PROJECT DRAWING M900, DOMESTIC HOT WATER LAYOUT

Floor Elevation Loads / Expansion Joint Travel / Operating Deflection Size Details / Branch / Equipment
70.9 m Top, Deflection= 3.5 mm (0.1-in) - --------------- Min. distance to first support= 914 mm.
DN50
22 67.4 m

Estimated operating load= -1,050 N (-230 lbs.) DN50


21 64.4 m Estimated max (staged) load= -7,630 N (-1,710 lbs.) xxx Anchor 1, Connected per Structural Eng's instructions
Part No: 3501-131-4, Carbon Steel
~ 63.0 m Estimated design expansion= 49.5 mm (1.9-in) DN50
20 61.5 m Between anchors= 47.2 m (154.9ft) Pressure (including pump)= 291 kPag (42 psig)
19 58.5 m DN50
18 55.6 m DN50
Offset, Min. riser to support= 875 mm (2.9')
DN50
17 52.6 m
Offset, Min. riser to support= 875 mm (2.9')
DN50
16 49.7 m
15 46.7 m DN50
14 43.8 m DN50
13 40.8 m DN50
12 37.9 m DN50
11 34.9 m DN50
10 32.0 m DN50
9 29.0 m DN50
7 23.1 m DN50
6 20.1 m DN50

Estimated operating load= 8,500 N (1,900 lbs.) DN50


5 17.2 m Estimated max (design) load= 13,000 N (2,800 lbs.) xxx Anchor 2, Connected per Structural Eng's instructions
4 14.3 m DN50
3 11.3 m DN50
11.3 m Bottom, Deflection= -3.2 mm (-0.1-in) - --------------- Min. distance to first support= 875 mm.
DN50
2 8.4 m Pressure (including pump)= 805 kPag (115 psig)

PROJECT NAME & RISER MATERIALS: RISER TITLE:

Mineral Wool insulation HOT WATER DUMMY


Carbon steel STD pipe (CS) LEVEL 2 TO LEVEL 22
PROJECT # DATE: RISER CALCULATION No. SHEET REV.
Jul 27, 2020 M900 1 OF 1 0
Using RISERCALC version 1606.59.18.35