CIRCUIT 1 (LIGHTING)
- As per Philippine Electric Code (PEC), 100 Watts shall be the maximum load for each household
lighting outlet
- By direct counting, 10 outlets = 1000 Watts
- 1000 W / 230 V = 4.35 A
- The PEC provides that “Ampacity of the connected load shall not exceed 80% of the amperage
capacity of the conductor and the fuse.”
- The maximum ampacity load of a 2mm2 No. 14 AWG copper wire is 15A.
15A x 80% = 12A
Referring to the table of allowable ampacities of wires and over current protection device, the
maximum allowable load of the circuit is sufficient enough to carry the 4.35A computed load for a
maximum of 100watts per light outlet. Therefore, the use of 2.0mm2 or No. 14 is safe.
Referring to the table of allowable ampacities of wires and overcurrent protection device,
- For 9.39A, use 2 piece s 3.55 mm2 or No. 12 TW copper wire for circuit no.2
- For the 2-No.12 TW wire, use 13 mm conduit pipe
-Under the column of fuse and breaker rating, the 20A fuse can safely carry a maximum
load of 16A. The 80% of 20A load permitted by the PEC on NO.12 circuit wire.