OVER CURRENT RELAY CALCULATION

11/0.415 KV 2.5 MVA TRANSFORMER


FULL LAOD CURRENT FORMULA I = KVA RATING/1.732 * RATING VOLTAGE
FAULT CURRENT PRIMARY FARMULA IF = FULL LOAD CURRENT / PERCENTAGE IMPEDENC
PERCENTAGE IMPEDENCE 8%
HV SIDE VOLTAGE IN KV 132000 HV CT RATIO 200/5
LV SIDE VOLTAGE IN KV 11500 LV CT RATIO 1600/5
KVA/MVA RATING 26000000
ROOT 3 1.732
HV CURRENT 113.723844
LV CURRENT 1305.35194

FAULT CURRENT PRIMARY 16316.8993

IDMT INVERSE DEFINIT MINIMUM TIME RELAY


X-TICS INVERSE
2 SETTING
1 PLUG SETTING SAY 120% OF MAX / FULL LOAD FAULT CURRENT SECONDARY = FAULT CURRENT P
PLUG SETTING PHASE TO GROUND IS 20% OF PHASE PLUG SETTING

PLUG SETTING Ø -Ø 4.079225


PLUG SETTING Ø - G 0.815845
FAULT CURRENT SECONDARY 50.99031

2 PSM/M.O.P.S PSM/M.O.P.S FORMULA = FAULT CURRENT SECONDARY / PLUG SETTING


PSM/M.O.P.S Ø -Ø = 12.5
PSM/M.O.P.S Ø - G
STANDARD INVERSE TIME FORMULA = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S
ASSUME T.D.S = 0.1
TIME OF OPERATING = ?
TIME OF OPERATING = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S
TIME OF OPERATING = 0.051812 0.014 0.2702066769
TIME OF OPERATING = 0.027021
ASSUME T.D.S =0.1
T.O. OPERATING = ?
T.O. OPERATING = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S
T.O. OPERATING = 0.14 0.051812
0.039174
ING VOLTAGE
ERCENTAGE IMPEDENCE

FAULT CURRENT PRIMARY/LV SIDE CT RATIO

T.D.S TIME DIAL SETTING

0.073168 0.19134

3.573768
0.013959 10.02903 1.002903