PROJECT : LOCATION: C-STORE

DB NO : DB-C3 A

FED FROM:SMDB-C

CONNECTED LOADS POINTS LOAD PER CIRCUIT


CCT ECC
MCB
RATING OF RATING SL CIR WIRE WIRE WATT /
RTG ROOM / AREA R Y B REMARKS
INCOMER OF ELCB No. No. SIZE SIZE EM- EX. 13A CU FCU 15A UNIT
IN A LTG W/H D/W W/M H/D CCU FR ISO
mm² mm² LTG FAN S/O A/C A/C S/O

1 R1 2333
40A, 4P
100mA 2 Y1 32 6.0 ISO. FOR RATIONAL OVEN 1 7,000 2333
40A 4P ISO

ELCB-1
3 B1 2333

4 R2 1000
40A, 4P
100mA 5 Y2 25 6.0 Mary chef 1 3,000 1000
ELCB-2
6 B2 1000

TOTAL 3333 3333 3333 10.00

CONNECTED LOAD = 10.00 KW MAX DEMAND: 9 KW

I.MAX CURRENT 90 AMP INCOMER RATING:

CABLE SIZE: 1x4C: 10mm2 Cu/XLPE/SWA/PVC + 1x1C: 10mm2 Cu,G/Y PVC ECC.