Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/261396533

Simultaneous measurement of partial discharge using TEV, IEC60270 and


UHF techniques

Conference Paper  in  Electrical Insulation, 1988., Conference Record of the 1988 IEEE International Symposium on · June 2012
DOI: 10.1109/ELINSL.2012.6251506

CITATIONS READS

25 1,123

3 authors, including:

Alistair Reid Martin David Judd


Cardiff University University of Strathclyde
68 PUBLICATIONS   609 CITATIONS    208 PUBLICATIONS   3,900 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Risk assesment of EHV GIS by means of Online PD measurements View project

Scalable Non-invasive Radiometric Wireless Sensor Network for Partial Discharge Monitoring in the Future Smart Grid View project

All content following this page was uploaded by Alistair Reid on 04 March 2015.

The user has requested enhancement of the downloaded file.


Simultaneous Measurement of Partial Discharge
Using TEV, IEC60270 and UHF Techniques

Alistair J. Reid Martin D. Judd and Graeme Duncan


School of Engineering and Built Environment Institute for Energy and Environment
Glasgow Caledonian University University of Strathclyde
Glasgow, UK Glasgow, UK
alistair.reid@gcu.ac.uk m.judd@eee.strath.ac.uk

Abstract—This paper explores a means of quantifying the Quantifying the transient earth voltage output in terms of
relationship between transient earth voltage (TEV), ultra-high- partial discharge severity can be challenging since there is no
frequency (UHF) and IEC60270 partial discharge (PD) widely accepted standard. It is the purpose of this study to
measurements on a pulse-by-pulse basis for well-defined, investigate the relationship between apparent charge, UHF
laboratory-based discharge sources. Since each technique energy and Transient Earth Voltage. The benefits of TEV
responds differently to the same PD event, there is no theoretical measurement derive from the ability to install sensors non-
relationship between the measured quantities; TEV and UHF intrusively on in-service equipment. Since PD magnitude is
techniques respond to the rate of change of charge movement, conventionally well understood in terms of apparent charge, it
while IEC60270 responds to its integral. Empirical measurement
is desirable to quantify the IEC/TEV relationship for a better
is therefore necessary. Discharge pulses for each system were
captured simultaneously using a 3 GHz, 20 GS/s digital sampling
understanding of PD severity in MV switchgear. For
oscilloscope. PD amplitudes recorded by the respective systems completeness, UHF data was measured simultaneously along
were analysed and their relationships evaluated. Although these with TEV and IEC.
relationships are complex and bear characteristics particular to
the PD geometry, the order-of-magnitude variation in amplitude II. EXPERIMENTAL PROCEDURE
between the sources allows approximate linear interpolation of
the relationships when pulses are plotted on a logarithmic scale. Figs. 1 and 2 show the laboratory-based setup, in which an
The TEV/IEC correlation approximated to 1 μV/pC. The enclosed metal chamber was used, together with PD test cells
TEV/UHF correlation approximated to 0.05 mV/mV (TEV/UHF). with well-defined topologies and discharge characteristics. A
Using TEV data measured at various points at an on-line proprietary TEV sensor was used. A Lemke LDS-6 IEC60270
medium voltage substation, approximate corresponding pC levels system was used to quantify apparent charge. The system was
have been estimated based on the above relationships. The calibrated when connected to each respective test object by
implications for PD severity judgment are discussed. injecting current pulses of known charge, as specified in the
IEC60270 standard. The hardware-integrated output pulse
Keywords-Partial discharges; Condition monitoring; UHF;
from the Lemke system, the peak of which is proportional to
TEV; Switchgear.
the apparent charge, was connected directly to a 3 GHz Lecroy
7300 Oscilloscope (top trace, Fig. 3) along with the TEV and
I. INTRODUCTION UHF signals. A UHF monopole antenna was installed
Partial discharge (PD) measurement is a well established internally (Fig. 2). The output voltage from the UHF sensor
condition monitoring technique used to detect incipient failures was also connected directly to the oscilloscope. Although the
within electrical insulation systems. A number of detection test chamber is shown with the front face removed in Fig. 2, it
techniques have been applied over the years to measure the was bolted in place for the duration of each test. The TEV
many effects of PD. PD measurement according to IEC sensor was placed on top of the test chamber and its output
standard 60270 [1] is a well established technique, in which PD connected to the oscilloscope. Fig. 3 shows three traces
is quantified in terms of ‘apparent charge’. The authors have captured simultaneously. All three traces arise from the same
previously carried out investigations examining the correlation PD event. Since PD signal propagation to the UHF and TEV
between IEC measurement and the increasingly used UHF sensors is essentially at the speed of light, both signals arrive
technique [2–4]. Recently, the transient earth voltage
around the same time. The measured IEC60270 trace arrives
phenomenon has been more widely exploited for condition
approximately 500 ns later due to circuit delay and other
monitoring and asset management of MV switchgear [5–10].
Transient earth voltage sensors make use of the skin effect to propagation effects in the measurement system.
measure electromagnetic radiation due to internal partial Four PD test cells were used, representing four common
discharge. This is an attractive sensing option since PD source topologies:
measurements are inherently safe and can be made without any 1. A floating electrode in SF6
physical intrusion or modification to the switchgear. 2. A point-plane configuration in SF6
3. A free metallic particle in SF6 Integrated IEC apparent

150
mV
4. A free metallic particle in oil (L10B) charge output

Although SF6 and oil are not common insulation media in UHF

300
mV
the equipment of interest in this study, these test cells were
used to provide a wide dynamic range in PD levels, allowing TEV

mV
6
greater confidence in the reported correlations.
2 μs
PD test Interlocked
chamber test cage Figure 3. Oscilloscope screenshot showing simultaneously captured
IEC60270, UHF and TEV traces from a single PD event.
Voltage
Due to the large variation in output voltage levels it was
supply necessary to apply attenuation or amplification to the
Lemke LDS-6
respective measurements for some test configurations. For
example, due to high amplitude discharges produced by the
Oscilloscope floating electrode, it was necessary to apply a 10 dB attenuator
to the UHF channel. Since TEV measurements have
comparatively low sensitivity, a 25 dB amplifier was needed
when measuring discharge from the point-plane and free
particle test cells.
All measurements were correlated in post-processing using
specially developed MATLAB code to produce the graphs
shown in the following section. The software reads the peak of
the measured waveform (approximately 6000 waveforms for
Figure 1. Experimental setup. From left to right: 3 GHz oscilloscope each test configuration) and correlates this into a 3-column
capturing TEV, IEC and UHF pulses simultaneously, Lemke LDS-6 ‘apparent array of data. At this point any attenuation or amplification was
charge’ measurement system (calibration device can be see on top of the unit),
Voltage supply. The test envlodure is located inside the interlocked HV test corrected through scaling to arrive at the actual output voltage
cage. for each sensor. The relationship between output voltage and
pC level for the IEC measurements was also calibrated for each
HV configuration and factored into the calculation.
TEV
supply The frequency response of the TEV sensor was measured
sensor
using a pulsed GTEM cell [11]. The sensor has a mean
effective height between 0.1 and 0.2 mm in the 200 MHz - 2
GHz range. This is considered low in terms of UHF sensitivity
UHF
(normally > 6 mm mean effective height). The TEV sensor is
monopole likely to have higher sensitivity at frequencies below the
calibration system’s lower limit of 200 MHz.

III. RESULTS

A. Laboratory Measurements
Figs. 4 and 5 show the TEV/IEC and TEV/UHF
PD test Coupling relationships respectively for all four test cells. TEV/IEC
cell capacitor results for the individual defects follow a non-linear trend,
characteristic to each PD source. However, when all data is
plotted on the same graph (Fig. 4) the approximate gradient of
Figure 2. Experimental setup. PD test cell is located within the aluminium the best-fit straight line is 1μV/pC. Since both UHF and TEV
test chamber and connected to voltage supply through an HV bushing at the techniques respond to the rate of change of charge, they exhibit
top. TEV sensor is located on top of the chamber and a UHF monopole sensor
is mounted internally. The front plate of the chamber was re-fitted during a more linear relationship, as shown in Fig. 5, with the best-fit
testing. straight line voltage ratio approximating to 0.05 mV/mV
(TEV/UHF). This correlation has been included for
completeness. Although the UHF measurement appears more
sensitive by a factor of almost 20, it must be noted that the
monopole sensor was mounted internally, while the TEV
sensor was mounted on the outside of the chamber. Clearly a
trade off exists between ease of installation and sensitivity for
the two sensor technologies.
Floating electrode in SF6

Free particle
in SF6

Free particle
in oil

Point-plane in SF6

Figure 4. Correlation between apparent charge and TEV output voltage for
four partial discharge sources

Floating electrode in SF6

Free particle
in SF6 Figure 6. Results of on-site TEV measurement for PD location at varoius
points on a MV substation. The approximate location of the fault is evidenced
Free particle by high measured dBmV levels around the Bus Section.
in oil
Re-arranging Eqn. 1, the TEV output voltage can be
defined, in this case, as:

Vout [mV] = 10(dBmV/20) x 1 (2)


Point-plane in SF6
Using the previously measured approximate relationship
between TEV and IEC of 1μV/pC (or 1x10-3 mV/pC), and
defining this constant as A, an approximation for the apparent
charge levels in the substation may be computed as follows
Figure 5. Correlation between UHF output voltage and TEV output voltage (using units of mV and pC):
for four partial discharge sources.
q [pC] = 10(dBmV/20) x A-1 (3)
B. On-Site Measurements
= 10(dBmV/20) x 103
In November 2009, a site survey was conducted at a
medium voltage substation having a suspected defect after
previous PD monitoring was carried out approximately a year From the above equation, an approximate dBmV level of 15
beforehand. TEV measurements were taken to establish dB measured on switchgear units 1-6 corresponds to an
whether PD was still present and to determine if the condition apparent charge level of around 5,600 pC. Using the same
had worsened. The measurement device used expresses approximation, 40 dB measured close to the source of the
readings in dBmV. The definition of a dBmV is: discharge at the bus section corresponds to an apparent charge
of around 100,000 pC.

dBmV = 20 log10 (Vout / Vref) (1) IV. DISCUSSION


It must be noted that the reported relationships are only
approximate. Since the TEV and IEC techniques respond
where Vout is the TEV sensor output voltage in mV. By differently to the same PD event it is clear on examination of
definition, dBmV uses a reference voltage of Vref = 1 mV. A the results that the relationship is not always linear. However,
plan of the substation along with sensor positions and TEV the assumption of an approximate linear relationship is helpful
dBmV levels at these positions is depicted in Fig. 6. when considering a wide range of measurements. In
establishing these relationships, the idealised laboratory test
setup was necessary to minimise any attenuation and
dispersion effects of each measurement system. These effects ACKNOWLEDGMENT
are evident on examination of the on-site measurements. For This work was funded through the EPSRC Supergen V, UK
example, the TEV dBmV level is greatly attenuated by the Energy Infrastructure (AMPerES) grant in collaboration with
shielding effects of the enclosures as the distance from the PD UK electricity network operators working under Ofgem's
source increases. The TEV mV level closest to the PD site Innovation Funding Incentive scheme; - full details on
should therefore be used when approximating the www.supergen-amperes.org
corresponding apparent charge.
Conventional IEC measurement techniques only REFERENCES
approximate the PD quantity – hence ‘apparent’ charge. The [1] IEC International Standard 60270. High Voltage Test Techniques -
use of TEV or UHF measurements to judge PD severity is Partial Discharge Measurements. International Electrotechnical
Commission (IEC), Geneva, Switzerland, 3rd edition, 2000.
equally valid, but since more experience has been gained in
[2] A. J. Reid, M. D. Judd, B. G. Stewart, and R. A. Fouracre. Frequency
the application of conventional techniques, the apparent distribution of RF energy from PD sources and its application in
charge level has become the internationally accepted quantity combined RF and IEC60270 measurements. In IEEE Conference on
for the assessment of PD magnitude and severity. It is hoped Electrical Insulation and Dielectric Phenomena, Kansas City, MO, USA,
that this initial study will go some way in assisting in the October 2006.
diagnosis of PD severity based on measurements on MV [3] A. J. Reid, M. D. Judd, R. A. Fouracre, and D. M. Hepburn.
Simultaneous measurement of partial discharges using IEC60270 and
switchgear using the more convenient TEV method. radio frequency techniques. IEEE Transaction on Dielectrics and
Electrical Insulation, Vol. 18, No. 2, pp. 444-445, April 2011.
V. CONCLUSIONS [4] A . J. Reid, M. D. Judd, R. A. Fouracre, and D. M. Hepburn.
Partial discharge has been measured simultaneously on a Identifcation of simultaneously active partial discharge sources using
combined RF and IEC60270 measurement. IET Science, Measurement
pulse-by-pulse basis using conventional IEC60270, UHF and and Technology, Vol. 5, No. 3, pp. 102-108, May 2011.
TEV methods in a laboratory-based test chamber using a
[5] James E. Smith, Gabe Paoletti, and Igor Blokhintsev. Hot-spot hunting:
number of well-defined PD sources. Since the TEV and IEC Experience with on-line partial discharge analysis as a tool for predictive
techniques respond differently to the same PD event, the maintenance for medium-voltage switchgear systems. IEEE Industry
measured relationship between the two quantities is not only Applications magazine, pp. 41–47, Sep-Oct 2004.
dependent on the charge but on the dynamics of charge [6] N. Davies and D. Jones. Testing distribution switchgear for partial
transfer. This gives rise to characteristic patterns when the discharge in the laboratory and the field. In Proc. IEEE International
pulse magnitudes for a particular PD source are plotted against Symposium on Electrical Insulation, pp. 716–719, Vancouver, Canada,
June 2008.
each other on the same graph. Although these correlations vary
[7] Z. Berler, A. Golubev I. Blokhintsev, G. Paoletti, V. Rashkes, and A.
between PD sources, an approximately linear relationship can Romashkov. Practical experience in on-line partial discharge
be estimated when all measured PD data is considered. A more measurements of MV switchgear systems. In Proc. IEEE International
linear relationship exists between TEV and UHF since both Symposium on Electrical Insulation, pp. 382–385, Anaheim, CA, USA,
techniques respond to the dynamics of charge motion. The April 2–5 2000.
gradient of the best-fit straight line in each case was 1μV/pC [8] Darren Jones. The costs and benefits of condition monitoring in
substations. In Proc. PES Transmission and Distribution Conference and
(TEV/IEC) and 0.05 mV/mV (TEV/UHF). Exposition, pp. 1–7, Chicago, USA, 21-24 April 2008.
Based on these correlations, TEV data was examined for [9] C. Kane, I. Blokhintsev, and A. Golubev. Measurement and analysis of
on-site measurements on a MV switchgear enclosure. The PD partial discharge in switchgear. In Proc. Electrical Insulation Conference
and Electrical Manufacturing Expo, pp. 203–210, Indianapolis, USA,
source was pinpointed to the Bus Section and the apparent Oct 2005.
charge quantity approximated to 100,000 pC in the region of
[10] A. Golubev, I. Blokhintsev, G. Paoletti, and J. Modrowski. On-line
the defect based on the measured TEV dBmV levels and the partial discharge applications to mv electrical switchgear. In Proc.
reported TEV/IEC correlation. Electrical Insulation Conference and Electrical Manufacturing and Coil
Winding Conference, pp. 225–232, Cincinnati, Ohio, USA, Oct 2001.
[11] M. Judd and O. Farish. A pulsed GTEM system for UHF sensor
calibration. IEEE Transactions on Instrumentation and Measurement,
Vol. 47, No. 4, pp. 875–880, August 1998.

View publication stats

You might also like