Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/250737498

System for optimising pump station control — Part II

Article  in  World Pumps · July 2004


DOI: 10.1016/S0262-1762(04)00261-5

CITATIONS READS

16 344

1 author:

Leszek Szychta
University of Science and Technology in Bydgoszcz
25 PUBLICATIONS   86 CITATIONS   

SEE PROFILE

All content following this page was uploaded by Leszek Szychta on 19 October 2017.

The user has requested enhancement of the downloaded file.


feature pump controls

System for optimising pump


station control — Part II
In the second of his two-part article on attaining optimum control of a pump assembly
(World Pumps February 2004), Leszek Szychta, Eng.D determines a control system and
method for pump components. This is based on the criterion for the optimum value of the
pump efficiency.

Power circuit and four-pump set exhibiting the rotational speed n* .(Figure2). Next,
the algorithm of optimum control system is shown in is to assume that any maximum range
optimum control Figure 1. of divergences Dh of momentary
values of the lead pump efficiencies h
We can derive only one rotational During the varying distribution in a from the optimum pump efficiency
speed hopt that corresponds to hopt , water supply network, running a hopt is characteristic for a selected
where optimum efficiency hopt pump that is set at constant head of pump’s head of water. The assumed
occurs (Figure. 2), from set of iso- water H=Huk, and optimum pump variations in the lead pump efficiency
efficiency curves. Water pumping rotational speed nopt is not feasible. Dh produces a range Dn of
processes display a variable head of It is essential to implement a control recommended values of the lead
water h, corresponding to different system where one pump works as the pump’s rotational speed. A PLC
values of optimum efficiency hopt. A lead pump and all the others as controller adjusts the rated value of
change in the head of water h auxiliary pumps. The lead pump frequency of the voltage powering the
requires adjustment of the value of operates at variable rotational speeds motor in order that the pump
the pump rotational speed n in order and initiates the work cycle of any rotational speed n fits within the Dn
to maintain the working point given pump. range of values.
characterised by the optimum pump
efficiency hopt at the optimum speed The range of variations in rotational Figure 3 shows a sample design of a
nopt. The principle of adjusting the speeds Dn of the lead pump, results four-pump set implementing the
pump rotational speed n is defined as from an appropriate algorithm for optimum control system. The freely
the criterion for control, according to controlling the pump head of water programmable controller PLC in the
the pump optimum efficiency hopt. H. According to pump’s set of iso- pump analyses the water supply
Control of a pump assembly, efficiency curves, the key to the system’ parameters, determines the
including the criterion of optimum method for controlling the pump pump’s head of water h, and then the
pump efficiency hopt , requires the head of water H is to obtain a family optimum value of rotational speed
fitting of frequency converters on of dependencies of pump’s relative nopt. In relation to the optimum
each pump motor. A structure of a efficiency hpw as a function of rotational speed nopt the next move

Figure.1. Descending portion of pump efficiency hpw together Figure 2. Relative pump efficiency hpw as a function of
with the approximating trend line ht for 10A25A pump and at rotational speed n*
h=0.8

2 0262 1762/04 © 2004 Elsevier Ltd. All rights reserved WORLD PUMPS June 2004
feature pump controls

MODBUS communication protocol.


Analogue and digital signals are
transmitted via a common
communications bus. The universal
connection using MODBUS protocol
allows for communication with other
peripheries, such as electromagnetic
flowmeters, power counters,
recorders, etc. Within this solution,
transmission through a series
connection ensures recording the
current frequency of the voltage
feeding the motor, rms current and
output voltage from frequency
converter. Moreover, the series
connection transmits signals to set
the pump’s rotational speed,
START/STOP signals, collects and
stores data concerning emergency
operation of the frequency converter
Figure 3. Control system according to the criterion of optimum pump efficiency value. in the PLC controller’s memory. In
case of a temporary defect in the
is to determine the range of shown in Figure 3 is the value of frequency converter, the PLC
variations of the pump’s rotational pressure in the head collector of the controller cancels the error
speed Dn in order to maintain the pump assembly as measured through a automatically. Its memory stores data
assumed divergences of the pump pressure converter. Using the PLC concerning defective work of the
efficiency Dh. controller, the current value of frequency converters.
pressure przecz is compared to set
An auxiliary pump can operate value pzad producing the regulation
during periods of increased water error e. Depending on the error e , Regulator structure
distribution, complementing the appropriate pumps are activated in the controlling
work of lead pump. An auxiliary following the optimum control system for auxiliary
pump operates at constant value of algorithm. Each pump motor is pumps
rotational speed nopt, where powered from the frequency
maximum value of pump efficiency is converter Pcz1¸Pcz4 working as a Controlling a pump set according to
obtained. When water distribution in SLAVE. The frequency of the output the leading pump algorithm assumes
water supply networks is reduced and voltage of the frequency converter is two types of pump operation: lead
the minimum water-discharge of a set by PLC controller, which and auxiliary pumps. The lead pump
pumping assembly exceeds demand functions as the MASTER. works at variable rotational speed.
for water, control should feature the The range of such variations Dn
so-called ‘sleeping’ pump (Figure4). The PLC controller communicates depends on the pump efficiency
with frequency converters through an divergence Dh on the optimum
In practice, pumps may ‘sleep’ at a RS485 series connection using efficiency hopt (Figure2). The
relative water discharge of less than
0.4. Sleeping begins when the head of
water in the head collector reaches
the rated value Hztzad. The pump
assembly re-starts operating when the
head of water Hzt in a water supply
system drops to the minimum value
defined as the waking level Hztbudz .

Application of the optimum control


algorithm.

In automatic systems, the head of


water is replaced by Mpa-rated
pressure. The input parameter for the
block regulating the drive system Figure 4. Pump operating in the ‘sleeping’ mode

WORLD PUMPS June 2004 www.worldpumps.com 3


feature pump controls

K1¸K4 positioned D1¸D4. Auxiliary


pumps work at constant rotational
speed as determined by the optimum
frequency setting fopt. The optimum
frequency fopt is constantly updated
depending on the water supply system
parameters. The key K4 is positioned
at ‘0’, which means that the pump P4
is switched off.

Conclusion
Controlling the operation of lead
Figure 5. Flow diagram implementing the optimum control algorithm. pump allows for maintaining the
constant value of head Hzt, and
approximately the maximum
efficiency of a pump assembly hg.
However, the method of control
under discussion leaves little room for
changing the amount of pumped
water, which is achieved only by
varying the rotational speed of the
lead pump. The range of rotational
speed variations of the lead pump Dn
is narrow due to a limited range of
efficiencies Dh. For a pump assembly
to match water demand in a water
supply system, the assembly has to be
frequently in ‘sleep’ mode.

In the process of pumping water,


Figure 6. The control flow diagram as per the lead pump algorithm.
variable pump’s head of water H
auxiliary pump(s) is activated at motor of lead pump frzecz. PI2 occurs occasionally. Taking
times when there is an increased regulator sets the value of frequency advantage of control, as per the
water demand. One or more auxiliary of voltage feeding the motor of pump optimum efficiency criterion, it is
pumps work at constant rotational fzad. The signal setting the frequency possible to set the pump’s rotational
speed values, where they reach fzad is subject to delay in the filter F, speed in such a way that its efficiency
optimum efficiency hopt. The and then transmitted to the is maximised for a current pump’s
number of auxiliary pumps depends frequency converter, setting the head of water H. This method of
on demand for water in the water frequency of voltage feeding the control helps to reduce pump
supply network. Assuming operation motor. operating costs. Its start-up and
of two auxiliary pumps, the following checking are smooth, which
configuration of blocks controls the According to Figure6, the pump P3 eliminates water hammers. Pump
operation of the pump set as per the becomes the lead pump with operation according to the diagram
lead pump algorithm (Figure 6). regulated rotational speed. The lead shown in Figure 3 allows for
pump status is determined by the keys ‘sleeping’, ensures uniform pump
Two PI regulators, connected in a K1¸K4 (Figure 6) positioned W1¸W4. operation, eliminates the less-than-
series, control the output head in the Motors of the lead pumps P1¸P4 are optimum cascading operation system
pump set. The regulator PI1 works as supplied with a voltage, the and current overload during pump
a process regulator that compares set frequency of which is f1¸f4 and tends start-up.
pressure pzad with the actual value of towards the value of set frequency
pressure przecz as read by the fzad.
frequency converter. The output of CONTACT
regulator PI1 is the setting for the The flow diagram in Figure 6 Leszek Sychta works in the Unit of
frequency f* of regulator PI2. The f* designates two pumps, P1 and P2, as Machines & Electrical Equipment at the
Faculty of Transport, Technical
setting is compared to the actual auxiliary units. The auxiliary pump University, Radom, Poland.
frequency of voltage feeding the status is determined by the keys leszek@elam.pl

4 www.worldpumps.com WORLD PUMPS June 2004


View publication stats

You might also like