Est Zeeshan HEAT LOAD ESTIMATE

Dtd 30-Apr-20 At 4pm


Job HVACR Society Est SUMMER Peak
Add. Karachi 24.9 Deg N Latitude
Space Office DB WB RH GR/LB
Size 0.0 0.00 5120 SQFT 10.0 FT HT. 51200 O.A. 99 74 21 88
Item Area Gain Factor Btu/Hr. Room 75 55 70
SOLAR GAIN - GLASS Diff 24 18
N glass 144 Sqftx 23 x 1.00 3312 VENTILATION
E glass 192 Sqftx 12 x 1.00 2304 5120 0.06 cfm/sft 307
S glass 144 Sqftx 12 x 1.00 1728 40 people 5 cfm 200
W glass 192 Sqftx 163 x 0.56 17526 0 Doorsx 0 cfm 0
SW glass 0 Sqftx 85 x 0.56 0 0 Crack 0
SE glass 0 Sqftx 12 x 0.56 0 0 Exhaust(excess) 0
NW glass 0 Sqftx 138 x 0.56 0 CFM VENTILATION 507
NE glass 0 Sqftx 12 x 0.56 0 S.H.F.AND ADP
HOR glass 0 Sqftx 0 x 0.00 0 193075 RSH
0 GAIN-WALLS/ROOF 219723 RTH 0.88 SHF
N Wall 576 Sqftx 13 x 0.35 2621 INDICATE . 53 oF
E Wall 768 Sqftx 27 x 0.35 7258 SELECTED ADP 54 oF
S Wall 576 Sqftx 25 x 0.35 5040 DEHUMIDIFIED AIR
W Wall 768 Sqftx 21 x 0.35 5645 0.88 21 = 18.5
SW Wall 0 Sqftx 31 x 0.35 0 193075 RSH
SE Wall 0 Sqftx 26 x 0.35 0 1.08 18.5 = 9674 CFM
NW Wall 0 Sqftx 17 x 0.35 0
NE Wall 0 Sqftx 19 x 0.35 0
R-sun 0 Sqftx 0 x 0.35 0 CHECK FIGURES
Roof Sun R-sh. 5120 Sqftx 44 x 0.12 27034 TONS 18.31
TRANS. GAIN CFM 9674
All glass 672 Sqftx 24 x 1.13 18225 ADP 54.0
Partition 0 Sqftx 19 x 0.45 0 CFMTON 528.33
Ceiling 0 Sqftx 15 x 0.12 0 CFM/SFT 1.9
Floor 5120 Sqftx 24 x 0.40 49152 400 CFM/TON 24.185
INFIL.& OUTSIDE SQ FT/TR 279.6
Inf. cfmx 24 oF x 1.08 0
O.A. 507 24 oFx 0.12 BFx 1.08 1578
INTERNAL HEAT
Occ. 40 People x 245 9800
Equipment Load 200 Watts x 20 3.40 13600
Light 0.30 Watts x 5120 3.4 5238
Appl. ( PC's) 2 230 3.40 1564

Sub total 171623


HEAT FAN SAFETY
GAIN% 0.0 HP% 7.5 FACT 5.0 21453
ROOM SENSIBLE HEAT 193075
Inf. 0 cfmx 18 Gr/lb 1.00 x 0.68 0
O.A. 507 cfmx 18 Gr/lbx 0.12 BFx 0.68 745
Occ. 40 People 205 8200
Steam 0.00 lb/hr x 1080 0
Sub total 8945
LEAK 0 SAFETY 0 0
LOSS% 0.0 FACT% 7.5 671
ROOM LATENT HEAT 9616
ROOM TOTAL HEAT 202691
S.H. 507 cfmx 24 oFx 0.88 x 1.08 11569
L.H. 507 cfmx 18 G/lb 0.88 x 0.68 5463
OUTSIDE AIR HEAT 17032
Grand Total Heat Sub-Total 219723
HEAT H.P. CHW
GAIN% 0.0 PUMP% 0.0 PPg% 0.0 0
TONS 18.31 GRAND TOTAL HEAT 219723
`