I - Environmental Conditions: Gas Engine Generator Set Data Sheet Kampung Baru Gas Plant Upgrading Project

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GAS ENGINE GENERATOR SET DATA SHEET

KAMPUNG BARU GAS PLANT UPGRADING PROJECT

I . ENVIRONMENTAL CONDITIONS
1 Location : Outdoor Sheltered Tropical
2 Ambient air temp. : Min : 21 °C Max : 33° C
3 Humidity : 76.5 - 81.5 % Altitude : < 100 m
4 Hazardous area classification : Non Hazardous
5 System Voltage : 415V ± 10%
6 System Frequency : 50Hz ± 5 %
7 Neutral Earthing : Solidly Earthed

II . GENERATOR DATA
1 Applicable Code And Standard - IEC 60034
2 Manufacturer - AML
3 Type and Model Number - STA
4 Rated Voltage V AC 415
5 Rated Frequency Hz 50
6 Number of Phase No. 3 Phase
7 Power Factor ( Lag / Lead ) - 0.8 Lag
8 Max Continuous rating at S1 duty kVA 562.5
9 Stator Connection - Star
10 Neutral Earthing Method - Resistance Grounded
11 Phase Rotation - A-B-C
12 System Max. Fault Current ( 3-ph-sym) kA 63 kA for 1 sec
13 Rotation facing drive end - STA
14 Insulation Class - F
15 Temperature rise - B
16 Speed / No. of Poles rpm# STA/STA
17 First Critical / Synch speed rpm STA
18 X/R Ratio - STA
19 Overload Capability : - Single
30 second % 150
1 hour % 110
20 Unbalanced load capability - STA
21 Voltage / Frequency variations to IEC 60034.1 - Zone 'B'
22 Generator efficiency :
Full load % STA
75 % load % STA
50 % load % STA
23 Type of excitation - Self (PMG) brushless rotating rectifier
24 Telephone Harmonic Factor (THF ) % 5
25 Suitable for Paralell operation with the system Yes/No Yes
26 Winding temperature detectors ( No. & Type ) - 9 ea PT100 RTD's (3/Phase )
27 Bearing temperature detectors - RTD PT100 min 2/bear
28 Max noise level at no load dB (A) 85 dB (A) at 1 m
29 Space heater for :
Generator kW STA
Control Panel kW STA
Voltage V AC 120
30 Pole Pitch Pitch 2/3
31 Direct axis reactances :
Synchronous (Xd) - Sat & Unsat % STA
Transient (X'd) % STA (typ <= 16 )
Subtransient (X"d) % STA (typ >= 12.5 )
32 Positive sequence resistance (R1) % STA
33 Negative sequence resistance (R2) % STA
34 Negative sequence reactance (X2) - Sat & Unsat % STA
35 Zero sequence resistance (R0) % STA
36 Zero sequence reactance (X0) % STA
37 Short Circuit ratio ( X/R ) % STA
38 Quadrature Axis Reactance :
Synchronous (Xq) - Sat & Unsat % STA
Transient (X'q) % STA
Subtransient (X"q) % STA
39 Direct Axis Open Circuit Time Constants :
Transient (T'do) % STA
Subtransient (T"do) % STA
40 Direct Axis Short Circuit Time Constants :
Transient (T'ds) % STA
Subtransient (T"ds) % STA
41 Quadrature Axis Open Circuit Time Constants :
Transient (T'qo) % STA
Subtransient (T"qo) % STA
42 Quadrature Axis Short Circuit Time Constants :
Transient (T'qs) % STA
Subtransient (T"qs) % STA

III. PHYSICAL CHARACTERISTIC (EXCL. DRIVER)


1 Package dimension (L X W X H ) mm STA
2 Package weight kg STA
3 Mounting - Horizontal foot mounted
4 Enclosure
5 Generator Enclosure IP Rating - IP 56
6 Package Enclosure IP Rating - Acoustic Enclosure IP 24
7 Generator Cooling Method - IC4A1A1 - TEFC Totally Enclosed Fan Cooled
8 Air Discharge ( Top or Bottom ) - STA
9 Air Filters - STA
10 Bearing type (DE & NDE ) - Sleeve type
11 Lubrication - Oil Lubrication
12 Terminal Box
IP Rating - IP 56
Size and arrangement - STA
13 Rotor mement inertia (GD²) kg m² STA
14 Motor inertia constant (H) - STA
15 Max cable size and no. of cores / phase
Main mm² STA
Heater mm² STA
Aux mm² STA

IV. EXCITATION SYSTEM


1 Manufacturer - AML
2 Permanent magnet pilot generator (PMG) type Yes / No Yes
3 Brushless rotating rectifier type Yes / No Yes
4 Voltage rating (% of axciter ceiling voltage ) % typ 250
5 Current capacity (% of nominal) % typ >= 200
6 Diode bridge element failure detection Yes / No Yes
7 Rated Current A STA
8 Rated Voltage V STA
9 Input Current A STA
10 Input Voltage V STA
11 Hermetically sealed - STA

V. AUTOMATIC VOLTAGE REGULATOR ( AVR ) SYSTEM


1 Manufacturer - AML
2 Type - STA
3 IEC 60034-16-12 model type - STA
4 Solid State regulator Yes / No Yes
5 Excitation Limitation :
Max Excitation limits V STA
Max volts/hertz limits V/Hz STA
6 Output voltage set point adjusment - STA
7 Voltage regulation under following load conditions :
100 % load rejection % STA
50 % Load acceptance, initial load 0 % % STA
50 % load acceptance, intial load 50% % STA
8 Under frequency protection Yes / No Yes
9 Over voltage protection Yes / No Yes
10 Voltage regulation under transient conditions % STA
11 Overfluxing control on auto and manual mode Yes / No Yes
12 Main and Manual AVR Yes / No Yes
13 Functional without external power supply Yes / No Yes
14 Differential protection Yes / No Yes

VI. AUTOMATIC VOLTAGE REGULATOR (AVR ) MODEL PARAMETER


1 Forward gain constant at VAR (KA) - STA
2 AVR Amplifier time constant (TA) - STA
3 Feedback gain of AVR (KF) - STA
4 AVR feedback time constant (TF1) - STA
5 AVR feedback time constant (TF2) - STA

VII. FILTER LOAD COMPENSATOR MODEL PARAMETERS


1 Filter time constant (Tc) - STA
2 Compensation gain constant (Rc) - STA
3 Compensation gain constant (Xc) - STA

VIII. EXCITER MODEL PARAMETERS


1 Excitation time constant (TE) - STA
2 Exciter Saturation (SE)
@ 75% UE max - STA
@ 100% UE max - STA
3 Excitation gain constant (KE) - STA
4 Maximum exciter voltage (UE max ) - STA
5 Minimum exciter voltage (UE min ) - STA
6 Minimum regulator output (VR min ) - STA

IX. CONVERNOR
1 Droop & Isochronous speed control Yes/No Yes
2 Frequency deviation for following load conditions :
100% load rejection % STA
50% load acceptance, initial load 0% % STA
50% load acceptance, initial load 50% % STA
3 Full load rejection with no overspeed trip Yes/No Yes
4 Frequency Range for steady state conditions % +/-1

X. SYNCHRONIZING CONTROL
1 Manufacturer - AML
2 Type - STA
3 Auto / Manual synchronizing unit Yes/No Yes
4 Check Synchronizing relay Yes/No Yes

XI. STARTING SYSTEM


1 Type of starting - Electric System (DC Motor )
2 Battery
Manufacture - STA
Cell type - Sealed lead acid ( maintenance free)
Number of cell - STA
Nominal voltage V DC 24
AH Capacity - STA
List of accessories - STA
3 Battery Charger - Yes, located in control panel

XII. TEST REQUIREMENTS


1 Type test Yes / No Yes
2 Performance test Yes / No Yes
3 Routine test Yes / No Yes
4 Special test - STA
5 Load test Yes / No Yes
6 Functional test Yes / No Yes
XIII. UNIT CONTROL PANEL
1 Fuel pressure gauge Yes / No Yes
2 Air intake manifold temperature gauge Yes / No Yes
3 Fuel filter differential pressure gauge Yes / No Yes
4 Lubricating oil pressure and temperature gauge Yes / No Yes
5 Tachometer Yes / No Yes
6 Water temperature gauge Yes / No Yes
7 Differential pressure gauge for each air filter Yes / No Yes
8 Oil Filter differrential pressure gauge Yes / No Yes
9 Start / stop push button Yes / No Yes
10 Fuel level gauge Yes / No Yes

XIV. ACCESSORIES
1 Anti-condensation heater Yes / No Yes
2 Anti-condensation heater power kW STA
3 Anti-condensation heater voltage V AC 120
4 Anti-condensation heater frequency Hz 50
5 Frame earth - External earthing boss
6 Surge arrestors - STA if required
7 Neutral Earthing Resistor - Yes

You might also like