The document provides calculations to determine relay settings for a 11/0.415kV transformer. It calculates the full load current, fault current, and plug and time delay settings for the relay. The key calculations are:
1) The full load current is determined based on the transformer KVA rating and voltages.
2) The fault current is calculated as the full load current divided by the percentage impedance.
3) The plug settings are determined as percentages of the fault current after applying CT ratios.
4) The time delay settings are calculated using an inverse time formula based on the plug settings and a time dial setting.
The document provides calculations to determine relay settings for a 11/0.415kV transformer. It calculates the full load current, fault current, and plug and time delay settings for the relay. The key calculations are:
1) The full load current is determined based on the transformer KVA rating and voltages.
2) The fault current is calculated as the full load current divided by the percentage impedance.
3) The plug settings are determined as percentages of the fault current after applying CT ratios.
4) The time delay settings are calculated using an inverse time formula based on the plug settings and a time dial setting.
The document provides calculations to determine relay settings for a 11/0.415kV transformer. It calculates the full load current, fault current, and plug and time delay settings for the relay. The key calculations are:
1) The full load current is determined based on the transformer KVA rating and voltages.
2) The fault current is calculated as the full load current divided by the percentage impedance.
3) The plug settings are determined as percentages of the fault current after applying CT ratios.
4) The time delay settings are calculated using an inverse time formula based on the plug settings and a time dial setting.
FULL LAOD CURRENT FORMULA I = KVA RATING/1.732 * RATING VOLTAGE FAULT CURRENT PRIMARY FARMULA IF = FULL LOAD CURRENT / PERCENTAGE IMPEDENC PERCENTAGE IMPEDENCE 8% HV SIDE VOLTAGE IN KV 132000 HV CT RATIO 200/5 LV SIDE VOLTAGE IN KV 11500 LV CT RATIO 1600/5 KVA/MVA RATING 26000000 ROOT 3 1.732 HV CURRENT 113.723844 LV CURRENT 1305.35194
FAULT CURRENT PRIMARY 16316.8993
IDMT INVERSE DEFINIT MINIMUM TIME RELAY
X-TICS INVERSE 2 SETTING 1 PLUG SETTING SAY 120% OF MAX / FULL LOAD FAULT CURRENT SECONDARY = FAULT CURRENT P PLUG SETTING PHASE TO GROUND IS 20% OF PHASE PLUG SETTING
PLUG SETTING Ø -Ø 4.079225
PLUG SETTING Ø - G 0.815845 FAULT CURRENT SECONDARY 50.99031
2 PSM/M.O.P.S PSM/M.O.P.S FORMULA = FAULT CURRENT SECONDARY / PLUG SETTING
PSM/M.O.P.S Ø -Ø = 12.5 PSM/M.O.P.S Ø - G STANDARD INVERSE TIME FORMULA = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S ASSUME T.D.S = 0.1 TIME OF OPERATING = ? TIME OF OPERATING = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S TIME OF OPERATING = 0.051812 0.014 0.2702066769 TIME OF OPERATING = 0.027021 ASSUME T.D.S =0.1 T.O. OPERATING = ? T.O. OPERATING = T.O.P ={0.14/(M.O.P.S)^0.02-1} * T.D.S T.O. OPERATING = 0.14 0.051812 0.039174 ING VOLTAGE ERCENTAGE IMPEDENCE