Professional Documents
Culture Documents
Hvac Design Thumb Rules Anuj Bhatia Air-Conditioning Capacity 1) A Ton of Refrigeration (1TR) Signifies The Ability of Air-Conditioning
Hvac Design Thumb Rules Anuj Bhatia Air-Conditioning Capacity 1) A Ton of Refrigeration (1TR) Signifies The Ability of Air-Conditioning
Anuj Bhatia
AIR-CONDITIONING CAPACITY
3) Each building is different and the design conditions differ greatly between
regions to region. Factors to consider when figuring the sq-ft/ ton ratio
include:
Office Building
Bank (main area) 225 sq. ft. of floor area per ton
Department Store
Application Average Load
Factory (precision manufacturing) 275 sq. ft. of floor area per ton
Specialty & Variety Store 200 sq. ft. of floor area per ton
Air-conditioning requirements are higher (200 to 400 sq-ft/Ton) for hot and
humid regions and lower (150 – 200 sq-ft/Ton) for cooler places.
1. Room air conditioner - Capacity ranges 0.5 to 2 TR per unit, suitable for
an area of not more than 1000 square feet
Air conditioners are sized by cooling capacity in BTU's per hour. To estimate
the optimum capacity for any room, first calculate the size of the area to be
conditioned by multiplying its width times its length, measured in feet. Then
select the cooling capacity needed using the table below, The BTU's associated
with the square footage will give an approximate optimum for the space.
Cooling Capacity (BTU
Room Area Square Feet
range)
Cooling capacities are based on rooms occupied by two people and having
average insulation, number of windows, and sun exposure.
To adapt the table for varying conditions, modify the capacity figures as
follows:
3. Add 600 Btu/hr for each additional person if area is occupied routinely
by more than two people.
30kW furnace =
30 x 50 = 1500CFM
30000/12000= 2.5tons
Note the values vary significantly with the equipment. CFM/kW tends to be
higher with smallest equipment (5-15kW) and lower as equipment becomes
larger.
SELECTION OF CHILLERS
The following is used as a guide for determining the types of liquid chillers
generally used for air conditioning
Typically
Building limited to 1-
Unlimited Unlimited Unlimited
Height to 4-story
buildings
Cooling
Low Low-moderate High High
Control
Moderate-
Maintenance Low Moderate High
high
Moderate-
Installed Cost Low High High
high
Operating
Low-moderate
Costs Moderate-
Moderate (climate Low
(energy and high
dependent)
water)
Medium to
1- to 2-story large facilities Medium to
Typical 1- to 2-story buildings in with limited very large
Applications buildings hot/dry access to facilities and
climates water or campuses
maintenance
kW/ton 12 / EER
EER 12 / (kW/ton)
A gas furnace has 78% AFUE efficiency (heat out delivered / heat in fuel
burned). An air conditioner or heat pump has 10 SEER or EER (Btu/hr/w). The
heating part of a heat pump achieves 6.6 Btu/hr/w heating season HSPF.
47°F db/43°F wb
> 65,000 Btuh and 3.4 COP
Outdoor Air
< 135,000 Btuh
17°F db/15°F wb
(Cooling Capacity) 2.4 COP
Outdoor Air
47°F db/43°F wb
3.3 COP
>135,000 Btuh Outdoor Air
(Cooling Capacity) 17°F db/15°F wb
2.2 COP
Outdoor Air
Grocery 61.0
Restaurant 38.9
Office 7.5
Warehouse 6.1
The values are for 78°F room dry bulb temperature. For 80°F dry bulb
temperature, the total heat remains the same, but the sensible heat value
should be decreased by approximately 8% and the latent heat values increased
accordingly.
These values include inside and outside air films, typical construction, and
effect of framing members.
Heat conductance of building wall: Use 0.088 for R-13 insulated house
wall.
Heat conductance of building floor: Use 0.047 for R-13 insulated house
raised floor.
Heat conductance of building ceiling: Use 0.031 for R30 insulated ceiling
including attic and roof.
Heat conductance of building roof: Use 0.031 for R30 insulated roof
including attic and ceiling.
Heat conductance of window glass: Use 0.65 for dual pane window.
More insulation gives higher resistance. Less insulation gives lower resistance.
These values include inside and outside air films, typical construction, and
effect of framing members.
Heat resistance of building wall: Use 11.3 for R-13 insulated house wall.
Heat resistance of building floor: Use 21.4 for R-13 insulated house
raised floor.
Heat resistance of building ceiling: Use 32.5 for R30 insulated ceiling
including attic and roof.
Heat resistance of building roof: Use 32.5 for R30 insulated roof
including attic and ceiling.
Heat resistance of window glass: Use 1.54 for dual pane window.
SOLAR LOADS
Solar – winter
The contribution of solar heat is ignored for the sizing of winter heating
equipment. It is most likely the greatest need for winter heat will occur at a
time when the sun is not out.
Solar – summer
Estimate 60 Btu/hr. / square foot enters every window on average during the
daylight hours. (Although there are about 450 Btu/hr. per square foot of
sunlight, this amount is not entering every window simultaneously, and there
are many other reasons to calculate with the lower rate. For discussion, see
solar through windows.)
This estimate assumes even distribution of windows around all sides of the
building, some overhangs, some window tinting, and curtains that are left
open. For other or non-average window conditions, a better solar estimate
may be necessary.
VENTILATION RECOMMENDATIONS
(people/1000ft2)
Food and Dining rooms 70 20
Beverage Cafeteria, fast 100 20
Service food
Kitchen 20 15
(cooking)
Reception areas 60 15
Conference 50 20
rooms
Elevators 30 60
Upper floors 20 15
Malls and 70 15
arcades
Smoking 25 25
lounges
Beauty shops 8 20
Hardware 150 25
stores
Auditorium 50 15
Education Classroom 50 15
Music rooms 20 20
Libraries 150 15
Auditoriums 30 30
Conference 120 20
rooms
Assembly 20 15
rooms
Dry cleaning, 10 15
laundry
Gambling 30 15
casinos
Patient rooms 20 20
Laboratories 20 30
Procedure 70 15
rooms
Pharmacies 100 20
Panel Filters
Electric Coils
Finned Tubular
Centrifugal fans are by far the most prevalent type of fan used in the HVAC
industry today. They are usually cheaper than axial fans and simpler in
construction, but generally do not achieve the same efficiency. Centrifugal fans
consist of a rotating wheel, or "impeller," mounted eccentrically inside a round
housing. The impeller is electrically driven by a motor connected via a belt
drive.
BC BI AF FC
BC BI AF FC
Maximum 78 85 90 70
Efficiency (%)
Axial fans consist of a cylindrical housing, with the impeller mounted inside
along the axis of the housing. In an axial fan, the impeller consists of blades
mounted around a central hub similar to those of an airplane propeller.
Typically, axial fans are more efficient than centrifugal fans.
Blades 2 to 8 4 to 8 5 to 20
Maximum 50 75 85
Efficiency (%)
Parameters Propellers Tube Axial Vane axial
speed3 / N2)]3
Fan Size and Tip Speed Flow and power (Q1 / Q2) = (HP1 /
Rotational Speed Air Density is directly HP2) = [(D1 / D2)]2
proportional to
diameter2
Pressure remains P1 = P2
constant
Rotational Speed Fan Size Pressure Speed, flow and (N1 / N2) = (Q1 /
and Air Density power are Q2) =
inversely
Variable Constant Law Equation
Flow remains Q1 = Q2
constant
Tables below provide a general guide for the proper selection of outlets based
on design requirements of CFM per square foot and air changes per hour
(SMACNA 1990).
Flammable No No No Yes
Up to 30 24 22 Up to 8 24 22
inch inch
31 – 60 22 20 9 – 24 22 20
inches inches
61 – 90 20 18 25 – 48 20 18
inches inches
91inches 18 16 49 – 72 18 16
and above inches
Gauge (or gage) sizes are numbers that indicate the thickness of a piece of
sheet metal, with a higher number referring to a thinner sheet. The
equivalent thicknesses differ for each gauge size standard, which were
developed based on the weight of the sheet for a given material. The
Manufacturers' Standard Gage provides the thicknesses for standard steel,
galvanized steel, and stainless steel. The Brown and Sharpe Gage, also known
as the American Wire Gage (AWG), is used for most non-ferrous metals, such
as Aluminium and Brass.
The chart below can be used to determine the equivalent sheet thickness, in
inches or millimetres, for a gauge number from the selected gauge size
standard. The weight per unit area of the sheet can also be seen in pounds
per square foot and kilograms per square meter.
Gaug kg/m
in mm lb/ft² in mm lb/ft² kg/m²
e ²
Gaug kg/m
in mm lb/ft² in mm lb/ft² kg/m²
e ²
DUCT REINFORCEMENT
Static W RS W RS W RS W RS
Pressur
e
18 in. NR
12 in. NR 14 in. NR
8 in. NR 8 in. NR
DUCTWORK AIR CARRYING CAPACITY
1/2" 1.8 GPM 18,000 1.5 Tons 1.5 GPM 15,000 1.3 Tons
BTUH BTUH
3/4" 4 GPM 40,000 3.3 Tons 3.5 GPM 35,000 2.9 Tons
BTUH BTUH
1" 8 GPM 80,000 6.7 Tons 7.5 GPM 75,000 6.3 Tons
BTUH BTUH
3" 130 GPM 1,300,000 108 Tons 130 GPM 1,300,000 108 Tons
BTUH BTUH
4" 270 GPM 2,700,000 225 Tons 260 GPM 2,600,000 217 Tons
BTUH BTUH
CLEANROOM DESIGN
When trying to calculate the additive effect of two sound sources, use the
approximation as below (note that the logarithms cannot be added directly).
2 3 6
3 4.8 9.6
4 6 12
5 7 14
Increase in Sound Increase in Sound
Number of Sources Power Level Pressure Level
( dB) dB
10 10 20
15 11.8 23.6
20 13 26
0 3
1 2.5
2 2
3 2
4 1.5
5 1
6 1
7 1
Sound Power Level Difference
Added Decibel to the Highest
between
Sound Power Level
two Sound Sources
(dB)
(dB)
8 0.5
9 0.5
10 or more 0
Noise Criteria (NC) are the curves based on different dB levels at different
octave bands. Highest curve intercepted is NC level of sound source. See table
below
Occupied Spaces
Area Maximum NC
Conference Rooms NC 35
Corridors NC 40
Lobby NC 40
The above NC levels may be increased for the areas equipped with fan coil
units. The designer shall submit an analysis showing the expected noise
levels for the prior approval of VA.
The systems must be engineered and the use of acoustic sound lining and
sound attenuators should be considered to achieve the design sound levels.
Diesel 137,750/gallon
Kerosene 134,000/gallon
Electricity 3,412/kWh
Propane 91,330/gallon
Kerosene 135,000/gallon
Coal 28,000,000/ton
GLAZING PROPERTIES
“U” Value
Material
(Btu / hr-ft2-°F)
16 mm thick .58
8 mm thick .65
6 mm thick .72
ROOF INSULATION
The U.S. Environmental Protection Agency (EPA) and the U.S. Department of
Energy (DOE) joined forces in establishing the Energy Star Building Label, a
voluntary, performance based, benchmarking and recognition initiative. In
February 1998, DOE published Energy Star target performance levels for
thermal transmittance and solar heat gain factors for windows, doors and
skylights.
SHGC
2 3600 3000
4 1800 1500
6 1200 1000
8 900 750
10 720 600
________________________________________________________________