for device versions with a motorized operating mechanism in the control cabinet
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 39
Mounting
4.1 Mounting size 00
Installing device versions with a motorized operating mechanism in the control cabinet
PP
3NJ62
40 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.1 Mounting size 00
PP
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 41
Mounting
4.1 Mounting size 00
Emergency mode
Installing 4-pole device versions with a motorized operating mechanism in the control cabinet
3NJ62
42 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.1 Mounting size 00
Overview
Note
The multi-function plug and the electronic fuse monitor (EFM) must be dismantled in order to
install accessories.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 43
Mounting
4.1 Mounting size 00
WARNING
The current transformers must not be operated with an open circuit.
3NJ62
44 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.1 Mounting size 00
,6HHWDEOH
(QGVOHHYHV
sPP
PP PP
6WULSSHG )RULQVFULSWLRQV +9.PP 6WULSSHG
VHHWDEOH
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 45
Mounting
4.2 Mounting size 1
Installing the plates for device versions with a motorized operating mechanism in the control cabinet
3NJ62
46 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.2 Mounting size 1
Installing device versions with a motorized operating mechanism in the control cabinet
PP
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 47
Mounting
4.2 Mounting size 1
PP
3NJ62
48 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.2 Mounting size 1
Emergency mode
Installing 4-pole device versions with a motorized operating mechanism in the control cabinet
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 49
Mounting
4.2 Mounting size 1
Overview
Note
The multi-function plug and the electronic fuse monitor (EFM) must be dismantled in order to
install accessories.
3NJ62
50 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.2 Mounting size 1
WARNING
The current transformers must not be operated with an open circuit.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 51
Mounting
4.2 Mounting size 1
,6HHWDEOH
(QGVOHHYHV
sPP
PP PP
6WULSSHG )RULQVFULSWLRQV +9.PP 6WULSSHG
VHHWDEOH
3NJ62
52 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.3 Mounting sizes 2 and 3
Installing the plates for device versions with a motorized operating mechanism in the control cabinet
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 53
Mounting
4.3 Mounting sizes 2 and 3
Installing device versions with a motorized operating mechanism in the control cabinet
PP
3NJ62
54 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.3 Mounting sizes 2 and 3
PP
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 55
Mounting
4.3 Mounting sizes 2 and 3
Emergency mode
Installing 4-pole device versions with a motorized operating mechanism in the control cabinet
3NJ62
56 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.3 Mounting sizes 2 and 3
Overview
Note
The multi-function plug and the electronic fuse monitor (EFM) must be dismantled in order to
install accessories.
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 57
Mounting
4.3 Mounting sizes 2 and 3
WARNING
The current transformers must not be operated with an open circuit.
3NJ62
58 System Manual, 11/2009, 711 6114-02 DS 03
Mounting
4.3 Mounting sizes 2 and 3
,6HHWDEOH
(QGVOHHYHV
sPP
PP PP
6WULSSHG )RULQVFULSWLRQV +9.PP 6WULSSHG
VHHWDEOH
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 59
Mounting
4.3 Mounting sizes 2 and 3
3NJ62
60 System Manual, 11/2009, 711 6114-02 DS 03
Configuration 5
5.1 Installation data
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 61
Configuration
5.2 Rated currents
00 160 125
125 100
80 64
1 250 200
224 180
125 100
2 400 320
355 284
315 252
3 630 504
500 400
400 320
3NJ62
62 System Manual, 11/2009, 711 6114-02 DS 03
Configuration
5.3 Configuration rules
Configuration rules for ventilated SIVACON cubicles with 3NJ62 switch disconnectors with fuses
● Equipment in the cubicle, from top to bottom, decreasing from size 3 to size 00
● Recommended maximum configuration per cubicle: approx. 2/3, including reserve
● Disconnectors of size 2 and 3 should - where possible - be distributed between different
cubicles
● Summation current of all feeders in the cubicle: max. 2000 A
● Rated currents of device sizes = 0.8 x IN of the biggest fuse link
● Rated currents of smaller fuse links of one size = 0.8 x IN of the fuse link
For the fully equipped cubicle, the rated diversity factor according to IEC 60439-1 applies.
Failure to comply with these instructions may lead to premature ageing of fuses and
uncontrolled tripping as a result of local overheating.
All data refers to an ambient temperature of the switchgear of 35°C (24-hour average value).
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 63
Configuration
5.3 Configuration rules
Blanking covers
Any sized groups of in- ≤ 64 A of single 100 mm = 2 units per group (Total 1 to In) x α
line disconnectors of device In combination with size 2 and
, 1 $ Q = permissible
, 1 $ Q
size 00 3 in one cubicle, the rated continuous load
currents are 280 A for size 2 current
, 1 $
and 440 A for size 3. α = Rated diversity
, 1 $
Devices of sizes 2 and 3 must factor
be allocated blanking covers
(see above).
3NJ62
64 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications 6
Standards EN/IEC 60947-3
Size Size 00
Type LV 3NJ6202-3 3NJ6203-1 3NJ6203-3
HR 3NJ6202-4 3NJ6204-1 3NJ6203-4
C 3NJ6204-2
BS 3NJ6243-3 3NJ6253-3 3NJ6262-3 3NJ6263-3
3NJ6262-4 3NJ6263-4
Switching capacity H H H S H
Rated insulation voltage Ui V 1000
Rated impulse voltage Uimp V 8000
For LV HRC fuse links according to - - 00 and 000
IEC 60269
For BS fuse links according to BS 88 A3 A3 00T*
* = fuse links from Lawson Fuses based
on BS 88
Rated operational current Ie for fuse
links according to IEC 60269 / BS 88 A 63 100 160 160 125 160 125
Rated operational voltage Ue
at 50 / 60 Hz rated frequency V 690 690 - - 500 690 500 690
with DC 230 440
Utilization category AC23B AC23B DC23B DC21B AC22B AC23B
Rated conditional short-circuit current
Short-circuit strength (rms value)
Short-circuit making capacity (rms kA 100 100 60 100 100
value) kA 66 66 60 55 66
Rated making capacity
cos φ = 0.65 A - - - - 480 375 - -
cos φ = 0.45 A 630 1000 - - - - - -
cos φ = 0.35 A - - - - - - 1600 1250
Rated breaking capacity
cos φ = 0.65 A - - - - 480 375 - -
cos φ = 0.45 A 504 800 - - - - - -
cos φ = 0.35 A - - - - - - 1280 1000
Endurance
Operating cycles, total 2000 2000 1600
Operating cycles, electrical (690 V, 300 300 200
cos φ = 0.65)
Power loss (without fuse links) W 7 17 43
Permissible ambient temperature °C - 5 ... + 55
Permissible mounting positions Horizontal or vertical with bottom connection
Degree of protection (in operating state) IP41
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 65
Technical specifications
3NJ62
66 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 67
Technical specifications
3NJ62
68 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 69
Technical specifications
3NJ62
70 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 71
Technical specifications
3NJ62
72 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 73
Technical specifications
3NJ62
74 System Manual, 11/2009, 711 6114-02 DS 03
Technical specifications
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 75
Technical specifications
Ammeters
Input x /1 A or x /5 A
Overload
Moving-iron measuring instrument 1.2 times
Bi-metal measuring instrument 2 times
Min/max pointer
Moving-iron measuring instrument min -
Bi-metal measuring instrument min 15
Intrinsic consumption
Moving-iron measuring instrument VA 0,6
Bi-metal measuring instrument VA 1
3NJ62
76 System Manual, 11/2009, 711 6114-02 DS 03
Dimensional drawings 7
7.1 2-/3-pole switch disconnectors
16(B
590 259
16(B
16(BE
3OXJLQ *XLGH
FRQWDFW SLQ
16(B 16(BE
16(B 16(BE
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 77
Dimensional drawings
7.1 2-/3-pole switch disconnectors
/ /
/ / /
16(B
3NJ62
78 System Manual, 11/2009, 711 6114-02 DS 03
Dimensional drawings
7.2 4-pole switch disconnectors
99
590 44,4 259
99
149
/ 1 / /
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 79
Dimensional drawings
7.3 Position of the phases, terminal bolts, and current transformers
/
/
/
/ / /
/ / /
16(B
/ / /
/
/
/
/
/ / /
/ /
16(B
/ / /
/
/
/
/ / /
/ / /
16(B
3NJ62
80 System Manual, 11/2009, 711 6114-02 DS 03
Dimensional drawings
7.4 Current transformers
16(B
º
Figure 7-16 Current transformers for 3NJ62 switch disconnectors, size 00 and size 1, with feed-
through opening ∅ 21 mm
45
30
NSE0_01965
º14
64.5
65
27
24
30 44
Figure 7-17 Current transformers for 3NJ62 switch disconnectors, size 00, with feed-through opening
∅ 14 mm
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 81
Dimensional drawings
7.4 Current transformers
16(B
º
Figure 7-18 Current transformers for 3NJ62 switch disconnectors, size 2 and size 3
3NJ62
82 System Manual, 11/2009, 711 6114-02 DS 03
Dimensional drawings
7.5 Ammeters
7.5 Ammeters
ป
16(B
ป
16(B
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 83
Dimensional drawings
7.5 Ammeters
3NJ62
84 System Manual, 11/2009, 711 6114-02 DS 03
Schematics 8
8.1 Switching examples
Switching examples
/
/
/
) ) )
.
7 /
$
16(B
Figure 8-1 Switching example with 1 current transformer wired to 1 ammeter, with 1 NO contact and
1 NC contact
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 85
Schematics
8.1 Switching examples
/
/
/
) ) )
.
7 /
16(B
Figure 8-2 Switching example with 1 current transformer wired to multi-function plug, with 1 NO
contact and 1 NC contact
/
/
/
) ) )
.
7 /
.
7 /
.
7 /
16(B
Figure 8-3 Switching example with 3 current transformers wired to multi-function plug, with 1 NO
contact and 1 NC contact
3NJ62
86 System Manual, 11/2009, 711 6114-02 DS 03
Schematics
8.1 Switching examples
/
/
/
) ) )
.
7 /
$
16(B
Figure 8-4 Switching example with 1 current transformer wired to 1 ammeter and multi-function
plug, with 1 NO contact and 1 NC contact
/
/
/
) ) )
.
7 /
$
.
7 /
.
7 /
16(B
Figure 8-5 Switching example with 3 current transformers wired to 1 ammeter and multi-function
plug, with 1 NO contact and 1 NC contact
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 87
Schematics
8.1 Switching examples
/
/
/
$FWLYH
)DXOW/
)DXOW/
)DXOW/
) ) ) 5HOD\
.
7 /
$
Figure 8-6 Switching example 3NJ62 manually operated, with 1 current transformer wired to 1
ammeter, with 1 NO contact and 1 NC contact, with electronic fuse monitoring device
(EFM10)
3NJ62
88 System Manual, 11/2009, 711 6114-02 DS 03
Schematics
8.1 Switching examples
/
/
/
'&9
9
$FWLYH
)DXOW/
0
) ) )
)DXOW/
)DXOW/
5HOD\
2
2
,
.
7 /
$
.
7 /
.
7 /
Figure 8-7 Switching example 3NJ62 with motorized operating mechanism, with 3 current transformers wired to 1
ammeter and multi-function plug, with 1 NO contact and 1 NC contact, with electronic fuse monitoring device
(EFM10)
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 89
Schematics
8.1 Switching examples
/
/
/
'LVSOD\
) ) ) 5HOD\ 5HOD\
.
7 /
$
Figure 8-8 Switching example 3NJ62 manually operated, with 1 current transformer wired to 1
ammeter, with 1 NO contact and 1 NC contact, with electronic fuse monitoring device
(EFM20)
3NJ62
90 System Manual, 11/2009, 711 6114-02 DS 03
Schematics
8.1 Switching examples
/
/
/
'&9
9
'LVSOD\
0
) ) )
5HOD\ 5HOD\
,
2
2
,
.
7 /
$
.
7 /
.
7 /
Figure 8-9 Switching example 3NJ62 with motorized operating mechanism, with 3 current transformers wired to 1
ammeter and multi-function plug, with 1 NO contact and 1 NC contact, with electronic fuse monitoring device
(EFM20)
3NJ62
System Manual, 11/2009, 711 6114-02 DS 03 91
Schematics
8.2 Terminal connection diagram of the multi-function plugs
3NJ62
92 System Manual, 11/2009, 711 6114-02 DS 03
Support
Download catalogs and information material:
www.siemens.com/lowvoltage/infomaterial
Online-Support:
www.siemens.com/lowvoltage/support
www.siemens.com/lowvoltage