ELTEK SGS PVT. LTD.

FAULT ANALYSIS REPORT OF FIELD FEED BACK COMPLAINT

Date: 30-09-2015
Name of Product and Model No.: P/P(4+1)x100A/PRS5600FP-2

Feedback Case No. :FC-1813-POW-15-16

Feedback reported from: BERHAMPUR-ODISHA

Sl. Fault reported in Complaint Qty. Reason of Fault Steps taken by manufacturer to Remarks
No. avoid recurrence of fault
1. FOUR MODULES OF 04 Due to heavy power fluctuation at We have provided check list for Nil
ELTEK POWER PLANT input mains, the intensity of surge, maintenance of site condition
ARE FAULTY AT CHIKITI developed was beyond the parameters like class B, SPD
EXCH OF BERHAMPUR specified limit of class-B, SPD connections, input voltage and
SSA.  hence rectifier modules gone faulty. proper earthing arrangement.

Prepared By Checked By

Value of store of fault equipment: Rs.

Value of store of related Inspection Certificate: Rs.

Inspection Certificate No. and Date: