PFR PFR PFR: Features

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Power Factor Regulator

PFR140
PFR120
PFR80
PFR60
Features
• Microprocessor based intelligent auto switching
control

• Automatic C/K and rated step adjustment

• Automatic CT polarity correction

• Display of power factor, current & total harmonic


distortion of current

• Programmable sensitivity

• Last step can be used as alarm/fan output

• Under/over voltage alarm, under/over compensate


alarm & high harmonic distortion alarm

• User-friendly setting

• Complies with IEC 61000-6-2 standard

Technical Data
RATINGS AUXILIARY POWER SUPPLY CURRENT INPUT Temperature : -5˚C to +55˚C
Current Supply voltage : 220~240 V AC / Rated current ( In ) :5A Humidity : 56 days at 93% RH and
380~415 V AC Operating Limits : 0.05 A to 6.5 A 40˚C non-condensing
Operating Limits : -15% + 10% Rated Frequency : 50 Hz or 60 Hz
Consumption : 10 VA max
PFR 140 / 120 / 80 / 60

Rated frequency : 50 Hz or 60 Hz MECHANICAL


CONTROL RANGE Mounting : Panel mounting
Power factor setting : 0.8 Ind - 0.8 Cap Dimension (mm) : 144(w) x 144(h) x 90(d)
OUTPUT CONTACTS C/K setting : 0.03 - 1.20 / Automatic Enclosure protection : IP54 at the panel
Numbers of outputs : 6 / 8 / 12 / 14 ( PFR60 Switching sensitivity : 5 - 600 s/step Approximate weight : 1.2 kg
/ PFR80 / PFR120 / Reconnection time for
PFR140 ) same step : 5 - 240 s
Rated voltage : 250 V AC THD threshold : 0.20 - 3.00 ( 20% - 300% ) /
Contact rating : 5A OFF
Expected electrical life : 100,000 operations at Switching Program : Automatic / Automatic
rated current Rotate / 4-quadrant /
Expected mechanical life : 5 x 106 operations Manual
Max current for the Rated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 /
common terminals : 12 A continuous 12 / 16
( Automatic if C/K set to
Auto )

ENVIRONMENTAL CONDITIONS
Power Factor Regulator

Typical Application Diagram

MAIN
N L3 L2 L1
13 13

220~240 V AC
AUX AUX

380~415 V AC
VOLTAGE 1 VOLTAGE
14 14
2

Power Factor Regulator


1
15 2 3 15
16 3 4 16
P1 17 5
CURRENT 4
18 6 For 220~240 V AC Model Only
/5A 5
P2 19 6 7
20 11 7 8
21 12 8 9
22 13 9 10
23 14 10 11
24 12
FUSE

K14 K13 K2 K1

LOAD

Ordering Information Case Dimensions


144 mm

MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
144 mm

PFR80 - 415 - 50 8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC Front


PFR120 - 415 - 50 12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 50 14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 50 6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR80 - 220 - 50 8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC 90 mm
76 mm
PFR120 - 220 - 50 12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR 140 / 120 / 80 / 60

PFR140 - 220 - 50 14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC


PFR60 - 415 - 60 6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
Side
PFR80 - 415 - 60 8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR120 - 415 - 60 12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 60 14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 60 6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
138 mm
PFR80 - 220 - 60 8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR120 - 220 - 60 12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR140 - 220 - 60 14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
138 mm

Panel
Cutout

You might also like