Identification
Manufacturers ID (63) Foxboro Eckardt
Device Type ID (6) SRD960 Device Subtype (129) SRD960
Tag Name OWNER TAG NAME Model Code BHQD......
Tag Date 21/03/2001 Valve S/N VALVE SER NUM
Calibration Date 21/12/2020 14:10:03 Actuator S/N ACT SERIAL NUM
Fabrication No. 95/015309 ECEP number ECEP-NR
Device ID 341899
Hardware / Firmware
Firmware Revision 18 Write Protect (0) No
Hardware Revision 2 Amplifier Type (1) Single
Device Options Input/Output
Messages
Message #1 MESSAGE 1 Message #2 MESSAGE 2
Message #3 MESSAGE 3 Maintenance Info MESSAGE 4
Calibration Info MESSAGE 5
Page 2/8 © Copyright 2009 - 2020 Foxboro Eckardt GmbH
Mounting Configuration
Mounting Compensation (7) Rotary/Clockwise Spring Type (2) Open
Actuator Type (1) Single Valve Type (1) Globe
Control Action (0) Direct Acting
Readback Select (1) Working Position Accessories (0) None
Setpoint
Setpoint Source (3) Analog Analog Setpoint Hi 20.00 mA
Analog Setpoint Lo 4.00 mA
Characterization
Flow Characteristic (0) Linear
100
80
60
Y (%)
40
20
0
0 20 40 60 80 100
X (%)
Control Parameters
P Term (Dec.) 88.50 P Term (Inc) 80.00
I Term (Dec) 50.00 I Term (Inc) 80.00
Inc. Ramping 0.20 sec Control Gap 0.40 %
Dec. Ramping 0.20 sec
Setpoint Damping (0) Filter T63 Booster Tunning 0.02
Travel Configuration
Lower Travel Stop 0.00 % Cutoff 0% 2.00 %
Upper Travel Stop 100.00 % Cutoff 100% 98.00 %
Cutoff Hyst. 0.005 %
Input/Output Configuration
Binary Output 1 Namur (<1mA / >=2.2mA) | Output active->HIGH Current | LoLo Alarm |
Position Alarms
High Alarm 110.00 % Low Alarm -10.00 %
High High Alarm 110.00 % Low Low Alarm -10.00 %
Alarm Deadband 1.00 %
Load Factor
Load factor 0.00 Spring range start 1.20 bar
Load factor lower limit -500.00 % Spring range end 2.00 bar
Load factor upper limit 1000.00 % Spring range unit (7) bar
Pressures Temperature
Air Supply Pressure 0.00 bar Internal Temperature 33 °C
Supply Press. Units (7) bar Temperature Units (32) °C
Output 1 Pressure 0.00 bar
Output 1 Pressure Units (7) bar
Output 2 Pressure 0.00 bar
Output 2 Pressure Units (7) bar
Service Management
Actual time in operation 528 hours Time since last service 551 hours
Service reminder after 100000 hours
Process
Process Status
Mode: ONLINE
Process Diagnostic
RAM: PASS
EEPROM: PASS
ROM: PASS
AD Converter: PASS
Actuator Out of Range: PASS
Current Loop I/P Motor: PASS
Potentiometer: PASS
Option Board: PASS
Max/Min Temperature
Min. electronic temperature 22 °C Temp. Lower Limit -40 °C
Max. electronic temperature 38 °C Temp Upper Limit 80 °C
Temperature Units (32) °C
Air Supply
Maximum Air Supply 0.00 bar
Position Histograms
Position History (1 to 15 minutes) Position History (1 to 24 hours)
Duration in Actuator Position [%]
80 80
60 60
40 40
20 15 20
1 3 1 0 3 0 1 0 1 0 0 0 0 0 0 0 0 0 0
0 0
0-10 10-20 20-30 30-40 40-50 50-60 60-70 70-80 80-90 90-100 0-10 10-20 20-30 30-40 40-50 50-60 60-70 70-80 80-90 90-100
Position Area [%] Position Area [%]
80 80
60 60
51
40 40
20
20 20
0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0
0 0
0-10 10-20 20-30 30-40 40-50 50-60 60-70 70-80 80-90 90-100 0-10 10-20 20-30 30-40 40-50 50-60 60-70 70-80 80-90 90-100
Position Area [%] Position Area [%]
Page 7/8 © Copyright 2009 - 2020 Foxboro Eckardt GmbH
60 60
40 40
22
20 20
0 2 0 1 0 0 0 0 0
0 0
Offline Steady Transient Offset Unstable Offline Steady Transient Offset Unstable
Response Status Response Status
60 54 60
40 40
20 18 20
0 0 2 0 0 0 0 0
0 0
Offline Steady Transient Offset Unstable Offline Steady Transient Offset Unstable
Response Status Response Status