Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 4

CONSULTING ENGINEERING SERVICES, INC.

811 MIDDLE STREET, MIDDLETOWN, CONNECTICUT 06457


PHONE; 860-632-1682 FACSIMILE: 860-632-1768

CHIMNEY NET INPUT CALCULATOR


PROJECT NAME GREENHILL
PROJECT NUMBER 97-018

I = (413,000)x((di*2)/M)xf{[(Dt-Da)xB]/(kxTm)}*.5)

di, IN 7.00

M - MASS FLOW PER 1,000 BTU OF FUEL BURNED


M (ASHRAE S92, 31.6 TABLE 2) 1.54

Dt - THEORETICAL DRAFT
CHIMNEY HEIGHT 30.00
VENT GAS TEMPERATURE RISE (ASHRAE S92, 31.6 TABLE 2) 500.00
Dt/100 FT 0.70
Dt 0.21

Da - AVAILABLE DRAFT
Da (FROM MANUFACTURER OF EQUIPMENT) -

B - BAROMETRIC PRESSURE
ALTITUDE, FT -
B 29.92

k - SYSTEM RESISTANCE
COMPONENT QTY k EACH k
INLET
GAS VENT WITH DRAFT HOOD 1 1.50 1.50
BAROMETRIC REGULATOR - 0.50 -
DIRECT CONNECTION - - -
ROUND ELBOW, 90 DEGREE 5 0.75 3.75
ROUND ELBOW, 45 DEGREE- 1 0.30 0.30
TEE OR 90 DEGREE CONNECTOR 1 1.25 1.25
Y CONNECTOR 1 0.75 0.75
CAP, TOP -
OPEN, STRAIGHT - - -
LOW RESISTANCE 1 0.50 0.50
OTHER - - -
SPARK SCREEN 1 0.50 0.50
PIPING (0.04x(L, FT/di, IN)) 30 0.02 0.51

k TOTAL 9.06

Tm (ASHRAE S92, 31.7 TABLE 4) 820.00

I, BTU/HR 382,069

DATE: 12/21/2020 PAGE 1 OF 4


CONSULTING ENGINEERING SERVICES, INC.
811 MIDDLE STREET, MIDDLETOWN, CONNECTICUT 06457
PHONE: 860-632-1682 FACSIMILE: 860-632-1768

CHIMNEY DIAMETER CALCULATOR


PROJECT NAME
PROJECT NUMBER

di = ((IxM)/(413,000x((((Dt-Da)xB)/(kxTm))*.5)))*.5

I, BTU/HR 10,221,539

di, IN - INITIAL GUESS 24.00

M - MASS FLOW, LB PER 1,000 BTU OF FUEL BURNED


M (ASHRAE S92, 31.6 TABLE 2) 1.54

Dt - THEORETICAL DRAFT
CHIMNEY HEIGHT 100.00
VENT GAS TEMPERATURE RISE (ASHRAE S92, 31.6 TABLE 2) 500.00
Dt/100 FT 0.70
Dt 0.70

Da - AVAILABLE DRAFT
Da (FROM MANUFACTURER OF EQUIPMENT) -

B - BAROMETRIC PRESSURE
ALTITUDE, FT -
B 29.92

k - SYSTEM RESISTANCE
COMPONENT QTY k EACH k
INLET
GAS VENT WITH DRAFT HOOD 1 1.50 1.50
BAROMETRIC REGULATOR - 0.50 -
DIRECT CONNECTION - - -
ROUND ELBOW, 90 DEGREE - 0.75 -
ROUND ELBOW, 45 DEGREE- - 0.30 -
TEE OR 90 DEGREE CONNECTOR - 1.25 -
Y CONNECTOR - 0.75 -
CAP, TOP -
OPEN, STRAIGHT - - -
LOW RESISTANCE 1 0.50 0.50
OTHER - - -
SPARK SCREEN 1 0.50 0.50
PIPING (0.04x(L, FT/di, IN)) 100 0.02 1.67

k TOTAL 4.17

Tm (ASHRAE S92, 31.7 TABLE 4) 820.00

DATE: 12/21/2020 PAGE 2 OF 4


CONSULTING ENGINEERING SERVICES, INC.
811 MIDDLE STREET, MIDDLETOWN, CONNECTICUT 06457
PHONE: 860-632-1682 FACSIMILE: 860-632-1768

di, IN 22.06

DATE: 12/21/2020 PAGE 3 OF 4


CONSULTING ENGINEERING SERVICES, INC.
811 MIDDLE STREET, MIDDLETOWN, CONNECTICUT 06457
PHONE: 860-632-1682 FACSIMILE: 860-632-1768

BAROMETRI
VENT GAS Dt PER 100 C
TEMP. RISE, FT, IN OF ALTITUDE, PRESSURE
DEG F WATER FT B, IN HG
100 0.2 - 29.92
150 0.3 2,000.00 27.82
200 0.4 4,000.00 25.82
300 0.5 6,000.00 23.98
400 0.6 8,000.00 22.22
500 0.7 10,000.00 20.58
600 0.8
800 0.9
1,100 1.0
1,600 1.1
2,400 1.2

DATE: 12/21/2020 PAGE 4 OF 4