Professional Documents
Culture Documents
Data Sheet - Flame Detector: VENTEC Oklahoma
Data Sheet - Flame Detector: VENTEC Oklahoma
7 MM SCFD Syngas
Plant
VENTEC Oklahoma
----------------------------------------------------------------------------------------------------------
Detector Tag No: 200-BE-1011A&B
Flame Detector Model: C7061F2001
Flame Detector Manuf: Honeywell
Flame Det Op Voltage: 120 VAC 60Hz
Flame Det Proc Conn: 1” NPT
Flame Det Housing: Cast Aluminum, FM Approval Flameproof
Self Checking: Yes
Nitrogen Purge: Optional
----------------------------------------------------------------------------------------------------------
Controller Tag Number: 200-BS-1011A&B
Primary Control Model: RM7830A1011
Primary Control Manuf: Honeywell
Prim Cntrl Op Voltage: 120 VAC 60Hz
Safety Switch Timing: 10 seconds
Flame-Out Response Time: 3 seconds
SPDT Alarm Contacts: Mfg Std
Mounting Sub-base Model: Q7800A1005
Ignition Transformer Model: A06-SA6 Prim. Voltage 120V 60Hz
------------------------------------------------------------------------------------------------------------
Options/Accessories
1. Stainless Steel Tag:
Attach stainless steel tag to detector housing, stamped with full tag number.
2. Vendor to provide Swivel Mounting Assemby for Detector: p/n: 118367A
Notes
Note 1: Include flame amplifier R7861A1026 and Timer p/n: ST7800A1005
Note 2: Include Honeywell Keyboard Display Module, Mod. No: S7800A1142
With 5 pin connector.
Note 3: Complete system to be set for 120V 60Hz power supply prior to shipping.
----------------------------------------------------------------------------------------------------------
Rev Description By Date Checked By Approved By
1 Issued for PO MP 05/28/15 DCW SLP