ANNEXURE-2

JUNCTION BOX SCHEDULE -INSTRUMENTATION

INCOMING (BOTTOM ENTRY) OUTGOING (BOTTOM ENTRY)


SIGNAL NO. OF NO. OF
S.No TAG NO. MULTIPAIR CABLE O.D NO. OF CABLE NO. OF CABLE NO. OF JB MOC REMARKS
TYPE CONNECTION STOPPING CABLE CABLE O.D CONNECTION STOPPING
CABLE (in mm) ENTRIES ENTRIES TB'S
PLUGS PLUGS
12 1/2 '' NPT 10 3
1 JB-A -01 ANALOG 10P X 1.0 mm2 25 1 -1/2 '' NPT 2 1 1P X 1.5 mm2 36 DIE CAST ALUMINIUM/FRP
12 1/2 '' NPT 10 4
2 2 12 1/2 '' NPT 3 2
JB-A -02 ANALOG 10P X 1.0 mm 25 1- 1/2 '' NPT 2 1 1P X 1.5 mm 36 DIE CAST ALUMINIUM/FRP
2 12 1/2 '' NPT 9 3
JB-D -01 108 DIE CAST ALUMINIUM/FRP
3 DIGITAL 10P X 1.0 mm2 25 1-1/2 '' NPT 4 1 6P X 1.0 mm2 15 3/4 '' NPT 5 1
JB-D -02 108 DIE CAST ALUMINIUM/FRP
4 DIGITAL 10P X 1.0 mm2 25 1-1/2 '' NPT 4 1 6P X 1.0 mm2 15 3/4 '' NPT 5 1
2 1P X 1.5 mm2 12 1/2 '' NPT 6 1
5 JB-D -03 DIGITAL 10P X 1.0 mm 25 1-1/2 '' NPT 3 1 72 DIE CAST ALUMINIUM/FRP
2P X 1.5 mm2 12 1/2 '' NPT 6 1
1P X 1.5 mm2 12 1/2 '' NPT 6 1
6 JB-D -04 DIGITAL 10P X 1.0 mm2 25 1-1/2 '' NPT 3 1 72 DIE CAST ALUMINIUM/FRP
2P X 1.5 mm2 12 1/2 '' NPT 6 1

NOTES :
1 ALL THE JUNCTION BOXES ARE WALL MOUNTED.
2 JUNCTION BOX SHALL BE COMPLETE WITH THE EARTHING ARRANGEMENT .
3 JB ENCLOSURE SHALL BE IP - 65 WEATHER PROOF
4 20% SPARE TERMINALS SHALL BE PROVIDED (INCLUDED IN NO. OF TBs).
5 TAG PLATE TO BE PROVIDED FOR ALL THE JBs.
6 PAINT SHADE SHALL BE RAL 7035
7 JB SHALL HAVE HINGED & BOLTED COVER ENDLESS NEOPRENE RUBBER GASKET,2.5MM2 SPRING LOADED ANTI LOOSENING & VIBRATION PROOF TERMINALS (PHOENIX MAKE)