Floor Standing B Series Technical Manual
Floor Standing B Series Technical Manual
TECHNICAL MANUAL
Split Unit Air Conditioner
Floor Standing B Series
FVRN - B series
— Cooling Only [50Hz] —
TM-5FSB-SL-STA1
Table of Contents
Table of Contents
Nomenclature......................................................................................................................1
Indoor.............................................................................................................................1
Outdoor...........................................................................................................................1
Product Line-Up..............................................................................................................2
Application Information......................................................................................................4
Operating Range............................................................................................................4
Refrigerant Circuit Diagrams..........................................................................................5
Installation Guideline......................................................................................................6
Sound Data...........................................................................................................................9
Sound Pressure Level....................................................................................................9
NC Curve......................................................................................................................10
Engineering & Physical Data............................................................................................12
Performance Data..............................................................................................................15
Calculation Steps..........................................................................................................15
Performance Tables......................................................................................................17
Outlines & Dimensions.....................................................................................................22
Wiring Diagrams................................................................................................................24
Service & Maintenance.....................................................................................................29
Troubleshooting................................................................................................................31
Nomenclature
Nomenclature
Indoor
FV R N 71 B X V1
Power Supply
V1 : 220-240V/1Ph/50Hz
Manufacturer
X : Malaysia
Product Series
B : B Series
Capacity*
71 : 7.1 kW
100 : 10.0 kW
125 : 12.5 kW
140 : 14.0kW
System & Grade
N : Non-Inverter Standard
Refrigerant & Mode
R : R410A Cooling Only
Model
FV : Floor Standing
Outdoor
R R 71 C B X V1
Power Supply
V1 : 220-240V/1Ph/50Hz
Y1 : 380-415V/3Ph/50Hz
Manufacturer
X : Malaysia
Fin Specs
A : Bare Fin
B : Gold Fin
Product Series
C : C Series
D : D Series
Capacity*
71 : 7.1 kW
100 : 10.0 kW
125 : 12.5 kW
140 : 14.0kW
Refrigerant & Mode
R: R410A Cooling Only
Model
R: Single Split Condensing Unit
Remark:
* : Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value.
1
Nomenclature
Product Line-Up
Indoor Unit
FVRN
Classification
Air Purification
Handset
PCB
Fin
Nomenclature
Hydrophilic Coated (Blue)
BRC52A62
08D01
FVRN71BXV1 X X X X
FVRN100BXV1 X X X X
COOLING
FVRN125BXV1 X X X X
FVRN140BXV1 X X X X
FVRN160BXV1 X X X X
2
Nomenclature
Outdoor Unit
RN
Classification
Refrigerant Control
Compressor
Fin
Nomenclature
Bare Aluminium
Cap Tube
Rotary
Scroll
RR71CBXV1 X X X
RR100DBXV1 X X X
RR125DBXY1 X X X
RR140DBXY1 X X X
COOLING
RR160DBXY1 X X X
RR71CAXV1 X X X
RR100DAXV1 X X X
RR125DAXY1 X X X
RR140DAXY1 X X X
RR160DAXY1 X X X
3
Application Information
Application Information
Operating Range
Cooling
Outdoor
DB (°C)
46
43
19
14 19 23 Indoor WB (°C)
4
Application Information
Model: FVRN71B-RR71C
5
Application Information
Installation Guideline
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
Installation Diagram
Indoor Unit
Outdoor Unit
6
Application Information
Outdoor Clearance
If the condensing unit is operated in an atmosphere containing oil (including machine oils),
salt (coastal area), sulphide gas (near hot spring, oil refinery plant); such substances may
lead to failure of the unit.
A B C D
OBSTACLE
OBSTACLE
OBSTACLE
AIR DISCHARGE
AIR INLET
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
Cable Size
FVRN71B FVRN100B FVRN125B
Model Unit
RR71C RR100D RR125D
Power supply cable size mm2 2.5 4.0 1.5
Number of wire 3 3 5
Interconnection cable size mm2 2.5 2.5 1.0
Number of wire 3 4 4
Recommended fuse A 32 25 20
FVRN140B FVRN160B
Model Unit
RR140D RR160D
Power supply cable size mm2 1.5 1.5
Number of wire 5 5
Interconnection cable size mm2 1.0 1.0
Number of wire 4 4
Recommended fuse A 25 25
7
Application Information
Refrigerant Piping
If the pipe length is too long, both the capacity and the reliability of the unit will decrease. As the number
of bends increases, resistance of the piping system to the refrigerant flow increases and thus lowering the
capacity, as a result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated as below
Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.5m, then additional
charge after vacuuming is not necessary. If the piping length is more than 7.5m, then use the additional
charge (g) per additional 1m length as tabulated:
Example:
FVRN71B & RR71C with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 24[g/m]
= 132[g]
Note: Installation and maintenance are to be performed only by qualified personnel who
are familiar with local codes and regulations, and experienced with this type of
equipment.
8
Sound Data
Sound Data
Sound Pressure Level
1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 48 47 41 39 35 29 24 44 38
FVRN71B Med 47 45 39 35 32 26 19 42 35
Low 45 43 36 32 28 20 16 39 33
High 52 50 47 43 41 36 29 49 43
FVRN100B Med 50 49 44 41 38 32 25 47 40
FVRN125B
Low 48 47 42 38 35 29 21 44 37
High 52 51 48 44 42 36 29 50 44
FVRN140B Med 50 50 46 42 39 33 25 48 41
Low 48 48 45 40 36 30 22 46 40
High 56 54 51 49 47 42 36 54 48
FVRN160B Med 55 53 50 47 45 40 34 53 46
Low 53 51 48 45 43 37 30 51 44
Microphone
FVRN71B
FVRN100B Indoor
FVRN125B unit
FVRN140B 1m
FVRN160B
9
Sound Data
NC Curve
FVRN71B
70
60
Sound pressure level (dB, ref 20µPa)
50
40
30
20
10
0
125 250 500 1000 2000 4000 8000
FVRN100B / FVRN125B
70
60
Sound pressure level (dB, ref 20µPa)
50
40
30
20
10
0
125 250 500 1000 2000 4000 8000
10
Sound Data
FVRN140B
70
60
Sound pressure level (dB, ref 20µPa)
50
40
30
20
10
0
125 250 500 1000 2000 4000 8000
FVRN160B
70
60
Sound pressure level (dB, ref 20µPa)
50
40
30
20
10
0
125 250 500 1000 2000 4000 8000
11
Engineering & Physical Data
TYPE SIROCCO
FAN
DRIVE DIRECT
TYPE 1 PHASE FIXED SPEED
INDEX OF PROTECTION (IP) 23
INSULATION GRADE F
FAN MOTOR RATED INPUT POWER W 154 237 237
RATED RUNNING CURRENT A 0.67 1.04 1.04
MOTOR OUTPUT W 44 100 100
POLES 8 10 10
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.40 0.44 0.44
ROW 2
TYPE SARANET
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WHITE
AIR FLOW CFM 1712 3000 3150
SOUND PRESSURE LEVEL dBA 56 58 60
UNIT DIMENSION HEIGHT x WIDTH x DEPTH mm 753 x 855 x 328 852 x 1030 x 400 852 x 1030 x 400
PACKING DIMENSION HEIGHT x WIDTH x DEPTH mm 793 x 990 x 415 1010 x 1180 x 514 1010 x 1180 x 514
UNIT WEIGHT kg 57 71 95
TYPE FLARE VALVE
PIPE
LIQUID mm 9.52
CONNECTION SIZE
GAS mm 15.88
TYPE PROPPELER
FAN
DRIVE DIRECT
TYPE 1-PHASE FIXED SPEED
INDEX OF PROTECTION (IP) 20 54 44
OUTDOOR UNIT
INSULATION GRADE F F F
FAN MOTOR RATED INPUT POWER W 124 223 276
RATED RUNNING CURRENT A 0.54 0.98 1.34
MOTOR OUTPUT W 66 145 145
POLES 6 8 8
TYPE ROTARY TWIN ROTARY SCROLL
MOBILEAL ARCTIC
OIL TYPE FV50S FV50S
22CC
COMPRESSOR OIL AMOUNT cm3 700 1300 1242
RATED INPUT POWER (COOLING) W 2622 3400 3587
RATED RUNNING CURRENT (COOLING) A 12.20 15.08 5.79
LOCKED ROTOR AMP. A 64 68 51.50
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.61 0.87 0.85
ROW 2 1 2
CASING COLOUR IVORY WHITE
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB
12
Engineering & Physical Data
INSULATION GRADE F F
FAN MOTOR RATED INPUT POWER W 406 496
RATED RUNNING CURRENT A 1.76 2.18
MOTOR OUTPUT W 245 400
POLES 6 6
TYPE SCROLL
OIL TYPE COPELAND ULTRA 32-3MAF
OIL AMOUNT cm3 1656 1774
COMPRESSOR
RATED INPUT POWER (COOLING) W 4255 4705
RATED RUNNING CURRENT (COOLING) A 7.49 8.20
LOCKED ROTOR AMP. A 74 74
MATERIAL COPPER
TUBE
DIAMETER mm 7
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.85 0.82
ROW 2 3
CASING COLOUR IVORY WHITE
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB
13
Engineering & Physical Data
Safety Device
R410A
INDOOR FVRN71B FVRN100B FVRN125B
MODEL
OUTDOOR RR71D RR100D RR125D
TYPE N/A N/A NC
HIGH PRESSURE
OPEN kPa / psi N/A N/A 4137 / 600
SWITCH
CLOSE kPa / psi N/A N/A 3310 / 480
TYPE N/A N/A NC
SAFETY LOW PRESSURE
DEVICE OPEN kPa / psi N/A N/A 48 / 7
SWITCH
CLOSE kPa / psi N/A N/A 152 / 22
PHASE SEQUENCER N/A N/A YES
DISCHARGE THERMOSTAT
˚C N/A N/A 125
SETTING
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
14
Performance Data
Performance Data
Calculation Steps
Interpolation method can be used to get the total Solution:
cooling capacity, TC and sensible cooling capacity, Based on the Performance Table,
SC and power input, PI at those temperatures which
1. Refer to the Indoor DB column,
are not stated out in the table. Extrapolation method
-- 25°C is located between 24°C & 27°C
is not allowed to be used.
for 16°C WB.
Example: -- 25°C is located between 24°C & 27°C
for 19°C WB.
Indoor Condition: 25°C DB, 17°C WB -- Thus, Interpolation needs to be applied.
Outdoor Condition: 37°C DB
Fan Speed: High 2. Refer to the Indoor WB column,
-- 17°C is located between 16°C & 19°C
for 25°C DB.
-- Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
-- 37°C is located between 35°C & 40°C.
-- Thus, Interpolation needs to be applied.
Details of Calculation:
1st Step: By Interpolation Method
To obtain the TC, SC & PI for 25°C – 24°C x1 – 7.47kW
⇒ =
27°C – 24°C 7.69kW – 7.47kW
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB ⇒ x1 = 7.54kW
Outdoor temperature Similarly,
EWB EDB 35°C
y1 = 6.64kW
TC SC PI
z1 = 2.80kW
15
Performance Data
Repeat the same process for (c) & (d) in 1st Step
3rd Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor temperature
EWB EDB 35°C 37°C 40°C
TC SC PI TC SC PI TC SC PI
16
Performance Data
Performance Tables
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
17
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
18
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
19
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
20
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
21
Outlines & Dimensions
I J K
Dimension
A B C D E F G H I J K L
Model
71 514 254 1850 676 859 600 270 242 73 77 115 34
100/125/140/160 514 254 1850 676 859 600 350 322 73 77 115 34
Note: Dimension in mm
22
Outlines & Dimensions
Outdoor Unit
N
M
C
N
A
G H
D
F
O
E
B
I J
Dimension
A B C D E F G H I J K L M N O
Model
71 855 730 328 520 179 46 93 149 101 113 603 126 164 15 34
Dimension
P Q R S
Model
71 23 362 73 75
J I J
N
M
N
A O C
K D
MADE IN MALAYSIA
B
F
E
G H
L
Dimension
A B C D E F G H I J K L M N O
Model
100/125/140/160 1030 826 400 695 57 72 90 40 746 142 60 26 448 22 28
Note: Dimension in mm
23
Wiring Diagrams
Wiring Diagrams
Cooling Only
Indoor Unit Outdoor Unit
Model: FVRN71B Model: RR71C
L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E
24
Wiring Diagrams
L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E
25
Wiring Diagrams
POWER SUPPLY
380-415V/3Ph/50Hz
R S T N E
26
Wiring Diagrams
POWER SUPPLY
380-415V/3Ph/50Hz
R S T N E
27
Wiring Diagrams
POWER SUPPLY
380-415V/3Ph/50Hz
R S T N E
28
Service & Maintenance
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.
29
Service & Maintenance
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once quarterly. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be
regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into
the unit when performing a leakage test or an air tight test. These gases could cause severe
explosion and damage if expose to high temperature and pressure.
30
Troubleshooting
Troubleshooting
Fault Diagnosis
Event Actions
Room Sensor Open or Short Blink E1
Indoor Coil Sensor Open Blink E2
Outdoor Coil Sensor Open Blink E3
Compressor Overload / Indoor Coil Sensor Short Blink E4
Outdoor Abnormal Blink E5
Water Pump Fault Blink E6
Hardware Error (Tact Switch Pin Short) Blink E8
Phase Sequencer
The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase
sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not
connected correctly, the phase sequencer operates, and the unit will not start.
The following table shows the LED indicator light for phase sequencer under normal operation and fault
conditions.
LED PW P_S P_T Actions
Description (Red) (Yellow) (Yellow)
Normal Operation -
Reverse Phase Switch off the unit. Check the 3 phase wiring.
T Phase Missing Switch off the unit. Check the 3 phase wiring.
S Phase Missing Switch off the unit. Check the 3 phase wiring.
R Phase Missing Switch off the unit. Check the 3 phase wiring.
31
Troubleshooting
32
Troubleshooting
Diagnostic Guidelines
A little high
Probable cause
A little low
Too high
Too low
Circuit Normal
High side • 1. Overcharged with refrigerant.
Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side • 1. Poor compression /no compression (compressor
Low side • defective)
2. Reversing valve leaking.
High side • 1. Undercharged with refrigerant.
Low side • 2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
High side • 1. Outdoor fan blocked (cooling).
Low side • 2. Outdoor coil dirty (cooling).
3. Non-condensable gases in refrigerant circuit (e.g. air).
High side • 1. Air intake temperature of indoor unit too high.
Low side •
33
Troubleshooting
Evaporator Stop
Fan Motor
Condenser Stop
Fan Motor
Overcurrent Tripped High Voltage or Low Voltage Get the Right Voltage
Relay For
Condenser Fan Check The Power Supply To The
Wrong Phase/Missing Phase Motor : Repair When Necessary
34
Troubleshooting
Insufficient cooling
Less or no compression
Compressor (Low running current) Replace compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 8°C to 13°C. *
( * value is for reference only )
Insufficient heating
High cooling
Windows / doors wide open Close the windows / doors
load
Less or no compression
Compressor (Low running current) Replace compressor
Satisfactory operation with temperature difference of air intake & discharge of indoor unit 14°C to 20°C. *
( * value is for reference only )
35