2.6.8.1 Roof panels shall be continuous from
ridge to eave for buildings 18m wide or less,
where endlaps are required, the width shall
be approximately 150 mm (as specified on the
drawings), and shall occur over a roof purlin.
2.6.8.2 Sidewall panels shall be continuous from
the eave to 40 mm below me column base plate,
except where the required panel length would
exceed 9.0 m. For a panel length in excess of 9.0 m,
the panel shall be spliced, and endlap shall be 100
mm wide (minimum) and occur over a wall girt.
2.6.8.3 Endwall panels shall be continuous from
the eave to 40 mm below the column base plate,
except where the required panel length would
exceed 9.0 m. For a panel length in excess of 9.0
m, the panel shall be spliced and the endlap shall
be 100 mm wide (minimum) and occur over a wall
girt. All endwall panels shall be square cut in the
field for 3:10 slope buildings.
2.6.8.4 All laps at roof panels shall be sealed with
a continuous ribbon of tape sealer,
2.6.8.5 Roof panels shall be secured to
intermediate framing members with No. 14 sheet
metal screws at a maximum spacing of 333 mm.
At endlaps, the maximum spacing of screws shall
be 111mm. At four corners of the buildings, panel
to structural fastener spacing shall not exceed 111
mm, to an area equivalent to x2 Dimension x is
determined by the following rule:
A. The smaller of
(1) 10% of the least horizontal dimension of the
building (span or length)
(2) 40% of the eave height.
B. But not less than
(1) 4% of the least horizontal dimension of the
building
(2) 0.9 meter
2.6.8.6 Wall panels shall be secured to
intermediate framing members with No. 14 selfdrilling
and tapping screws at a maximum spacing
of 333 mm. At endlaps the maximum spacing of
screws shall be 111 mm.
2.6.8.7 Sidelaps of roof and wall panels shall be
stitched through the high rib with No. 12 sheet
metal screws at 500 mm centers.
2.6.9 Flashing, trim & closures:
2.6.9.1 Flashing and/or trim shall be furnished
at the rake, corners, eaves, framed openings,
and wherever necessary to provide weather
tightness and finished appearance. Color shall be
selected from Kirby Building Systems standard
colors, with the exception of the corner trim,
which matches the building wall color.
2.6.9.2 Color-coated, galvanized steel for
flashing, metal closure, trim and other
miscellaneous uses shall be 26 gauge of the
same specification as the roof and walls covering
material.
2.6.9.3 A formed peak panel matching the slope
and profile of adjoining panels shall be provided
along the building ridge.
2.6.10 Color finish:
2.6.10.1 Unless specified otherwise, all wall and
roof panels, flashing, trim and other exposed
galvanized steel surfaces shall be color coated.
a. Color of panels and corner trim shall be
selected by the customer from Kirby Building
Systems standard colors.
b.The gutters, downspouts, rake trim, eave trim
and door flashing shall be white unless otherwise
selected from Kirby Building Systems-Kuwait
standard