312 - Ref 541

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

1.

Location : MRS#1

Feeder Name : Spare Feeder / P. No: 26

2. Equipment Details:

Make ABB
3. General Inspection:
Type REF 541
OK Uaux 110 – 220 V DC
Un 110 – 125 V
4. Service settings:
In 1/5A

4.1 NEF 1 Low:


Operation mode Normal inverse
Start Current 10.0%
TMS 0.10

4.2 NEF1 High:


Operation mode Not in use

4.3 NOC3 High(C):


Operation mode Not In Use

4.4 NOC3 Low (D):


Operation mode Normal inverse
Start Current 0.10*In
TMS 0.10

4.5. Inrush 3 (D):


Operation mode Not in Use

5. Secondary Injection Test:


5.1. NEF1 (Low):
Operated Time (S)
Ref Set Current (A) Operated Current (A) TMS
X2 X5
RE - - - - -
YE - - - - -
BE - - - - -

5.2. NEF1 (Low):

Operated Time (S)


Ref Set Current (A) Operated Current (A) TMS
X2 X5
RE - - - - -
YE - - - - -
BE - - - - -

5.3. NOC3 (Low):

Ref Set Current (A) Operated Current (A) TMS Operated Time (S)
*2 *5
R 0.10 0.102 0.10 - -
Y 0.10 0.102 0.10 - -
B 0.10 0.102 0.10 - -

5.4. NOC3 (Low):

Operated Time (S)


Ref Set Current (A) Operated Current (A) TMS
*2 *5
R - - - - -
Y - - - - -
B - - - - -

6. Functional checks: (Whether Operational Checks OK / Not OK / Not Available)

1 Correct operation of appropriate indicator / aux. relay --


2 Correct operation of output contacts --
3 Relay cover properly fixing --
4 Correct operating reset switch --

7. Comments : Nil.

8. Remarks : Relay Internal faulty.