TEST REPORT FOR GROUNDING RESISTANCE

Project Maintenance Power Room


Location Power Room
Climate Sunny Rainy ✘ Cloudy

Classification Grounding Conductor Ground Good ≤ 5Ώ ( ohms )


No. Grounding Application and Name of Equipment to be grounded Resistance in
Ώ ( ohms )
( EA , EB or EC ) Copper Rod (Size and Type ) Yes No
GROUNDING BOX ( Power Room)

1 NEUTRAL TRANSFORMER-1 E2 NYA 95mm2 3.08 a

2 BODY LOW VOLTAGE PANEL / MDB 1 E1 & E3 NYA 95mm2 2.87 a

3 NEUTRAL TRANSFORMER-2 E5 NYA 95mm2 0.54 a

4 BODY LOW VOLTAGE PANEL E4 NYA 95mm2 0.55 a

Remarks :

Ground Resistance : ≤ 5 Ώ
Tested By : Checked By : Approved By :

Date: / / Date: / / Date: / Date:/ / /


PHOTOGRAPH REPORT

Date : 01 November 2020 Date : 01 November 2020


Location : Power room Location : Power room
Grounding Point : Grounding Neutral Trafo 1 Grounding Point : Grounding MDB 1

Date : 01 November 2020 Date : 01 November 2020


Location : Power room Location : Power room
Grounding Point : Grounding Neutral Trafo 2 Grounding Point : Grounding MDB 2