Viper Cable Charts and Wiring Diagrams

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

99-97-1962

(V 5.4)

Viper Climate and


Production Computer
Cable Charts and Wiring Diagrams
Cable Charts and Wiring Diagrams

Program Version
The product described in this manual is computer based, and most functions are realised by software.
This manual corresponds to:
• Software Version CPU 5.4
It was released in May, 2006.
Product and Documentation Changes
Big Dutchman reserve the right to change this document and the product herein described without
further notice. In case of doubt, please contact Big Dutchman.
Latest date of change appears from the back page.

NOTE
• All rights reserved. No part of this manual may be reproduced in any manner whatsoever
without the expressed written permission of Big Dutchman in each case.
• Big Dutchman have made reasonable efforts to ensure the accuracy of the information
contained in this manual. Should any mistakes or imprecise information occur in spite of
this, Big Dutchman would appreciate being notified hereof.
• Irrespective of the above, Big Dutchman shall not accept any liability with regard to loss or
damage caused or alleged to be caused by reliance on any information contained herein.
• Copyright 2006 by Big Dutchman

IMPORTANT
NOTES CONCERNING THE ALARM SYSTEM
Where climatic control is used in livestock buildings, breakdowns, malfunctions or faulty settings may
cause substantial damage and financial losses. It is therefore most important to install a separate,
independent alarm system, which monitors the house concurrently with the climate computer.
According to EU-directive No. 91/629/EØF and 91/630/EØF an alarm system must be installed in any
house that is mechanically ventilated.
Please note that the product liability clause of Big Dutchman’s general terms and conditions of sale
and delivery specify that an alarm system must be installed.

In case of misoperation or improper use, ventilation systems can result in production loss
or cause loss of lives among animals.
Big Dutchman recommend that ventilation systems should be mounted, operated and
serviced only by trained staff and that a separate emergency opening unit and an alarm
system be installed as well as maintained and tested at regular intervals, according to Big
Dutchman’s terms and conditions of sale and delivery.

Viper Climate and Production Computer


4 Cable Charts and Wiring Diagrams

1 INTRODUCTION 7

2 CABLE CHARTS - CLIMATE 8


2.1 Basic Cable Charts .................................................................................. 8
2.1.1 System without Emergency Opening .............................................................................. 8
2.1.2 System with MC 278M ON/OFF Emergency Opening ................................................. 8
2.1.3 System with MC 278CT Temperature Controlled Emergency Opening..................... 9
2.1.4 Winch Motors.................................................................................................................. 10
2.1.5 MultiStep® 230 V ............................................................................................................ 11
2.1.6 Fans 400 V ....................................................................................................................... 11
2.1.7 Fans, Heating, Cooling, 24-hour Clock, Auxiliary Sensor and Differential Pressure
Sensor............................................................................................................................... 13
2.1.8 Wiring box, Fans, Heating, Cooling, 24-hour Clock, Auxiliary Sensor and
Differential Pressure Sensor .......................................................................................... 14
2.1.9 Winch Motors.................................................................................................................. 15

3 WIRING DIAGRAMS - CLIMATE 16


3.1 Basic Wiring Diagrams.......................................................................... 16
3.1.1 Connection of Mains Voltage to I/O Module and Internal Fan Speed Controllers .. 16
3.1.2 Connection of Mains Voltage, Temperature Sensors and Alarm............................... 17
3.1.3 Connection of Mains Voltage, Temperature Sensors, Alarm and MC 278M ON/OFF
Emergency Opening ....................................................................................................... 18
3.1.4 Connection of Mains Voltage, Temp. Sensors, Alarm and MC 278CT Temperature
Controlled Emergency Opening .................................................................................... 19
3.1.5 Connection of Tunnel opening Motor ........................................................................... 20

3.2 Connection of Fans ............................................................................... 20


3.2.1 Fan for Internal Fan Speed Controller, 2-wire ............................................................ 20
3.2.2 Fan for Internal Fan Speed Controller, 3-wire ............................................................ 21
3.2.3 Frequency Controlled Fan and ETA Fan..................................................................... 21

3.3 Connection of External Fan Speed Controller .................................... 23


3.3.1 MC 37 External Fan Speed Controller ......................................................................... 23
3.3.2 MC 23U External Fan Speed Controller ...................................................................... 23

3.4 Connection of Winch Motors for Air Intake or System with one Winch
Motor....................................................................................................... 24
3.4.1 CL 75A 24 V Winch Motor for Air Intake ................................................................... 24

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 5

3.4.2 Two CL 75A 24 V Decentralized Winch Motors for Air Intake in one House with
Intake in one Zone .......................................................................................................... 25
3.4.3 Six CL 75A 24 V Decentralized Winch Motors for Air Intake in one House with
Intake in three Zones...................................................................................................... 26
3.4.4 CL 75A 230 V Winch Motor for Air Intake ................................................................. 27
3.4.5 Joventa DAG 2.p1 Winch Motor for Air Intake .......................................................... 28
3.4.6 CL 74B Winch Motor for Air Intake ............................................................................ 29
3.4.7 Joventa DMG 1.1s Winch Motor for Air Intake.......................................................... 29
3.4.8 DA 20 Winch Motor for Air Intake............................................................................... 30
3.4.9 CL 74AV Stepless Winch Motor for Air Intake .......................................................... 31
3.4.10 Two CL 74B Decentralized Winch Motors for Air Intake.......................................... 32

3.5 Connection of Winch Motors for Air Outlet ......................................... 33


3.5.1 CL 74AV Stepless Winch Motor for Air Outlet........................................................... 33
3.5.2 Two Decentralized CL 74AV Stepless Winch Motors for Air Outlet ........................ 34
3.5.3 CL 75A 24 V Winch Motor for Air Outlet ................................................................... 35
3.5.4 CL 75A 230 V Winch Motor for Air Outlet ................................................................. 36
3.5.5 Joventa DAG 2.p1 Winch Motor for Air Outlet .......................................................... 37
3.5.6 CL 74B Winch Motor for Air Outlet ............................................................................ 38
3.5.7 Joventa DMG 1.1s Winch Motor for Air Outlet .......................................................... 38
3.5.8 MultiStep® Air Outlet ..................................................................................................... 39
3.5.9 MultiStep® Gable Fan for Air Outlet............................................................................ 40

3.6 Connection of Heating .......................................................................... 40


3.6.1 0-10 V Analog Heating ................................................................................................... 40
3.6.2 Relay Heating (380 V Electric Heating)........................................................................ 41
3.6.3 Relay Heating (Solenoid Valve) ..................................................................................... 41

3.7 Connection of Sensors ......................................................................... 42


3.7.1 DOL 14 Humidity Sensor............................................................................................... 42
3.7.2 Auxiliary Sensor (e.g. CO2/NH3/Wind Velocity) .......................................................... 42

3.8 Special Connections ............................................................................. 42


3.8.1 Connection of Differential Pressure Sensor ................................................................. 42
3.8.2 Internal Cooling/Humidification/Soaking .................................................................... 43
3.8.3 External Cooling ............................................................................................................. 43
3.8.4 External Cooling, Pad..................................................................................................... 44
3.8.5 Pad Temperature Sensor................................................................................................ 44
3.8.6 Weather Station .............................................................................................................. 45

Viper Climate and Production Computer


6 Cable Charts and Wiring Diagrams

3.9 Connection of Equal Pressure System................................................ 46


3.9.1 Equal Pressure System - MultiStep® ............................................................................. 46
3.9.2 Equal Pressure System - Stepless .................................................................................. 47

4 CABLE CHARTS - PRODUCTION 48


4.1 Basic Cable Charts ................................................................................ 48
4.1.1 24-hour Clock, Feeding System, Light, Water, Silo Weighing, Silo Augers and Cross
Auger (230 V) .................................................................................................................. 48
4.1.2 24-hour Clock, Feeding System, Light, Water, Silo Weighing, Silo Augers and Cross
Auger (400 V) .................................................................................................................. 49
4.1.3 Dimmer, MS 41R Proximity Switch, Water Meter, Poultry Weighers and Tip
Weigher............................................................................................................................ 50

5 WIRING DIAGRAMS - PRODUCTION 51


5.1 Basic Wiring Diagrams.......................................................................... 51
5.1.1 Connection of Silo Augers 230 V ................................................................................... 51
5.1.2 Connection of Silo Augers 400 V ................................................................................... 52
5.1.3 Connection of Switch and Auxiliary Contactor ........................................................... 52
5.1.4 Connection of Silo Weighing Module with max. 1 m CAN Cable .............................. 53
5.1.5 Connection of 2 Input Silo Weighing Module with max. 200 m CAN cable.............. 54
5.1.6 Connection of 4 Input Weighing Module with max. 200 m CAN cable ..................... 56
5.1.7 Connection of DOL 90 Water Meter............................................................................. 58
5.1.8 Connection of Poultry Weigher ..................................................................................... 58
5.1.9 Connection of Sensor in Cross Auger Container ......................................................... 59
5.1.10 Connection of Feed Demand Sensor ............................................................................. 59
5.1.11 Connection of Relays for Light, Water, Feeding System and Cross Auger............... 60
5.1.12 Connection of Sensor in the last Pan............................................................................. 61
5.1.13 Connection of Tip Weigher............................................................................................ 61
5.1.14 Connection of 24-hour Clock ......................................................................................... 62

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 7

1 INTRODUCTION
This document includes a collection of cable charts and wiring diagrams, which are to be used when
installing a Viper Climate and Production computer in any house. The document may therefore
contain sections that are not relevant to the specific house. In case of doubt, contact Big Dutchman
Service or your dealer.
The connection terminals in Viper Climate and Production computer are universal so that various
components can be connected to the individual terminals.
The connection may differ from the showed connection depending on which components are to be
connected. Therefore, the diagrams in this document must be considered examples.
The Viper Climate and Production computer installation menu (Technical/Setup/ Installation)
indicates precisely to which terminals a component must be connected. When the wiring diagrams
read, “See the setup menu Show installation”, it refers to the indications of the computer. See
also Technical Manual.
If a Big Dutchman wiring box has not been bought, it can be replaced by a locally manufactured
wiring box.
The installation must be made by an authorized electrician according to the current national
regulations and EU regulations.

Viper Climate and Production Computer


8 Cable Charts and Wiring Diagrams

2 CABLE CHARTS - CLIMATE


When you want to… lay cables, you must
1) select the basis cable chart out of three, which matches the emergency opening of the system
2) select cables for the remaining components according to the other cable charts

2.1 Basic Cable Charts


2.1.1 System without Emergency Opening
OUTSIDE SERVICE ROOM
Alarm system

DOL 12

HOUSE
Viper

DOL 14

DOL 12

2.1.2 System with MC 278M ON/OFF Emergency Opening


OUTSIDE SERVICE ROOM
Alarm system

DOL 12

HOUSE Viper
MC 278M

DOL 14

DOL 12

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 9

2.1.3 System with MC 278CT Temperature Controlled


Emergency Opening
HOUSE SERVICE ROOM OUTSIDE

Viper
MC 278CT

= Junction box

NB Use min. 1 mm2 armoured installation cables everywhere, however min. 1.5mm2 for CL 75 24 V
R. Do not use any shrink-on sleeves.

Viper Climate and Production Computer


10 Cable Charts and Wiring Diagrams

2.1.4 Winch Motors

CL 74AV stepless

For larger systems, see the cable chart for MultiStep®


CL 74A ON/OFF

Viper
CL 75A 24 V

CL 75A 230 V

DA 20

Joventa
DMG 1.1s

Joventa
DAG 2.p1

CL 74B

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 11

2.1.5 MultiStep® 230 V


The supply voltage for CL 74AV stepless 1 CL 74AV stepless 2
the fans is divided into
several groups
depending on the
number of fans and their
power consumption.
Air outlet 1 Air outlet 2
Wiring box
Viper

2.1.6 Fans 400 V


The supply voltage for the fans is divided Wiring box
into several groups depending on the Viper
number of fans and their power
consumption.

Viper Climate and Production Computer


12 Cable Charts and Wiring Diagrams

2.1.6.1 Fans – one Phase


The supply voltage for the fans is divided into Wiring box
several groups depending on the number of fans Viper
and their power consumption.

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 13

2.1.7 Fans, Heating, Cooling, 24-hour Clock, Auxiliary Sensor


and Differential Pressure Sensor
2-wire Max. 6.8 A

Viper
3-wire
Max. 6.8 A

Maximum 16 A MC 37

MC 23U
Maximum 3 × 10 A

Window emergency air inlet


CL 74B

Analog heating shunt

ON/OFF relay heating

Cooling

External cooling

Electronic differential
pressure sensor

Auxiliary sensor

Viper Climate and Production Computer


14 Cable Charts and Wiring Diagrams

2.1.8 Wiring box, Fans, Heating, Cooling, 24-hour Clock,


Auxiliary Sensor and Differential Pressure Sensor
Wiring box
Viper
Max. 6.8 A

2-wire

Max. 6.8 A

3-wire

Max. 16 A MC 37

MC 23U
Max. 3 × 10 A

Analog External cooling


heating shunt

Electronic
differential Curtain
pressure sensor
Auxiliary sensor

ON/OFF
relay heating

Cooling

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 15

2.1.9 Winch Motors

CL 74AV

CL 74A ON/OFF
Inlet

CL 75A 24 V Viper

Inlet
min. 1.5 mm2
CL 75A 230 V

min. 1.5 mm2

CL 75CT 230 V

Cable dimensions for CL 75


min. 1.5 mm2 depending on length
24 V DC
CL 75CT 230 V 2
Length < 7 m 7 x min. 1.0 mm
2
70 < length < 100 m 7 x min. 1.5 mm
2
100 < length < 165 m 7 x min. 2.5 mm
2
165 < length < 265 m 7 x min. 4.0 mm
2
min. 1.5 mm 230 V
2
All lengths Min. 1.5 mm

Viper Climate and Production Computer


16 Cable Charts and Wiring Diagrams

3 WIRING DIAGRAMS - CLIMATE


3.1 Basic Wiring Diagrams
3.1.1 Connection of Mains Voltage to I/O Module and Internal
Fan Speed Controllers
FAN SPEED CONTROLLER 6.8 A
I/O MODULE
BASIS MODULE
POWER SUPPLY

Test
one-pole switch

Viper

Use rigid wiring cable min. 1.5 mm2.

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 17

3.1.2 Connection of Mains Voltage, Temperature Sensors and


Alarm

Alarm system
Viper

DOL 12
Front2

TEST

one-pole switch

Viper
2
Use rigid wiring cable min. 1.5 mm .

Viper Climate and Production Computer


18 Cable Charts and Wiring Diagrams

3.1.3 Connection of Mains Voltage, Temperature Sensors,


Alarm and MC 278M ON/OFF Emergency Opening
MC 278M ON/OFF EMERGENCY
OPENING

Alarm system
Viper

DOL 12

TEST
one-pole switch

Viper

Use rigid wiring cable min. 1.5 mm2.

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 19

3.1.4 Connection of Mains Voltage, Temp. Sensors, Alarm and


MC 278CT Temperature Controlled Emergency Opening
MC 278CT

Viper

Use rigid wiring cable min. 1.5 mm2.

Viper Climate and Production Computer


20 Cable Charts and Wiring Diagrams

3.1.5 Connection of Tunnel opening Motor

MC 278CT

Only connect one of the CL


75CT motors to the MC 278CT,
and place the motor as close to
the MC 278CT as possible.

3.2 Connection of Fans


3.2.1 Fan for Internal Fan Speed Controller, 2-wire
Viper

Maximum 6.8 A
2-wire

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 21

3.2.2 Fan for Internal Fan Speed Controller, 3-wire


Viper

3-wire
Maximum 6.8 A

3.2.3 Frequency Controlled Fan and ETA Fan


3.2.3.1 CL 74AV Winch Motor, Stepless and Frequency
Controlled/ETA Fan
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

NB In house 2 L1 must be moved to L2 (fixed phase


must be the same as the fan speed controller).
Viper

Air outlet 1
CL 74AV

See Show
installation

Viper Climate and Production Computer


22 Cable Charts and Wiring Diagrams

3.2.3.2 Two CL 74AV Winch Motors, Stepless and Frequency


Controlled/ETA Fans
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

NB In house 2 L1 must be moved to L2 (fixed phase


must be the same as the fan speed controller).

Air outlet 1
CL 74AV

Viper

Air outlet 2
CL 74AV

See Show
installation

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 23

3.3 Connection of External Fan Speed Controller


3.3.1 MC 37 External Fan Speed Controller
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
MC 37
MC 37, 230 V 16A
Viper

3.3.2 MC 23U External Fan Speed Controller


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
MC 23U
MC 23U, 3×400 V + N 10A
MC 23U, 3×400 V + N 13A
Viper

Viper Climate and Production Computer


24 Cable Charts and Wiring Diagrams

3.4 Connection of Winch Motors for Air Intake or System


with one Winch Motor
3.4.1 CL 75A 24 V Winch Motor for Air Intake
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 75A 24 V

Air intake
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 25

3.4.2 Two CL 75A 24 V Decentralized Winch Motors for Air


Intake in one House with Intake in one Zone
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Air intake 1 Air intake 2

Winch motor
CL 75A 24 V
Viper

Viper Climate and Production Computer


26 Cable Charts and Wiring Diagrams

3.4.3 Six CL 75A 24 V Decentralized Winch Motors for Air


Intake in one House with Intake in three Zones
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Air intake 1 Air intake 2


Winch motor
CL 75A 24 V

Air intake 1 Air intake 2


Winch motor
CL 75A 24 V
Viper

Air intake 1 Air intake 2


Winch motor
CL 75A 24 V

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 27

3.4.4 CL 75A 230 V Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 75A 230 V

Air intake
Viper

Viper Climate and Production Computer


28 Cable Charts and Wiring Diagrams

3.4.5 Joventa DAG 2.p1 Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Joventa DAG 2.p1

Air intake
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 29

3.4.6 CL 74B Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 74B

Air intake
Viper

3.4.7 Joventa DMG 1.1s Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Joventa DMG 1.1s

Air intake
Viper

Viper Climate and Production Computer


30 Cable Charts and Wiring Diagrams

3.4.8 DA 20 Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

DA 20
Viper

Air intake

BL = Blue
Br = Brown
S = Black

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 31

3.4.9 CL 74AV Stepless Winch Motor for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

NB In house 2 L1 must be moved to L2 (fixed


phase must be the same as the fan speed
controller).

Air intake
CL 74AV
Viper BASIS MODULE

Viper Climate and Production Computer


32 Cable Charts and Wiring Diagrams

3.4.10 Two CL 74B Decentralized Winch Motors for Air Intake


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 74B CL 74B

Air intake
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 33

3.5 Connection of Winch Motors for Air Outlet


3.5.1 CL 74AV Stepless Winch Motor for Air Outlet
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

NB In house 2 L1 must be moved to L2 (fixed phase must


be the same as the fan speed controller).
Viper

Air outlet 1
CL 74AV

Viper Climate and Production Computer


34 Cable Charts and Wiring Diagrams

3.5.2 Two Decentralized CL 74AV Stepless Winch Motors for


Air Outlet
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

NB In house 2 L1 must be moved to L2 (fixed phase must


be the same as the fan speed controller).

Air outlet 1
CL 74AV
Viper

Air outlet 2
CL 74AV

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 35

3.5.3 CL 75A 24 V Winch Motor for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 75A 24 V

Air outlet 1
Viper

Viper Climate and Production Computer


36 Cable Charts and Wiring Diagrams

3.5.4 CL 75A 230 V Winch Motor for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 75A 230 V

Air outlet 1
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 37

3.5.5 Joventa DAG 2.p1 Winch Motor for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Joventa DAG 2.p1

Air outlet 1
Viper

Viper Climate and Production Computer


38 Cable Charts and Wiring Diagrams

3.5.6 CL 74B Winch Motor for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

CL 74B

Air outlet
Viper

3.5.7 Joventa DMG 1.1s Winch Motor for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Joventa DMG 1-1s

Air outlet 1
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 39

3.5.8 MultiStep® Air Outlet


CL 74AV is called Air outlet 1.
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

Step 8

Step 7

Step 6

Step 5

Step 4

Step 3

Step 2

Step 1

Air outlet 1
CL 74AV

Stepless

Distribute the fans on one, two


or three phases according to
the load.

Viper Climate and Production Computer


40 Cable Charts and Wiring Diagrams

3.5.9 MultiStep® Gable Fan for Air Outlet


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

MultiStep®
Viper

3.6 Connection of Heating


3.6.1 0-10 V Analog Heating
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Analog heating shunt


Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 41

3.6.2 Relay Heating (380 V Electric Heating)


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

3.6.3 Relay Heating (Solenoid Valve)


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

Viper Climate and Production Computer


42 Cable Charts and Wiring Diagrams

3.7 Connection of Sensors


3.7.1 DOL 14 Humidity Sensor
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

BL = Blue
BR = Brown
S = Black
Viper

3.7.2 Auxiliary Sensor (e.g. CO2/NH3/Wind Velocity)


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

3.8 Special Connections


3.8.1 Connection of Differential Pressure Sensor
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Differential pressure sensor


Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 43

3.8.2 Internal Cooling/Humidification/Soaking


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Water from nozzle


Viper

Internal cooling

3.8.3 External Cooling


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Cooled air
Air
Viper

External cooling

Viper Climate and Production Computer


44 Cable Charts and Wiring Diagrams

3.8.4 External Cooling, Pad


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

3.8.5 Pad Temperature Sensor


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

BL = Blue
BR = Brown
S = Black

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 45

3.8.6 Weather Station


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

Wind velocity

Wind direction

Viper Climate and Production Computer


46 Cable Charts and Wiring Diagrams

3.9 Connection of Equal Pressure System


We distinguish between two types of equal pressure systems:
1) MultiStep® air outlet: The swivel shutters are controlled by the MultiStep® principle and open
by turns
2) Stepless air outlets: The swivel shutters are mechanically connected and open equally much

Swivel shutter

CL 74A
Cable

Fan

Recirculation motor

3.9.1 Equal Pressure System - MultiStep®


Recirculation
Mount the recirculation fans in an external fan speed controller MC 37.
This diagram is an example of the typical connection.

MC 37
MC 37. 230 V 16 A
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 47

Air Supply
Mount the fans for air supply in an external fan speed controller MC 37.
This diagram is an example of the typical connection. Connect it to the potentiometer of Air intake 1 .

MC 37
MC 37. 230 V 16 A
Viper

Air Intake
See the above diagrams 3.4.
Air Outlet
Connect the air outlet like an ordinary MultiStep®.

3.9.2 Equal Pressure System - Stepless


Recirculation
Connect the recirculation fans to the internal fan speed controller. See diagram 3.2.1.
Air Intake and Outlet
Mount the fans in both air intake and air outlet in the external fan speed controller MC 37.
This diagram is an example of the typical connection. Connect it to the potentiometer of Air intake 1.

MC 37
MC 37. 230 V 16 A
Viper

Air Intake
See above diagrams 3.4.
Air Outlet
See above diagrams 3.5.

Viper Climate and Production Computer


48 Cable Charts and Wiring Diagrams

4 CABLE CHARTS - PRODUCTION


4.1 Basic Cable Charts
4.1.1 24-hour Clock, Feeding System, Light, Water, Silo
Weighing, Silo Augers and Cross Auger (230 V)
Wiring box
Viper

24-hour clock

Feeding system

Light

Water

Silo weighing

Silo auger

Silo auger

Cross auger

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 49

4.1.2 24-hour Clock, Feeding System, Light, Water, Silo


Weighing, Silo Augers and Cross Auger (400 V)
Wiring box
Viper

Silo weighing

24-hour clock

Feeding system

Light

Water

Silo auger

Silo auger

Cross auger

Viper Climate and Production Computer


50 Cable Charts and Wiring Diagrams

4.1.3 Dimmer, MS 41R Proximity Switch, Water Meter, Poultry


Weighers and Tip Weigher
Viper

Dimmer

MS 41R
proximity
switch

Water meter

Poultry
weighers

Tip weigher

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 51

5 WIRING DIAGRAMS - PRODUCTION


5.1 Basic Wiring Diagrams
5.1.1 Connection of Silo Augers 230 V
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Silo 1

Silo 1 Silo 2

Silo 2

Viper Climate and Production Computer


52 Cable Charts and Wiring Diagrams

5.1.2 Connection of Silo Augers 400 V


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Silo 1

Silo 1 Silo 2

Silo 2

5.1.3 Connection of Switch and Auxiliary Contactor


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Switch and
contactor Viper/Wiring box

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 53

5.1.4 Connection of Silo Weighing Module with max. 1 m CAN


Cable
The silo weighing module has two inputs and each input can be connected with up to eight load
cells/weight bars, e.g. WB1600 or WB6000.
1) Check that the silo is placed max. 30 m from the climate computer. If the distance is longer,
use the installation guide on next page: (200 m CAN cable)
2) Mount a small watertight junction box next to the silo so that all load cell cables can reach it.
(The junction box is not included in the delivery)
3) Mount the silo weighing module next to the climate computer
4) Connect the silo load cell cables in parallel in the junction box
5) Connect the load cell cable shields mutually in the junction box with short connections (max.
20 mm)
6) Connect the junction box with the silo weighing module with max. 30 m shielded four-wire
load cell cable
7) Attach the silo weighing module by means of max. 1 m four-wire shielded cable to the four-
poled terminal strip on the I/O-module or the main module in the climate computer
8) Connect the cable shield under the toggle in the silo weighing module and on the main module
(will not be on the main module until the end of 2005)

Silo weighing module 1 m


Silo weighing module

Weighing module
I/O-module
Viper

WB1600 or WB6000
load cells/weight bars

Load cell shield


termination

Viper Climate and Production Computer


54 Cable Charts and Wiring Diagrams

5.1.5 Connection of 2 Input Silo Weighing Module with max.


200 m CAN cable
The silo weighing module has two inputs and each input can be connected with up to eight load
cells/weight bars, e.g. WB1600 or WB6000.
1) Check that the silo is placed more than. 30 m from the climate computer. If the distance is
shorter, use the installation guide on the previous page: (1 m CAN cable)
2) Mount a small watertight junction box next to the silo so that all load cell cables can reach it.
(The junction box is not included in the delivery)
3) Mount the silo weighing module max. 30 m from the junction box
4) Connect the silo load cell cables in parallel in the junction box
5) Connect the load cell cable shields mutually in the junction box with short connections (max.
20 mm)
6) Connect the junction box with the silo weighing module with max. 30 m shielded four-wire
load cell cable
7) Mount the manufacturer-supplied data network module on the main module. Fasten the screw
firmly and connect the flat cable
8) Attach the silo weighing module by means of max. 200 m two-wire twisted pair with double
shield (Cat. 5 cable twisted pair) to the data network module in the climate computer. Always
use two wires from the same twisted pair to CAN HI and LO. Do not use two wires from
different pairs).
9) Connect the cable shield under the toggle in the silo weighing module and on the data network
module
10) Connect 230/240 V mains voltage to the power module in the silo weighing module

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 55

Silo weighing module 200 m

Weighing
module
Power module
MC 235/236

Data network
Viper

module

WB1600 or WB6000 load


cells/weigt bars

Load cell shield


termination

Viper Climate and Production Computer


56 Cable Charts and Wiring Diagrams

5.1.6 Connection of 4 Input Weighing Module with max. 200 m


CAN cable
The weighing module has four inputs and is designed for silo weighing. Each input can be connected
with up to eight load cells/weight bars, e.g. WB1600 or WB6000.
1) Check that the silo is placed more than 30 m from the climate computer. If the distance is
shorter, use the installation guide on the previous page: (1 m CAN cable)
2) Mount a small watertight junction box next to the silo so that all load cell cables can reach it.
(The junction box is not included in the delivery)
3) Mount the weighing module max. 30 m from the junction box
4) Connect the load cell cables in parallel in the junction box
5) Connect the load cell cable shields mutually in the junction box with short connections (max.
20 mm)
6) Connect the junction box with the silo weighing module with max. 30 m shielded four-wire
load cell cable
7) Mount the manufacturer-supplied data network module on the main module. Fasten the screw
firmly and connect the flat cable
8) Attach the weighing module by means of max. 200 m two-wire twisted pair with double shield
(Cat. 5 cable twisted pair) to the data network module in the climate computer. Always use
two wires from the same twisted pair to CAN HI and LO. Do not use two wires from different
pairs).
9) Connect the cable shield under the toggle in the weighing module and on the data network
module
10) Connect 230/240 V mains voltage to the power module in the weighing module
Two of the weighing module inputs can be used for animal weighing as well.

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 57

Weighing module 200 m

Weighing modulel
Power supply
Data network module
Viper

WB1600 eller WB6000


weigtbars

Loadcell schield
termination

Viper Climate and Production Computer


58 Cable Charts and Wiring Diagrams

5.1.7 Connection of DOL 90 Water Meter


Activate the pull-down resistance. See jumper number in the setup menu Show installation.
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.
Viper

5.1.8 Connection of Poultry Weigher


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Weigher
Poultry 2
weigher

Weigher
1

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 59

5.1.9 Connection of Sensor in Cross Auger Container


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Sensor in cross auger container

MS 41R

5.1.10 Connection of Feed Demand Sensor


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Feed demand sensor

MS 41R

Viper Climate and Production Computer


60 Cable Charts and Wiring Diagrams

5.1.11 Connection of Relays for Light, Water, Feeding System


and Cross Auger
This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Water

Light

Feeding system

Cross auger

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 61

5.1.12 Connection of Sensor in the last Pan


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Wiring box

MS 45R
MS 45R sensor in the last pan
House

Motor relay, thermoswitch

5.1.13 Connection of Tip Weigher


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

Tip weigher pulse


relay

Viper Climate and Production Computer


62 Cable Charts and Wiring Diagrams

5.1.14 Connection of 24-hour Clock


This diagram is an example of the typical connection. This varies, however, depending on the current
setup. For exact connection, see the setup menu of Viper: Show installation.

C
Viper

Viper Climate and Production Computer


Cable Charts and Wiring Diagrams 63

Viper Climate and Production Computer


2006.05.01 • 609181-02 • 9.15 • EN

Big Dutchman International GmbH • Calveslage • Auf der Lage 2 • 49377 Vechta
Tel. 04447/801-0 • Fax 04447/801-237