VERIFIED FIRE WATER DEMAND CALCULATION

CLIENT REV. DATE MADE BY CHECKED BY APPROVED BY PAGE


PT PERTAMINA EP A 7-Aug-20 SK/CHM API THP
LOCATION A1 22-Sep-20 SK/CHM API THP
FIRE ZONE-3 B 17-Nov-20 AKN/CHM API THP 6
BERINGIN
0 8-Dec-20 RPP/CHM API THP

FIRE ZONE : Fire Zone-3


LOCATION : Liquid Handling System, Flare System and Foam System
EQUIPMENT : Production Tank A/B (BRA-T-1001 A/B), Test Tank (BRA-T-1002), Production Liquid Transfer pump A/B (BRA-P-
1001 A/B), Test Liquid Transfer Pump (BRA-P-1002), Flare KO Drum (BRA-KOD-5601), Flare KO Drum Pumps
A/B (BRA-P-5601 A/B), KO Drum Sump Pump (BRA-P-5602) and Foam Package (BRA-FA-5403)

1. PRODUCTION TANK

Equipment to be Protected
Equipment Number : BRA-T-1001 A/B
Equipment Name : Production Tank A/B
Tank Diameter : 6.0 m Taken from PID No. 20-01-BRGA-PRO-PID-0021/0022
Tank Height : 9.0 m Taken from PID No. 20-01-BRGA-PRO-PID-0021/0022
Cone Roof Height : 0.62 m
Cone Roof Diagonal : 3.06 m

Protected Area Calculation


2
Area : 70 m Protected tank's shell with height of 3.7 m (API RP 2030)
2
Area : 29 m Protected tank's roof

Minimum Fire Water Requirement


Fire Water Required (10% Hydraulic Contingency) : 83 USgpm For Tank's Shell
Fire Water Required (10% Hydraulic Contingency) : 35 USgpm For Tank's Roof
Total Fire Water Required 118 USgpm

Spray Nozzle Calculation and Actual Fire Water Requirement


Nozzle Type : Protectospray Nozzle (or equal) (Attachment-3)
Orrifice Size : No. 18 (1/4")
K-Factor (as per Vendor Catalog) : 1.8 gpm/psi1/2

Nozzle pressure (as per Vendor Catalog) : 50 psi


Flow Rate per nozzle : 12.7 USgpm
Theoritical Nozzle Quantity : 7 nozzles For Tank's Shell
Theoritical Nozzle Quantity : 3 nozzles For Tank's Roof

Top Head Nozzle


Distance from Nozzle to Object (as per Vendor Catalog) : 0.6 meter
Nozzle angle (as per Vendor Catalog) : 110 degree
Nozzle Coverage Actual (as per Vendor Catalog) : 1.6 meter (b)

No of nozzle in a line : 4 nozzles


Circumference of one ring nozzle : 6.3 meter
Distance between nozzle to nozzle (Horizontal) : 1.57 meter (a)
Ring Quantity : 1

Shell Nozzle With Rundown


Distance from Nozzle to Object (as per Vendor Catalog) : 0.6 meter
Nozzle angle (as per Vendor Catalog) : 110 degree
Nozzle Coverage Actual (as per Vendor Catalog) : 1.6 meter (b)

No of nozzle in a line : 15 nozzles


Circumference of one ring nozzle : 22.6 meter
Distance between nozzle to nozzle (Horizontal) : 1.5 meter (a)
Ring Quantity : 1

Because of distance between nozzles (a) smaller than diameter of coverage area of each nozzle (b)
then nozzles quantity are adequate and horizontal overlap meet.

Actual Nozzle Quantity : 19 Nozzles


Actual Flowrate : 242 USgpm
VERIFIED FIRE WATER DEMAND CALCULATION

CLIENT REV. DATE MADE BY CHECKED BY APPROVED BY PAGE


PT PERTAMINA EP A 7-Aug-20 SK/CHM API THP
LOCATION A1 22-Sep-20 SK/CHM API THP
FIRE ZONE-3 B 17-Nov-20 AKN/CHM API THP 7
BERINGIN
0 8-Dec-20 RPP/CHM API THP

0.6 m 1.6 m

1.5 m
0.8 m

1.5 m
1.6 m

0.6 m

Nozzle Arrangement Side View Nozzle Arrangement Cross View

2. TEST TANK

Equipment to be Protected
Equipment Number : BRA-T-1002
Equipment Name : Test Tank
Tank Diameter : 3.0 m Taken from PID No. 20-01-BRGA-PRO-PID-0023
Tank Height : 7.2 m Taken from PID No. 20-01-BRGA-PRO-PID-0023
Cone Roof Height : 0.31 m
Cone Roof Diagonal : 1.53 m

Protected Area Calculation


2
Area : 35 m Protected tank's shell with height of 3.7 m (API RP 2030)
2
Area : 8 m Protected tank's roof

Minimum Fire Water Requirement


Fire Water Required (10% Hydraulic Contingency) : 42 USgpm For Tank's Shell
Fire Water Required (10% Hydraulic Contingency) : 10 USgpm For Tank's Roof
Total Fire Water Required 52 USgpm

Spray Nozzle Calculation and Actual Fire Water Requirement


Nozzle Type : Protectospray Nozzle (or equal) (Attachment-3)
Orrifice Size : No. 18 (1/4")
K-Factor (as per Vendor Catalog) : 1.8 gpm/psi1/2

Nozzle pressure (as per Vendor Catalog) : 50 psi


Flow Rate per nozzle : 12.7 USgpm
Theoritical Nozzle Quantity : 4 nozzles For Tank's Shell
Theoritical Nozzle Quantity : 1 nozzles For Tank's Roof

Top Head Nozzle


Distance from Nozzle to Object (as per Vendor Catalog) : 0.6 meter
Nozzle angle (as per Vendor Catalog) : 110 degree
Nozzle Coverage Actual (as per Vendor Catalog) : 1.6 meter (b)

No of nozzle in a line : 2 nozzles


Circumference of one ring nozzle : 3.1 meter
Distance between nozzle to nozzle (Horizontal) : 1.57 meter (a)
Ring Quantity : 1

Shell Nozzle With Rundown


Distance from Nozzle to Object (as per Vendor Catalog) : 0.6 meter
Nozzle angle (as per Vendor Catalog) : 110 degree
Nozzle Coverage Actual (as per Vendor Catalog) : 1.6 meter (b)

No of nozzle in a line : 9 nozzles


Circumference of one ring nozzle : 13.2 meter
Distance between nozzle to nozzle (Horizontal) : 1.5 meter (a)
Ring Quantity : 1

Because of distance between nozzles (a) smaller than diameter of coverage area of each nozzle (b)
then nozzles quantity are adequate and horizontal overlap meet.
VERIFIED FIRE WATER DEMAND CALCULATION

CLIENT REV. DATE MADE BY CHECKED BY APPROVED BY PAGE


PT PERTAMINA EP A 7-Aug-20 SK/CHM API THP
LOCATION A1 14-Sep-20 SK/CHM API THP
FIRE ZONE-3
BERINGIN B 17-Nov-20 AKN/CHM API THP 8
0 8-Dec-20 RPP/CHM API THP

Actual Nozzle Quantity : 11 Nozzles


Actual Flowrate : 140 USgpm

0.6 m 1.6 m
1.5 m

0.8 m

1.5 m

1.6 m
0.6 m

Nozzle Arrangement Side View Nozzle Arrangement Cross View

Scenario 1: Inside of Production Tank A (BRA-T-1001A) on Fire


Fire Water Requirement by Foam Chamber : 33 USgpm
Fire Water Requirement by Water Spray : 382 USgpm
Fire Water Requirement by Fire Hydrant : 500 USgpm
Total Fire Water Requirement : 915 USgpm

Scenario 2: Inside of Production Tank B (BRA-T-1001B) on Fire


Fire Water Requirement by Foam Chamber : 33 USgpm
Fire Water Requirement by Water Spray : 242 USgpm
Fire Water Requirement by Fire Monitor : 500 USgpm
Fire Water Requirement by Fire Hydrant : 500 USgpm
Total Fire Water Requirement : 1275 USgpm

Scenario 3: Inside of Test Tank (BRA-T-1002) on Fire


Fire Water Requirement by Foam Chamber : 8 USgpm
Fire Water Requirement by Water Spray : 242 USgpm
Fire Water Requirement by Fire Monitor : 500 USgpm
Fire Water Requirement by Fire Hydrant : 500 USgpm
Total Fire Water Requirement : 1250 USgpm

The Largest Fire Water Requirement : 1482 USgpm Scenario 4


PT. Pertamina EP Calculation for Fire Water Demand & Water Pond

ATTACHMENT 3 – SPRAY NOZZLE DATA SHEET

20-01-BRGA-PRO-CAL-0024 Rev.0 Page 15 of 17


DATA SHEET

CLIENT REV. DATE MADE BY CHECKED BY APPROVED BY PAGE


PT PERTAMINA EP A 7-Aug-20 SK/CHM API THP
LOCATION A1 22-Sep-20 SK/CHM API THP
WATER SPRAY NOZZLE B 17-Nov-20 AKN/CHM API THP 1
BERINGIN
0 8-Dec-20 RPP/CHM API THP
PROCESS SAFETY

Rev A1
Document No.: Document Title:
Date 27-Nov-20
20-01-BRGA-PSF-DTS-0005 DATASHEET FOR DELUGE SYSTEM
Page 11
SERVICE : DELUGE SYSTEM CLIENT : PT. PERTAMINA EP
P&ID NO : 20-01-BRGA-PRO-PID-0042 PLANT LOCATION : SP BERINGIN A
SAFETY EQ.
: 20-01-BRGA-PSF-DWG-0002 AREA : PRABUMULIH, SOUTH SUMATERA
LAYOUT NO
MANUFACTURE : AS PER COMPANY AML
NO. OF UNIT : 113 Ea (Note 5)
TECHNICAL DATA
Location : ▫ Offshore ▪ Onshore ▫ Other .……………
Atmosphere
Ambient Temp. (Min / Max) ⁰F
:
:

81 / 95
Salt Laden ▪ Tropical
Humidity (Min / Max)
▫ Other .……………
%: 87 / 100
Wind Speed (Average) mps : 1.8 Precipitation : -
Area Classification : Class I Zone 2 Group IIA
SPRAY NOZZLE
Nozzle Type : D3 Protectospray
Connection Type : Male NPT
Connection Size in : 1/2 (Note 1)
o
Spray Angle deg : 110
Body Material : Bronze and 316 SS
Orifice Size in : 1/4
Free Passage Diameter : 1/8 (Note 1)
K-Factor gpm/psi^0.5 : 1.8 (Fire Zone-1 & 3)
3 (Fire Zone-2)
Operating Pressure psig : 20-60 (Note 1)
Approval : UL listed / FM Approved
Accessories : Sprinkle Wrench, W-Type 11 Wrench
Painting : Note 2
Applicable Standard NFPA 15
Zone Protected Equipment K Factor Quantity
Production Separator (BRA-V-1001) 1.8 gpm/psi^0.5 6 Nozzles
Test Separator (BRA-V-1003) 1.8 gpm/psi^0.5 5 Nozzles
Fire Zone-1
Inlet Scrubber (BRA-V-2000) 1.8 gpm/psi^0.5 6 Nozzles
HP Gas Scrubber (BRA-V-2000) 1.8 gpm/psi^0.5 5 Nozzles
Compressor Train 1 (BRA-CPX-2001) 3 gpm/psi^0.5 14 Nozzles
Fire Zone-2 Compressor Train 1 (BRA-CPX-2002) 3 gpm/psi^0.5 14 Nozzles
Compressor Train 1 (BRA-CPX-2003) 3 gpm/psi^0.5 14 Nozzles
Production Tank A (BRA-T-1001 A) 1.8 gpm/psi^0.5 19 Nozzles
Fire Zone-3 Production Tank B (BRA-T-1001 B) 1.8 gpm/psi^0.5 19 Nozzles
Test Tank (BRA-T-1002) 1.8 gpm/psi^0.5 11 Nozzles
TOTAL 113 Nozzles

For Illustration Only

NOTES
1. Vendor to specify and verify data.
2. Painting specification for external metal surface shall refer Painting Specification (20-01-BRGA-PIP-SPE-0004).
3. The location, number & arrangement of firewater spray nozzle shall refer to Fire Water Hydraulic Calculation (20-01-BRGA-PSF-CAL-0001)
4. Stock of spare nozzle shall refer to NFPA 15 Section 5.2.5.5
5. Protected equipment, k-factor, and detail quantity refer to Fire Water Demand & Water Pond Calculation (20-01-BRGA-PRO-CAL-0024)