Professional Documents
Culture Documents
Senkron Makine Vektor Kontrol
Senkron Makine Vektor Kontrol
Senkron Makine Vektor Kontrol
The machine models, which are discussed in chapter 3, are based on some
parameters that are very seldom supplied by the manufacturer. Typical generator
data, supplied by manufacturer, is presented in Table 1.
The stator base values can be determined by the rated quantities of the machine
as explained in chapter 3.3.1. The term LAD can be calculated and converted to the
equivalent circuit value using equation - 30 in chapter 3. The field to stator mutual
inductance MF is determined from the air gap line on the no-load field current using
VB =BMFiF/2
-0
where iF is the field current that gives the rated voltage in the air gap line. As
explained in chapter 3.3.2, the equal flux linkage method is used for determining
the rotor base quantities. According to that method, the rotor base values can be
approximated by using equation 36 in chapter 3. Canay [ 1] has shown that these
Determination of Parameters of the Model
approximations can introduce errors in the magnitude of the field current. However,
Canay’s parameters have not been used by the most of the power systems
computation program including EMTP [ 2] and FALCON [3], they are not accounted
here.
After defining the stator base values, the rotor base constants, kF, kD, kQ, may be
determined by equations 39 and 40 in chapter 3. Consequently, the base
impedance values of the related circuits can be calculated by equations 40 and 42
in chapter 3.
Determination of the rotor circuit leakage inductances in the d-axis can be made by
using following equivalent circuit. The main assumption for these circuits is that
damping effects are neglected during the transient period. The field winding
leakage inductance is calculated from Figure 1 using
LAD
L’d
F d
D
LAD L’’d
Figure 1 The d-axis equivalent circuits for transient and sub-transient period.
L AD
F
Ld
' ' d
D
L AD F L F Ld ' ' d
-0
The self inductances of the field and the damper windings may be calculated as;
LD = ℓD + LAD LF = ℓF + LAD
-0
The same procedure can be followed for the q-axis quantities using the equivalent
circuit of Figure 2.
Q q
LAQ L’’q
Therefore;
LAQ = Lq - ℓq
-0
-0
A.5 Resistances
Although the manufacturers usually supply the armature resistance, the rotor
resistance needs to be calculated. From the d-axis transient time constant equation
the field winding resistance is determined.
RF = LF/Td0’
-0
From equation 73 in chapter 3, the damper winding resistance can be written as;
LD M R2
/ LF
RD
T "d 0
-0
RQ = LQ/T”q0
-0
In this section the equivalent circuit values from EMTP will be compared against
the procedure described here. The synchronous machine data, which is used for
this calculation, is extracted from the first case of EMTP benchmark DC26. In Table
2, the data is presented.
Rated power
VR 13.8 kV Line to line rated voltage
f 50 Hz Rated frequency
R 0.0014 pu Armature resistance
xl 0.175 pu Leakage reactance
xd 1.85 pu d-axis reactance
xq 1.76 pu q-axis reactance
x’d 0.2575 pu d-axis transient reactance
x’q 1.76 pu q-axis transient reactance
x’’d 0.18 pu d-axis sub-transient reactance
x’’q 0.18 pu q-axis sub-transient reactance
T‘d0 5.75 s d-axis transient open circuit time constant
T‘q0 0 s q-axis transient open circuit time constant
T‘’d0 0.051 s d-axis sub-transient open circuit time constant
T‘’q0 0.383 s q-axis sub-transient open circuit time constant
x0 0.198 pu Zero sequence reactance
p 2 Number of poles
WR2 50 million lb-ft2 Inertia constant
The inertia constant term is given in Imperial units and in a strange form. Generally,
in the USA this term, WR2, has been supplied by the manufacturer instead of the
moment of inertia, J. In addition, the consistent Imperial unit of J is slug feet 2 or
WR2/g where g is the acceleration of gravity (32.17398 feet/s 2).
1 50 14.594 0.3048 6
2
Wk 10 2 50
2 32.17398
1 50 14.594 0.3048 10
2
6
2 50
H 2 32.17398 693 s
150 10 6
213.8 10 3 / 3
kM F 32 73.21 mH
2 50 600
According to definition of equal mutual flux linkage method per unit values of kMF,
kMD, kMQ and MR equal to LAD.
ℓd = ℓq = .70722 mH
Mutual inductances may be equated as;
0.2575 0.175
F 1.675 0.0867 pu
1.85 0.2575
0.0867 472.727 40.985 mH
1.675 0.0867(0.18 0.175)
D 5.323 10 3 pu
1.675 0.0867 (0.0867 1.675)(0.18 0.175)
= 5.323 10 3 472.727 2.516 mH
Let us compare the calculated equivalent circuit values with EMTP results. In the
table, reactance values are presented in the unit of ohms by multiplying with
fundamental frequency.
Described
EMTP results
procedure Explanation
(in ohms)
(in ohms)
LF 261.66 265.12 Self inductance of field windings
kMF 23.0 23.0 Mutual inductance between field and armature
MR 248.79 248.76 Field damper mutual inductance for d axis
Ld 2.35 2.35 Self inductance of the d axis armature winding
kMD 23.0 23.0 Mutual inductance from armature to damper
LD 249.53 249.54 Self inductance of the d axis damper winding
LQ 236.14 236.14 Self inductance of q axis
kMQ 21.77 21.76 Mutual inductance between q-axis to armature
Lq 2.23 2.23 Self inductance of the q axis armature
RF 0.15 0.17 Resistance of the field winding
Ra 0.00177 0.00177 Resistance of the armature
RD 0.81 0.85 Resistance of the d axis damper winding
RQ 1.96 1.96 Resistance of the q axis damper winding
In general, the results are similar results except the self inductance of field winding
LF. IEEE benchmark [4] accepts that 80% of the current associated with the
transient time constant flows in the field winding and another 20% in the damper
winding after a short circuit. Therefore, ignoring the damper winding introduces
errors in the field parameters. To avoid this, account should be taken of the damper
winding during the transient period. The following set of equations is advised for
determining the open circuit transient and sub-transient time constants [Error:
Reference source not found],
LF LD
T 'd 0 T ' ' d 0
RF RD
LF LD M 2
T 'd 0 T ' ' d 0
RF RD
-0
For the short circuit time constant, following relationships between the short and
open circuit time constant can be used
Ld
T ' d 0 T ' 'd 0 T ' d T ' ' d
L ' 'd
Ld L L
T 'd 0 T ' 'd 0 T 'd T ' 'd 1 d d
L'd L'd L' 'd
-0
With the help of these equations one set of constants can be easily converted to
the other set. In addition, the two time constants of the F-branch and D-branch of
Figure 5 in chapter 3 may be written as,
T1 F RF T2 D RD
L AD Ld Ld
T1 T2 T ' d 0 T '' d 0 T ' d T '' d
L AD L AD
L AD Ld L'' d
T1T2 T ' d 0 T ' ' d 0
L AD
-0
L AD T1 T2
F
L AD T2
T 'd 0 T ' 'd 0 T1
L AD Ld L' 'd
L AD T2 T1
D
L AD T1
T 'd 0 T ' 'd 0 T2
L AD Ld L' 'd
-0
Simple Formulae (in ohms) EMTP results (in ohms) Detailed formulae (in ohms)
LF 261.66 265.11 264.29
LD 249.53 249.54 249.54
RF 0.15 0.17 0.17
RD 0.81 0.85 0.80
As seen above results the detailed formulae has been produced closer values
particularly for the field self inductances.
A.7 REFERENCES