Supplement
ACS800-14 Frequency Converter Modules (110 to 1800 kW)
ACS800-14 Drives
Supplement
3AFE68458986 REV C EN
EFFECTIVE: 22.8.2006
Table of contents
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
The ACS800-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Parameter edits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Basic operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mandatory parameter edits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Alternative operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Optional parameter edits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Resulting alternative operation: Start-up sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ACS800-14 frame sizes and power module types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
AC and DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
ACS800-14 scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Charging circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fuses and resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Disconnectors (switch fuses) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Main contactors and breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Busbar/Quick connector kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Frame 1×R7i + 1×R7i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Frame 1×R8i + 1×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Frame 2×R8i + 2×R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table of contents
6
Illustrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Drive circuit diagram (frame 1×R7i + 1×R7i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Drive circuit diagram (frame 1×R8i + 1×R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Drive circuit diagram (frame 2×R8i + 2×R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
Drive circuit diagram (frame 3×R8i + 3×R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Drive circuit diagram (frame 4×R8i + 4×R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Fan on/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Mounting example (frame 1×R7i + 1×R7i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Mounting example (frame 1×R8i + 1×R8i) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
Quick connector kit #68399939 (LCL+ISU1+ISU2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Quick connector kit #68320887 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
DC busbar kit #64806823 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
Quick connector kit #68239435 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
Quick connector kit #68362962 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117
Quick connector kit #68242231 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119
AC busbar kit #68320909 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
Door fan connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Roof fan connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
NLMD-01 LED Monitoring Display wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Connection directly from ADPI Panel Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Connection using Y-splitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
Table of contents
7
Introduction
This manual gives information specific to ACS800-14 frequency converter modules.
The document contains the information that differs from, or adds to, what is stated in
the related manuals listed below.
• Technical Guide No. 3: EMC Compliant Installation and Configuration for a Power
Drive System (3AFE61348280). Contains information for Original Equipment
Manufacturers of AC drive systems on how to ensure compliance with the
requirements of the EMC Directive.
Inquiries
Address any inquiries about the product to the local ABB representative, quoting the
type code and serial number of the unit. If the local ABB representative cannot be
contacted, address inquiries to ABB Oy, AC Drives, PO Box 184, 00381 Helsinki,
Finland.
ADBU Type of optical branching unit for fibre links that use the DDCS protocol.
AGPS Gate driver power supply board. An optional board within inverter modules
used to implement the Prevention of Unexpected Start function.
Frame (size) Relates to the construction type of the component in question. For
example, several drive types with different power ratings may have the
same basic construction, and this term is used in reference to all those
drive types.
With the ACS800-14, the frame size of the drive indicates the quantity and
frame size of the supply modules, plus the quantity and frame size of the
inverter modules, e.g. “2×R8i + 4×R8i”.
To determine the frame size of a drive type, see the ACS800-14 frame
sizes and power module types table on page 19.
Inverter unit An entity containing all inverter modules controlling a motor, together with
their control electronics, and I/O and auxiliary components.
PPCS Power Plate Communication System; a protocol used in the optical fibre
link that controls the output semiconductors of an inverter module.
RDCU Drive control unit. The RDCU is a separate unit consisting of an RMIO
board built in a plastic housing.
RMIO Motor control and I/O board. Contains the principal inputs and outputs of
the drive. The RMIO is contained within the RDCU drive control unit.
The ACS800-14
DC bus
M M
Main
supply
M
Switch
fuse
Charging
circuit
3~
Example circuit diagrams of frame 1×R7i + 1×R7i and 1×R8i + 1×R8i drives are
presented starting on pages 49 and 57 respectively.
Mounting examples for 1×R7i + 1×R7i and 1×R8i + 1×R8i drives are presented
starting on page 100 and 106 respectively.
The ACS800-14
12
The following single-line diagram represents a drive with 2 supply and 2 inverter
modules (Frame 2×R8i + 2×R8i).
DC bus
M M M M
400 VAC
LCL filter
M
Main
supply M
AC fuses
3~
Charging
circuit
The ACS800-14
13
Parameter edits
If only the basic parameter edits are made the VSD will start with a single start input
applied to the INU control card only. Removal of this start signal trips the VSD and
opens the main contactor (or circuit breaker) every time.
To prevent the contactor tripping every time it is recommended to make the basic
and optional parameter / wiring modifications listed later.
Basic operation
INU 95.06 LCU Q Defines the reference value for Set to ‘zero’ to ensure
PW REF the line-side converter reactive the units operates at 1pu
power generation. Line-side powerfactor, i.e no
converter can generate reactive reactive compensation
power to the supply network.
INU 95.07 LCU DC Defines the intermediate circuit Set to ‘600’ when
REF DC voltage reference for the line- operating on a nominal
side converter. 400 V / 3 / 50 supply
INU 16.09 CTRL Defines the source of the control Set to ‘external’.
Board board power supply. This will now mask the
Supply PPCC link fault on the
INU card during
powerup of the system
Parameter edits
14
Alternative operation
ISU 16.15 I/O Starts the converter by the level Set to ‘DI2 LEVEL’
START of digital input DI2. The converter
MODE starts to modulate and the
charging resistors will be
bypassed when the converter
RMIO board is powered, its
digital input DI2 is ON and there
are no faults.
Note the system must be powered down the up to store the above edits
Wiring modifications
The above change requires a start switch to be connected to DI2.
Parameter edits
15
Wiring Example
A single start signal can be used to start the system. The start is connected directly
into the ISU card (DI2) and is interlocked with the ‘main contactor closed’ signal. This
prevents the INU card from receiving a start input (DI1 or Di6) until the main
contactor is healthy and in circuit.
Alternatively a timer can be used to prevent the INU card receiving the start signal
too early.
Failure to prevent the INU from receiving the start input until after the ISU has started
and synchronised to the mains will simply mean the INU card will trip and require re-
setting before the output can be achieved.
Parameter edits
16
Parameter edits
17
Technical data
Ratings
The ratings for the ACS800-14 with 50 Hz and 60 Hz supplies are given below. The
symbols are described below the table.
Nominal No-over- Light- Heavy-duty Heat dis- Noise
Air flow
ratings load use overload use use sipation level
ACS800-14 type
Icont.max Imax Pcont.max I2N PN I2hd Phd
A A kW A kW A kW kW m3/h dBA
Three-phase supply voltage 380 V, 400 V or 415 V
ACS800-14-0140-3 202 293 110 194 90 151 75 6 1300 74
ACS800-14-0170-3 250 363 132 240 132 187 90 7 1300 74
ACS800-14-0210-3 292 400 160 280 160 218 110 8 3160 75
ACS800-14-0260-3 370 506 200 355 200 277 132 10 3160 75
ACS800-14-0320-3 469 642 250 450 250 351 200 13 3160 75
ACS800-14-0390-3 565 773 315 542 315 423 250 16 3160 75
ACS800-14-0490-3 704 963 400 675 355 526 250 22 3160 75
ACS800-14-0640-3 919 1258 500 882 500 688 355 24 6400 77
ACS800-14-0770-3 1111 1521 630 1067 630 831 450 31 6400 77
ACS800-14-0960-3 1379 1888 800 1324 710 1031 560 43 6400 77
ACS800-14-1070-3 1535 2102 900 1474 800 1149 630 46 10240 78
ACS800-14-1370-3 1978 2707 1200 1899 1100 1479 800 63 10240 78
ACS800-14-1810-3 2610 3573 1600 2506 1400 1953 1100 83 12800 78
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS800-14-0170-5 200 291 132 192 132 150 90 6 1300 74
ACS800-14-0210-5 245 356 160 235 160 183 110 8 1300 74
ACS800-14-0260-5 302 347 200 289 200 226 132 9 3160 75
ACS800-14-0320-5 365 457 250 350 215 273 160 11 3160 75
ACS800-14-0400-5 455 530 315 437 315 340 200 14 3160 75
ACS800-14-0460-5 525 660 355 504 355 393 250 16 3160 75
ACS800-14-0510-5 595 648 400 571 400 445 315 18 3160 75
ACS800-14-0580-5 670 972 500 643 450 501 315 22 3160 75
ACS800-14-0780-5 892 1294 630 856 630 667 450 26 6400 77
ACS800-14-0870-5 1005 1458 710 965 630 752 500 32 6400 77
ACS800-14-1140-5 1313 1906 900 1261 900 982 710 43 6400 77
ACS800-14-1330-5 1528 2217 1120 1467 1120 1143 800 46 10240 78
ACS800-14-1640-5 1884 2734 1400 1809 1300 1409 1000 64 10240 78
ACS800-14-2160-5 2486 3608 1800 2387 1700 1860 1300 84 12800 79
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V, or 690 V
ACS800-14-0160-7 132 192 110 127 110 99 90 8 1300 74
ACS800-14-0200-7 150 218 132 144 132 112 90 9 1300 74
ACS800-14-0260-7 201 301 200 193 160 150 132 12 3160 75
ACS800-14-0320-7 279 417 250 268 250 209 200 15 3160 75
ACS800-14-0400-7 335 502 315 322 250 251 200 18 3160 75
ACS800-14-0440-7 382 571 355 367 355 286 270 19 3160 75
ACS800-14-0540-7 447 668 450 429 400 334 315 21 3160 75
ACS800-14-0790-7 659 985 630 632 630 493 450 36 6400 77
ACS800-14-0870-7 729 1091 710 700 710 545 500 35 6400 77
ACS800-14-1050-7 876 1310 900 840 800 655 630 42 6400 77
ACS800-14-1330-7 1112 1663 1120 1067 1120 831 800 54 10240 78
ACS800-14-1510-7 1256 1879 1250 1206 1200 940 900 62 10240 78
ACS800-14-1980-7 1657 2480 1700 1591 1600 1240 1200 82 12800 79
Technical data
18
Symbols
Nominal ratings
Icont.max Continuous RMS output current. No overloadability at 40 °C.
Imax Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed
by drive temperature.
Typical ratings for no-overload use
Pcont.max Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for light-overload use (10% overloadability)
I2N Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes.
PN Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Typical ratings for heavy-duty use (50% overloadability)
I2hd Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes.
Phd Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage
(400, 500 or 690 V).
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3281 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Temperature derating
In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F), the rated output current is decreased
by 1% for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current
given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F), the derating factor is 100% - 1 % · 10 °C =
90% or 0.90. The output current is then 0.90 × I or 0.90 × I . °C
2N cont.max
Altitude derating
At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further
information.
Technical data
19
AC and DC fuses
See page 24.
Technical data
20
Tightening torques
All fixing used in the assembly should be tightened to the correct torque.
The following table is applicable to zinc and chrome plated grade 8.8 screws
(greased or non-greased), used in the electrical connections of the ACS800-14
modules.
M5 3.5 3.5
M6 6 9
M8 17 20
M10 35 40
M12 55 70
Technical data
21
Ordering information
ACS800-14 scope
The minimum ACS800-14 kits include the ABB-specific parts as listed below. The
interconnecting busbars, fuses, ventilation kits, etc. are available as optional ABB
kits or via other manufacturers if an equivalent specification can be offered.
• LCL filter(s)
• IGBT supply module(s) (ISU)
• Inverter module(s) (INU)
• Common mode filter toroids
• Quick connectors
• Two RDCU Drive Control Units (one for ISU, one for INU)
• Control panel mounting platform kit (RPMP-13-ISU).
The client must provide
• Engineering design
• Metalwork
• Fuses
• Connections
• Cooling system
• 24 V DC supply for drive control electronics
• 230 V 50 Hz 1-phase supply for ALCL-1x-x filter fan (if present) and ABB
ventilation fan kits (if present)
• 400 V 50 Hz 3-phase supply for ALCL-2x-x filter fan (if present) and ISU/INU
fans.
Ordering information
22
Charging circuit
The capacitor banks of the power (ISU and INU) modules needs to be charged
during the start-up before connecting the drive to the three-phase line.
The control and wiring of the charging circuit is presented in the circuit diagrams in
the chapter Illustrations. The dimensions of the components are shown in the
ACS800-204 IGBT Supply Units as Modules; Hardware Manual.
Contactors
Charging circuit contactors
230V 115V
ACS800-14 type
Qty Type Data Order code Qty Type Data Order code
400 V
ACS800-14-0140-3
ACS800-14-0170-3
ACS800-14-0210-3
ACS800-14-0260-3
ACS800-14-0320-3
1 A9-30-10-80 230VAC 50/60 Hz 59017608 1 A9-30-10-89 115VAC 50/60 Hz 59016989
ACS800-14-0390-3
ACS800-14-0490-3
ACS800-14-0640-3
ACS800-14-0770-3
ACS800-14-0960-3
ACS800-14-1070-3 1 A16-30-10-80 230VAC 50/60 Hz 59017632 1 A16-30-10-89 115VAC 50/60 Hz 59016997
ACS800-14-1370-3
1 A30-30-10-80 230VAC 50/60 Hz 64114395 1 A30-30-10-89 115VAC 50/60 Hz 64315242
ACS800-14-1810-3
500 V
ACS800-14-0170-5
ACS800-14-0210-5
ACS800-14-0260-5
ACS800-14-0320-5 1 A9-30-10-80 230VAC 50/60 Hz 59017608 1 A9-30-10-89 115VAC 50/60 Hz 59016989
ACS800-14-0400-5
ACS800-14-0460-5
ACS800-14-0510-5
ACS800-14-0580-5
ACS800-14-0780-5 1 A16-30-10-80 230VAC 50/60 Hz 59017632 1 A16-30-10-89 115VAC 50/60 Hz 59016997
ACS800-14-0870-5
ACS800-14-1140-5
ACS800-14-1330-5 1 A30-30-10-80 230VAC 50/60 Hz 64114395 1 A30-30-10-89 115VAC 50/60 Hz 64315242
ACS800-14-1640-5
ACS800-14-2160-5 1 A50-30-11-80 230VAC 50/60 Hz 59015915 1 A50-30-10-89 115VAC 50/60 Hz 59017012
690 V
ACS800-14-0160-7
ACS800-14-0200-7
ACS800-14-0260-7
ACS800-14-0320-7 1 A9-30-10-80 230VAC 50/60 Hz 59017608 1 A9-30-10-89 115VAC 50/60 Hz 59016989
ACS800-14-0400-7
ACS800-14-0440-7
ACS800-14-0540-7
ACS800-14-0790-7
ACS800-14-0870-7 1 A30-30-10-80 230VAC 50/60 Hz 64114395 1 A30-30-10-89 115VAC 50/60 Hz 64315242
ACS800-14-1050-7
ACS800-14-1330-7
1 A40-30-10-80 230VAC 50/60 Hz 59017659 1 A40-30-10-89 115VAC 50/60 Hz 59017675
ACS800-14-1510-7
ACS800-14-1980-7 1 A50-30-11-80 230VAC 50/60 Hz 59015915 1 A50-30-10-89 115VAC 50/60 Hz 59017012
Ordering information
23
Ordering information
24
AC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
AC fuse information
Drive type aR, IEC aR, UL Recognized
Qty In
Bussmann Ferraz Shawmut Order code Bussmann Ferraz Shawmut Order code
400 V
ACS800-14-0140-3 3 315 170M3817 – 68316049 170M3017 – 68446376
ACS800-14-0170-3 3 400 170M5808 – 64683926 170M5008 – 68628032
ACS800-14-0210-3 3 450 170M5809 6.9URD2PV0450 68316031 170M5059 – 68441811
ACS800-14-0260-3 3 630 170M6810 6.9URD3PV0630 68301572 170M6210 – 68327423
ACS800-14-0320-3 3 800 170M8545 6.9URD3PV0800 64786423 170M6212 – 68327415
ACS800-14-0390-3 3 1000 170M6814 6.9URD3PV1000 68301564 170M6214 – 68442044
ACS800-14-0490-3 3 1000 170M6814 6.9URD3PV1000 68301564 170M6214 – 68442044
ACS800-14-0640-3 3 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-0770-3 3 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
ACS800-14-0960-3 3 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
ACS800-14-1070-3 6 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-1370-3 6 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-1810-3 6 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
500 V
ACS800-14-0170-5 3 315 170M3817 – 68316049 170M3017 – 68446376
ACS800-17-0210-5 3 400 170M5808 – 64683926 170M5008 – 68628032
ACS800-14-0260-5 3 450 170M5809 6.9URD2PV0450 68316031 170M5059 – 68441811
ACS800-14-0320-5 3 630 170M6810 6.9URD3PV0630 68301572 170M6210 – 68327423
ACS800-14-0400-5 3 800 170M8545 6.9URD3PV0800 64786423 170M6212 – 68327415
ACS800-14-0460-5 3 1000 170M6814 6.9URD3PV1000 68301564 170M6214 – 68442044
ACS800-14-0510-5 3 1000 170M6814 6.9URD3PV1000 68301564 170M6214 – 68442044
ACS800-14-0580-5 3 1000 170M6814 6.9URD3PV1000 68301564 170M6214 – 68442044
ACS800-14-0780-5 3 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-0870-5 3 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
ACS800-14-1140-5 3 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
ACS800-14-1330-5 6 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-1640-5 6 1600 170M6419 6URD33TTF1600 68393108 170M6419 6URD33TTF1600 68393108
ACS800-14-2160-5 6 2000 170M6421 5.5URD33TTF2000 68244455 170M6421 5.5URD33TTF2000 68244455
690 V
ACS800-14-0160-7 3 250 170M3816 – 10028574 170M3016 – 68628008
ACS800-14-0200-7 3 315 170M3817 – 68316049 170M3017 – 68446376
ACS800-14-0260-7 3 315 170M3817 6.9URD1PV0315 68316049 170M3017 – 68446376
ACS800-14-0320-7 3 450 170M5809 6.9URD2PV0450 68316031 170M5059 – 68441811
ACS800-14-0400-7 3 450 170M5809 6.9URD2PV0450 68316031 170M5059 – 68441811
ACS800-14-0440-7 3 630 170M6810 6.9URD3PV0630 68301572 170M6210 – 68327423
ACS800-14-0540-7 3 630 170M6810 6.9URD3PV0630 68301572 170M6210 – 68327423
ACS800-14-0790-7 3 1000 170M6414 6.9URD32TTF1000 68333296 170M6414 6.9URD32TTF1000 68333296
ACS800-14-0870-7 3 1250 170M6416 – 68244463 170M6416 – 68244463
ACS800-14-1050-7 3 1250 170M6416 – 68244463 170M6416 – 68244463
ACS800-14-1330-7 6 1000 170M6414 6.9URD32TTF1000 68333296 170M6414 6.9URD32TTF1000 68333296
ACS800-14-1510-7 6 1000 170M6414 6.9URD32TTF1000 68333296 170M6414 6.9URD32TTF1000 68333296
ACS800-14-1980-7 6 1250 170M6416 – 68244463 170M6416 – 68244463
PDM-184674-D
Ordering information
25
DC fuses
Notes:
• Larger fuses must not be used.
• Fuses from other manufacturers can be used if they meet the ratings.
• The recommended fuses are for branch circuit protection per NEC as required for
UL approval.
DC fuse information
Drive type IEC UL Recognized
Qty
Bussmann Ferraz Shawmut In Order code Bussmann In Order code
400 V
ACS800-14-0140-3 – – – – – – – –
ACS800-14-0170-3 – – – – – – – –
ACS800-14-0210-3 – – – – – – – –
ACS800-14-0260-3 – – – – – – – –
ACS800-14-0320-3 – – – – – – – –
ACS800-14-0390-3 – – – – – – – –
ACS800-14-0490-3 – – – – – – – –
ACS800-14-0640-3 8 170M8552 6.9URD3PV1000 1000 68301564 170M6215 1000 68327407
ACS800-14-0770-3 8 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-0960-3 8 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-1070-3 12 170M8552 6.9URD3PV1000 1000 68301564 170M6215 1000 68327407
ACS800-14-1370-3 12 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-1810-3 16 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
500 V
ACS800-14-0170-5 – – – – – – – –
ACS800-14-0210-5 – – – – – – – –
ACS800-14-0260-5 – – – – – – – –
ACS800-14-0320-5 – – – – – – – –
ACS800-14-0400-5 – – – – – – – –
ACS800-14-0460-5 – – – – – – – –
ACS800-14-0510-5 – – – – – – – –
ACS800-14-0580-5 – – – – – – – –
ACS800-14-0780-5 8 170M8552 6.9URD3PV1000 1000 68301564 170M6215 1000 68327407
ACS800-14-0870-5 8 170M8552 6.9URD3PV1000 1000 68301564 170M6215 1000 68327407
ACS800-14-1140-5 8 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-1330-5 12 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-1640-5 12 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
ACS800-14-2160-5 16 170M8547 6.9URD33PA1250 1250 64786512 170M6216 1250 68327393
690 V
ACS800-14-0160-7 – – – – – – – –
ACS800-14-0200-7 – – – – – – – –
ACS800-14-0260-7 – – – – – – – –
ACS800-14-0320-7 – – – – – – – –
ACS800-14-0400-7 – – – – – – – –
ACS800-14-0440-7 – – – – – – – –
ACS800-14-0540-7 – – – – – – – –
ACS800-14-0790-7 8 170M8646 12URD73PA0700 700 68316006 170M8636 700 68327458
ACS800-14-0870-7 8 170M8647 11URD73PA0800 800 68265568 170M8637 800 68327440
ACS800-14-1050-7 8 170M8647 11URD73PA0800 800 68265568 170M8637 800 68327440
ACS800-14-1330-7 12 170M8647 11URD73PA0800 800 68265568 170M8637 800 68327440
ACS800-14-1510-7 12 170M8647 11URD73PA0800 800 68265568 170M8637 800 68327440
ACS800-14-1980-7 16 170M8647 11URD73PA0800 800 68265568 170M8637 800 68327440
PDM-184674-D
Ordering information
26
Ordering information
27
Ordering information
28
Contactors are needed for the on-off control of the main AC input power. The
contactor is operated with a three-position switch (off/on/start) located on the cabinet
door.
For more information on the contactors, see the documents available from
http://www.abb.com. Feed the contactor type (e.g. AF210) into the search field.
The air circuit breaker is used for the on-off control of the drive main AC input power
in the high power units where the contactors are not applicable. Typically, the
breaker is operated with a three-position (On/Off/Start) switch located on the cabinet
door. The breaker can be used as the main disconnector (when pulled out). The
main features are:
• rated voltage: 690 VAC
• rated current: 1250…5000 A. See table above.
• rated breaking capacity under short circuit Icu: 75…100 kA. See table above.
• version: withdrawable (disconnects when pulled out)
• busbar orientation: rear horizontal busbars
• number of busbar poles: 3
• dimensions [mm]: H: 461, D:423.5, W: 432
• weight: 104 kg.
For more information on the breaker and the wagon for the breaker, see SACE
Emax Installation, service, and maintenance instructions for low voltage air circuit
breakers (ITSCB 601933/001 it-en 6-99). The document is available from
http://www.abb.com. Untick “Search Web pages (HTML) only” when using the
search function.
Ordering information
29
DC link kit
(ISU to INU)
A more detailed
drawing is
presented on page
103. 1 68654475
The common
mode filter toroids
shown are
included in the
power modules kit.
Ordering information
30
DC link kit
(ISU to INU)
A more detailed
drawing is
presented on page
110. 1 68468604
The common
mode filter toroids
are included in the
basic ACS800-14
kit.
Ordering information
31
Ordering information
32
DC busbars from
fuse bases to DC
terminals of supply
or inverter module.
4 64806823
A more detailed
drawing is
presented on page
115.
Ordering information
33
A more detailed
drawing is
presented on page
117.
Ordering information
34
A more detailed
drawing is
presented on page
117.
AC-busbar set
Ordering information
35
Ordering information
36
Ordering information
37
IP20/21
IP20/21 cabinet ventilation kits
Inlet/Door outlet Inlet/Door outlet Roof outlet (Rittal TS 8
Roof outlet (Generic cubicle)
(Generic cubicle) (Rittal TS 8 cubicle) cubicle)
ACS800-14-…
Width Order Width Order Width Order Width Order
Qty Qty Qty Qty
(mm) code (mm) code (mm) code (mm) code
0140-3 0170-5 0160-7 1* 400 68328128 1* 400 68328110
1* 400 + 600 68260817 1* 400 + 600 68260817
0170-3 0210-5 0200-7 1* 600 68328144 1* 600 68328136
0260-5
0210-3 0260-7 1 400 68239478 1 400 68328110
0320-5
0260-3 0320-7
0400-5
0320-3 0400-7 1 800 68259827 1 800 68328446
0460-5
0390-3 0440-7
0510-5 1 600 68239460 1 600 68328136
0490-3 0540-7
0580-5
0640-3 0780-5 0790-7 1 600 68239460 1 600 68239460 1 600 68328144 1 600 68328136
0770-3 0870-5 0870-7
0960-3 1140-5 1050-7 1 800 68259827 1 400 + 600 68260817 1 800 68328446 1 400 + 600 68328161
1 800 68259827 1 400 + 600 68260817 1 800 68328446 1 400 + 600 68328161
1070-3 1330-5 1330-7
1370-3 1640-5 1510-7 400 + 600 400 + 600
1 600 + 800 68328691 1 68328705 1 600 + 800 68328608 1 68328641
+ 600 + 600
2 600 68239460 2 600 68239460 2 600 68328144 2 600 68328136
1810-3 2160-5 1980-7
2 800 68259827 2 400 + 600 68260817 2 800 68328446 2 400 + 600 68328161
* Roof outlet depends on the assembly: 400 mm for the LCL filter and 600 mm for the ISU/INU modules combined or 600 mm for LCL filter and ISU/INU
modules combined. Inlet is always 400 mm for the LCL filter and 600 mm for the ISU/INU modules combined.
IP42
IP42 cabinet ventilation kits
Inlet/Door outlet Inlet/Door outlet
Door outlet with fan
(Generic cubicle) (Rittal TS 8 cubicle)
ACS800-14-… Roof outlet
Width Order Width Order Width Order
Qty Qty Qty
(mm) code (mm) code (mm) code
0140-3 0170-5 0160-7
1* 400 + 600 68260795 1* 400 + 600 68260795 2 400 68410711
0170-3 0210-5 0200-7
0260-5
0210-3 0260-7 1 400 68239443 400 68410711
0320-5
0260-3 0320-7
0400-5
0320-3 0400-7 1 800 68259797 3
0460-5
0390-3 0440-7
0510-5 1 600 68239451 400 68410711
0490-3 0540-7
0580-5
See IP20/21
0640-3 0780-5 0790-7 1 600 68239451 1 600 68239451
table above
0770-3 0870-5 0870-7 5 400 68410711
0960-3 1140-5 1050-7 1 800 68259797 1 400 + 600 68260795
Note: Separate cabinet for LCL + INU/ISU needed when using door outlet.
Ordering information
38
IP54
IP54 cabinet ventilation kits
Inlet/Door outlet Inlet/Door outlet Roof outlet with fan
Door outlet with fan Roof outlet with fan
(Generic cubicle) (Rittal TS 8 cubicle) (Rittal TS 8 cubicle)
ACS800-14-…
Width Order Width Order Width Order Width Order Width Order
Qty Qty Qty Qty Qty
(mm) code (mm) code (mm) code (mm) code (mm) code
0140-3 0170-5 0160-7 400 + 400 +
1* 68327890 1* 68327890 2 400 68330301 1 600 68327857 1 600 68327857
0170-3 0210-5 0200-7 600 600
0260-5
0210-3 0260-7 1 400 68327806 1 400 68327831
0320-5
0260-3 0320-7
0400-5
0320-3 0400-7 1 800 68328462 3 400 68330301 2 400 68327831
0460-5
0390-3 0440-7
0510-5 1 600 68327822 1 600 68327857
0490-3 0540-7
0580-5
0640-3 0780-5 0790-7 1 600 68327822 1 600 68327822 2 400 68327831 1 600 68327857
0770-3 0870-5 0870-7 400 + 5 400 68330301 400 +
0960-3 1140-5 1050-7 1 800 68328462 1 68327890 1 600 68327857 2 68328519
600 600
400 + 400+
1 800 68328462 1 68327890 2 400 68327831 1 68328519
600 600
1070-3 1330-5 1330-7
400 + 8 400 68330301 600 +
1370-3 1640-5 1510-7 600 + 600 +
1 68328471 1 600 + 68327903 1 68328489 1 600 + 68362881
800 800
600 400
600 +
2 600 68327822 2 600 68327822 4 400 68327831 2 68327857
600
1810-3 2160-5 1980-7 10 400 68330301
400 + 400 +
2 800 68328462 2 68327890 2 600 68327857 2 68328519
600 600
*400 mm for the LCL filter, 600 mm for the ISU/INU modules combined.
Ordering information
39
400 mm wide
cubicle.
Aperture size:
274 × 522 mm
1 pc Grille (metallic) 68239478
(10.8” × 20.55”).
Effective area:
1150 cm2
(180 in2) approx.
600 mm wide
cubicle.
Aperture size:
471 × 522 mm
1 pc Grille (metallic) 68239460
(18.54” × 20.55”).
Effective area:
1920 cm2
IP20 inlet kit,
(295 in2) approx.
unfiltered
800 mm wide
cubicle.
Aperture size:
671 × 522 mm
1 pc Grille (metallic) 68259827
(26.42“ × 20.55”).
Effective area:
2880 cm2
(445 in2) approx.
400 + 600 mm
68239478 + 68239460 68260817
wide cubicles
600 + 800 mm
68239460 + 68259827 68328691
wide cubicles
400 + 2×600 mm
68239478 + 2×68239460 68328705
wide cubicles
Ordering information
40
400 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
274 × 522 mm
airTex G150) 68239443
(10.8” × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
1150 cm2 1 pc Fastener
(180 in2) approx.
600 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
471 × 522 mm
airTex G150) 68239451
(18.54” × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
IP42 inlet kit, 1920 cm2 1 pc Fastener
filtered (295 in2) approx.
800 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
671 × 522 mm
airTex G150) 68259797
(26.42“ × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
2880 cm2 2 pcs Fastener
(445 in2) approx.
400 + 600 mm
68239443 + 68239451 68260795
wide cubicles
600 + 800 mm
68239451 + 68259797 68328560
wide cubicles
400 + 2×600 mm
68239443 + 2×68239451 68328586
wide cubicles
Ordering information
41
400 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
274 × 522 mm
airComp 300-50) 68327806
(10.8” × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
1150 cm2 1 pc Fastener
(180 in2) approx.
600 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
471 × 522 mm
airComp 300-50) 68327822
(18.54” × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
IP54 inlet kit, 1920 cm2 1 pc Fastener
filtered (295 in2) approx.
800 mm wide
1 pc Grille, inner
cubicle.
(metallic)
Aperture size:
1 pc Filter mat (Luftfilter
671 × 522 mm
airComp 300-50) 68328462
(26.42“ × 20.55”).
1 pc Grille, outer
Effective area: (plastic)
2880 cm2 2 pcs Fastener
(445 in2) approx.
400 + 600 mm
68327806 + 68327822 68327890
wide cubicles
600 + 800 mm
68327822 + 68328462 68328471
wide cubicles
400 + 2×600 mm
68327806 + 2×68327822 68327903
wide cubicles
Ordering information
42
1 pc Cooling fan
One power 1 pc Support plate
IP42 door module. 1 pc Grille (inner)
outlet kit with Aperture size: 1 pc Filter mat (Luftfilter 68410711
fan 274 × 440 mm airTex G150)
(10.79” × 17.32”) 1 pc Grille (outer)
1 pc Fastener
1 pc Cooling fan
One power 1 pc Support plate
IP54 door module. 1 pc Grille (inner)
outlet kit with Aperture size: 1 pc Filter mat (Luftfilter 68330301
fan 274 × 440 mm airComp 300-50)
(10.79” × 17.32”) 1 pc Grille (outer)
1 pc Fastener
Ordering information
43
400 mm wide
generic cubicle.
Aperture size: 1 pc Roof plate
314 × 320 mm 2 pcs Side plate (L/R)
68328128
(12.36” × 12.60”). 2 pcs Side plate
Effective area: (Front/Rear)
920 cm2 (140 in2)
approx.
600 mm wide
generic cubicle.
IP21/42 Aperture size: 1 pc Roof plate
generic roof 514 × 350 mm 2 pcs Side plate (L/R)
outlet kit 68328144
(20.24” × 13.78”). 2 pcs Side plate
Effective area: (Front/Rear)
1536 cm2
(240 in2) approx.
800 mm wide
generic cubicle.
Aperture size: 1 pc Roof plate
714 × 320 mm 2 pcs Side plate (L/R)
68328446
(28.11“ × 12.60”). 2 pcs Side plate
Effective area: (Front/Rear)
2304 cm2
(355 in2) approx.
600 + 800 mm
68328144 + 68328446 68328608
wide cubicles
Ordering information
44
400 mm wide
Rittal TS 8
1 pc Roof plate
cubicle.
2 pcs Side plate (L/R)
Aperture size:
2 pcs Side plate
314 × 320 mm 68328110
(Front/Rear)
(12.36” × 12.60”).
2 pcs Support plate
Effective area: (L/R)
920 cm2 (140 in2)
approx.
IP21/42 roof
outlet kit for
Rittal TS 8
cubicles
600 mm wide
Rittal TS 8
1 pc Roof plate
cubicle.
2 pcs Side plate (L/R)
Aperture size:
2 pcs Side plate
514 × 350 mm 68328136
(Front/Rear)
(20.24” × 13.78”).
2 pcs Support plate
Effective area: (L/R)
1536 cm2
(240 in2) approx.
400 + 600 mm
68328110 + 68328136 68328161
wide cubicles
400 + 2×600 mm
68328110 + 2×68328136 68328641
wide cubicles
Ordering information
45
1 pc Support plate
1 pc Bottom plate
1 pc Support frame
400 mm wide
1 pc Cooling fan
cubicle.
1 pc Fan housing
Aperture size: 68327831
2 pcs Grille (inner)
314 × 350 mm
2 pcs Filter mat
(12.36” × 13.78”)
(Luftfilter airTex
G150)
2 pcs Grille (outer)
IP54 roof
outlet kit with
fan
1 pc Support plate
1 pc Bottom plate
1 pc Support frame
600 mm wide
1 pc Cooling fan
cubicle.
1 pc Fan housing
Aperture size: 68327857
2 pcs Grille (inner)
514 × 350 mm
2 pcs Filter mat
(20.24” × 13.78”)
(Luftfilter airTex
G150)
2 pcs Grille (outer)
400 + 600 mm
68327831 + 68327857 68328519
wide cubicles
600 + 800 mm
68327857 + 2×68327831 68328489
wide cubicles
Ordering information
46
See the ACS800 Multidrive Modules Product Reference for information on the
RDCU-02C control unit. See the ACS800 IGBT Supply Control Program Firmware
Manual for information on the supply application program. See the ACS800
Standard Application Program 7.x Firmware Manual for information on the inverter
application program.
The electrical and optical connections of the control units are shown in the example
drive diagram starting on page 66.
Ordering information
47
Other options
See the ACS800 Product Reference for generic equipment for the ACS800 product
family such as I/O options and PC tools.
Ordering information
48
Ordering information
49
Illustrations
Illustrations
50
Illustrations
51
Illustrations
52
Illustrations
53
Illustrations
54
Illustrations
55
Illustrations
56
Illustrations
57
Illustrations
58
Illustrations
59
Illustrations
60
Illustrations
61
Illustrations
62
Illustrations
63
Illustrations
64
Illustrations
65
Illustrations
66
Illustrations
67
Illustrations
68
Illustrations
69
Illustrations
70
Illustrations
71
Illustrations
72
Illustrations
73
Illustrations
74
Illustrations
75
Illustrations
76
Illustrations
77
Illustrations
78
Illustrations
79
Illustrations
80
Illustrations
81
Illustrations
82
Illustrations
83
Illustrations
84
Illustrations
85
Illustrations
86
Illustrations
87
Illustrations
88
Illustrations
89
Illustrations
90
Illustrations
91
Illustrations
92
Illustrations
93
Illustrations
94
Illustrations
95
Note: The cooling fan(s) of the IGBT supply module(s) must be on when power is
applied since the supply unit must modulate when powered.
The fan on/off control is implemented by using relay output RO3 of the inverter unit’s
RDCU control unit (A41) to control additional contactors K20 and K21, which in turn
switch the cooling fans on and off. The following parameter changes must be made
for the on/off control to work:
• Set parameter 14.03 RELAY RO3 OUTPUT to “PARAM 14.18”.
• Set parameter 14.18 RO PTR3 to “+118.003.01”.
Illustrations
96
Illustrations
97
Illustrations
98
Illustrations
99
Illustrations
100
Illustrations
101
Illustrations
102
Illustrations
103
Illustrations
104
Illustrations
105
Illustrations
106
Illustrations
107
Illustrations
108
Illustrations
109
Illustrations
110
Illustrations
111
Illustrations
112
Illustrations
113
Illustrations
114
Illustrations
115
Illustrations
116
Illustrations
117
Illustrations
118
Illustrations
119
Illustrations
120
Illustrations
121
Z2 Z1
U1 U2
U1 Brown
U2 Blue
Z2 Z1 U2 U1 TK TK Z1 Black
Z2 Orange
N L1 PE
RMIO (ISU)
X39
Panel Interface
X3
ADPI-01 RMIO (INU)
X2 X39
X5
Illustrations
122
Panel Interface
RMIO (ISU)
X3 X39
X2 Y-splitter
Illustrations
3AFE68458986 REV C EN
EFFECTIVE: 22.8.2006