Make Alstom Type VAA11 SL - No VX 110 - 125V

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

1.

Location

2. Equipment Details:

Make Alstom
3. Type VAA11
Sl.No
Vx 110 – 125V
General Inspection : OK

4. Pick up/Drop off Test:

Ref Pickup volt(V) Drop off Volt(V)


9,10 80.3 39.4

5. Functional checks: (Whether Operational Checks OK / Not OK / Not Available)

1 Correct operation of appropriate indicator / aux. relay OK


2 Correct operation of output contacts OK
3 Relay cover properly fixing OK
4 Correct operating reset switch OK

6. Comments : Nil.

7. Remarks : Relay found Healthy.