EPS ETA High-Voltage Generator: Product Specification

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

EPS ETA High-Voltage Generator

PRODUCT SPECIFICATION

RAD Configuration

Copyright application © 2019 by EMD Technologies Incorporated. All rights reserved. EMD Technologies
Incorporated and the EMD Technologies Incorporated logo are trademarks of EMD Technologies Incorporated.

Contents of this publication may not be reproduced in any form or by any means, electronic or mechanical,
including photocopying and recording, or by any information storage or retrieval system without the written
permission of EMD Technologies Incorporated, 400 rue du Parc, Saint-Eustache (Québec), Canada, J7R 0A1.
EPS ETA High-Voltage Generator

HISTORY
Date Rev. Description
01.10.2019 G0 Initial Release

Specifications are subject to change without notice

EMD’s High Voltage Generators are protected by one or more claims of EMD’s United States Patent Number
7,936,544, 6,738,275, 6,967,559 and 7,375,993 and EMD's European Patent 1 102 388 B1. Additional EMD patent
applications pertinent to the product are pending.

Manufacturer:

EMD Technologies MDSS GmbH Intertek Semko AB


400 du Parc, Schiffgraben 41 Torshamnsgatan 43, Box 1103
Saint-Eustache, (Quebec) 30175 Hannover, SE-164 22 Kista,
Canada, J7R 0A1 Germany Sweden

Document Number 10000.000.EPS ETA.G0 2/30


EPS ETA High-Voltage Generator

TABLE OF CONTENTS

1.0 INTRODUCTION TO EPS ETA HIGH-VOLTAGE GENERATOR.................................................................... 4


1.1 Epsilon Platform & Configuration ............................................................................................................................... 5
1.2 Epsilon Main Features .................................................................................................................................................... 6
1.3 Options.............................................................................................................................................................................. 8
1.3.1 Operator Console P/N 9777.101 (& Handswitch 10018.004) ....................................................................... 8
1.3.2 Handswitch 10018.004 (Requires EMD’s Operator Console) ..................................................................... 10
1.3.3 Epsilon Cabinet P/N 10017.005 ....................................................................................................................... 11
1.3.4 Two-Tube Option ............................................................................................................................................... 11
1.3.5 Auxiliary Power Supplies .................................................................................................................................... 12
1.3.6 Multi-Energy – Stepping ..................................................................................................................................... 12
1.3.7 Multi-Energy – Real-Time .................................................................................................................................. 13
1.3.8 DAP Interface P/N 10028.000 ......................................................................................................................... 14
1.3.9 Relay Board P/N 9932.02 .................................................................................................................................. 14
1.3.10 Power Distribution Unit (PDU) ........................................................................................................................ 15
1.3.11 Universal Chambers Interface Board P/N 11002.000................................................................................... 15

2.0 TECHNICAL SPECIFICATIONS .................................................................................................................................. 16


2.1 ELECTRICAL REQUIREMENTS .......................................................................................................................... 16
2.1.1 Electrical Line Requirements ............................................................................................................................. 16
2.1.2 Power Ratings ....................................................................................................................................................... 17
2.2 Maximum Power Output ............................................................................................................................................. 19
2.3 Tube Loading ................................................................................................................................................................. 20
2.3.1 Loading Factors.................................................................................................................................................... 20
2.3.2 Loading Accuracy and Repeatability ................................................................................................................. 21
2.4 Exposure Modes ............................................................................................................................................................ 22
2.4.1 Tube Loading Modes .......................................................................................................................................... 22
2.4.2 AEC Mode Specifications .................................................................................................................................. 22
2.5 X-Ray Tube .................................................................................................................................................................... 25
2.5.1 X-Ray Tube Interface .......................................................................................................................................... 25
2.5.2 Focal Spot / Anode Speed ................................................................................................................................. 25
2.6 Generator I/Os Basic Specifications.......................................................................................................................... 26
2.6.1 Programmable Inputs .......................................................................................................................................... 26
2.6.2 Open Collector Outputs ..................................................................................................................................... 26
2.6.3 Cable Requirements ............................................................................................................................................. 26
2.7 Environmental Specification ....................................................................................................................................... 27
2.8 Mechanical Data ............................................................................................................................................................ 28

3.0 COMPLIANCE INFORMATION .................................................................................................................................. 30

Document Number 10000.000.EPS ETA.G0 3/30


EPS ETA High-Voltage Generator

1.0 INTRODUCTION TO EPS ETA HIGH-VOLTAGE GENERATOR

The EPS ETA High-Voltage generator is an Advanced High Frequency X-ray Generator designed with a unique
power inverter technology and modular conception. The Generator is remarkable for its kV flatness output, an
unequalled kV rise time and for its solid dielectric high-voltage unit (no oil).

Tube loading:
100 kV, 400 mA, 10 ms

Typical kV rise time:


175 µs

Figure 1 – Typical kV Waveform.

Figure 2 – EPS ETA High-Voltage Generator illustration (covers hidden for better visualization).

Document Number 10000.000.EPS ETA.G0 4/30


EPS ETA High-Voltage Generator

1.1 Epsilon Platform & Configuration

As more power or custom features are needed, they are simply added using plug-in modules quickly inserted to
the generator's main core. The latter consists of an electronic controller driving an encapsulated (oil-free) high-
voltage unit. The generator comes in different configurations, best suited to conventional RAD and to the latest
digital procedures. Features and options are summed up in Table 1 and described later in the text.

Table 1- Main Configurations of EPS ETA High-Voltage Generator (1)


AEC Hardware Options
kW APS ME
ION S.S. Ion PhD/PMT Con/Hs Relay DAP Cb

45 2 O O O O O O O O

50 2 O O O O O O O O

55 2 O O O O O O O O

65 2 O O O O O O O O

70 2 O O O O O O O O

80 2 O O O O O O O O
(1) All configurations come with a mandatory option for rotor controller: low or dual speed
anode rotation.
(2) O = Optional feature

Ion Ion Chamber Interface (2) Con/Hs Operator Console/Handswitch

S.S. Ion Solid State Ion Chamber DAP Dose Area Product

PhD Photodiode Cab Epsilon Cabinet

PMT Photomultiplier tube APS Auxiliary Power Supplies

Relay Relay Board (8 relays) ME Multi-Energy

Document Number 10000.000.EPS ETA.G0 5/30


EPS ETA High-Voltage Generator

1.2 Epsilon Main Features

1. Extremely sharp kV waveform, with rise and fall times unparalleled in the industry, resulting in superior
image quality and reduced soft radiation.

2. 380/480 VAC Universal Line Voltage Input, allowing automatic worldwide installation.

3. Solid dielectric high-voltage encapsulation.

4. Self-diagnostic methods, using redundant circuits.

5. Epsilon PC Tools configuration/diagnostic program:


- Configuration files for easy & quick set-up of generator.
- Boot loader for software update, diagnostic mode,
- Tube and generator statistics.
- HTML log with a thorough context-sensitive event descriptor.
- Second language module.

Figure 3 – Epsilon PC Tools Program.

Document Number 10000.000.EPS ETA.G0 6/30


EPS ETA High-Voltage Generator

6. Automatic X-ray tube calibration module (Figure 4, left) with X-ray tube emission curves viewer (Figure 4,
right) for backup and export.

Automatic X-ray tube calibration menu X-ray tube emission curves

Figure 4 – Epsilon Tube Calibration module and tube calibration display

7. PC serial connectivity (RS-232/CAN/USB) providing full flexibility for customer control.

8. Expansion motherboard for simplified customization through optional boards.

9. External Control Panel (CON2): A Customer can develop his own operator console (external controller, also
referred to as CON2) to communicate with the generator through a bidirectional serial link using a protocol
proprietary of EMD Technologies. With CON2, the generator is capable of performing multi-energy
exposure mode not otherwise possible with a regular EMD’s operator console (CON1). Both CON2 and
CON1 can coexist on a given Epsilon network.

If a customer develops his own console, that console shall allow the operator to operate the device safely and
in complete respect of the regulatory laws in force in the country of installation. IEC 60878-5339 and/or IEC
60878-5909 symbols, presenting physiological side effects of X-rays, shall be displayed on the console.
Accompanying documents of the product shall inform that the generator can be operated by trained personnel
only. If the product is used in USA or in Canada, a warning text shall appear on the console with the mention
that the use of the product by unauthorized individuals is prohibited.

Document Number 10000.000.EPS ETA.G0 7/30


EPS ETA High-Voltage Generator

1.3 Options

1.3.1 Operator Console P/N 9777.101 (& Handswitch 10018.004)

The Epsilon Operator Console (Figures 5, 6) provides simple control of the EPS ETA High-Voltage generator. It
manages 4 configurable workstations with 3 patient sizes for more than 2000 APR exams.

Figure 5 – Epsilon Operator Console.

The console includes three (3) 7-segment parameter displays and adjustment keys to quickly set up an exam.
Exposure can be launched from the console or from an optional handswitch. The console also displays in a graphic
screen a built-in service mode for quick diagnostic and system status feedback.

Document Number 10000.000.EPS ETA.G0 8/30


EPS ETA High-Voltage Generator

Operator Console Keys


1. Power Off 9. mA/mAs Exposure Mode
2. Power On 10. Ion Chamber’s Fields Selection
3. RAD Switch 11. AEC Mode On/Off
4. PREP Switch 12. Parameters / Selection
5. Fault Reset 13. Graphic Screen Selections
6. Special Functions 14. AEC Density Correction
7. Workstation keys [4] 15. Patient Size [3]
8. Ion Chamber’s Film-screen Selection
Operator Console Status Indicators
A. Tube Selection F. Time Units Display
B. Focal Spot Selection G. AEC Density Bar Graph
C. System Limits H. Exposure PREP Indicator
D. Interlock Fault I. X-ray On Indicator
E. mA/mAs Display
Operator Console Screen Displays
i. kV Display; ii. mA/mAs Display; iii. Exposure Time Display; iv. Graphic Screen Display

Figure 6 – Epsilon Operator Console (description of Figure 5).

Figure 7 – Graphic screen on the operator console.

Document Number 10000.000.EPS ETA.G0 9/30


EPS ETA High-Voltage Generator

Table 2- Operator Console Audible Alarm


Alarm conditions Tone

X-ray Emission Continuous tone (1/4 second minimum).

80 % of maximum run length elapsed Pulsed tone (2 beeps per second)

Anode H.U. over 80% Pulsed tone (2 beeps per second)

System Fault, Error 4 consecutive beeps

1.3.2 Handswitch 10018.004 (Requires EMD’s Operator Console)

An optional X-ray Hand-Switch (Figure 8) provides the Epsilon operator console with a hand held push-button
switch that can be extended 3.8 m (8 feet) from the operator console.

N° Qt Description

Handswitch/ cable/
1 1
connector

Handswitch console
2 1
holder

Handswitch console
3 1
bracket

4 1 Protective cover

5 1 Screw PHMS

6 2 Spacer

7 2 Screw SEMS

8 2 Nut Klock

Figure 8 – Handswitch Option installation on Epsilon operator console.

Document Number 10000.000.EPS ETA.G0 10/30


EPS ETA High-Voltage Generator

1.3.3 Epsilon Cabinet P/N 10017.005

This cabinet option (Figure 9) offers mechanical and electrical enclosure to the generator using high quality
aluminum panels easily assembled. The cabinet hides out the mains cable entry and affords two passageway
configurations for the High-Voltage cables.

1.3.4 Two-Tube Option

The 2-Tube option provides a standalone X-ray tube switch and the necessary hardware & software to drive two
different X-ray tubes from a single generator. Each tube is assigned to specific workstations. Commutation time
to switch tube is about 5 seconds.

EPS Generator Cabinet Two-Tube Option Cabinet

Figure 9 – Epsilon cabinet for EPS ETA Generator (left) and 2-tube option (right).

Document Number 10000.000.EPS ETA.G0 11/30


EPS ETA High-Voltage Generator

1.3.5 Auxiliary Power Supplies

The following four (4) options (P/N 11028.xxx) provide additional supplies for room interfacing. Note that with
the first three (3) auxiliary power supplies, it is mandatory that the generator be supplied with 400Y/230VAC
mains. The fourth option is available with 400-480 VAC mains.

Medical Grade Power Supply 150 VA Power Transformer


Option Mains
24VDC-2.7A 24VAC-150VA
P/N 11028.000 ✓ ✓
400Y/230VAC
P/N 11028.001 ✓ --
(+ Neutral)
P/N 11028.004 -- ✓
P/N 11028.005 ✓ ✓ 400-480 VAC

1.3.6 Multi-Energy – Stepping

This option allows an external controller to vary the tube loading factors during the exposure run, in-between
exposures. The external controller must communicate with the generator through the use of a serial protocol
(CANBUS or RS-232) proprietary to EMD Technologies Incorporated. Exposure parameters are pre-determined
before beginning the run. All step changes are controlled via an external trigger and a CON2 serial protocol.

Document Number 10000.000.EPS ETA.G0 12/30


EPS ETA High-Voltage Generator

1.3.7 Multi-Energy – Real-Time

This option allows an external controller to vary the tube loading factors during the exposure run, in-between
exposures. The external controller must communicate with the generator through the use of a serial protocol
(CANBUS or RS-232) proprietary to EMD Technologies Incorporated. Exposure parameters vary live during the
run.

Figure 10 – Typical Multi-Energy Exposures.

Document Number 10000.000.EPS ETA.G0 13/30


EPS ETA High-Voltage Generator

1.3.8 DAP Interface P/N 10028.000

The DAP Interface option allows interfacing a VACU DAP measurement device
on the generator to display, on the Epsilon Operator Console, the radiation level
a patient is exposed to in radiological exams.
Figure 11 –
Display of instantaneous DAP on the console’s graphic screen

1.3.9 Relay Board P/N 9932.02

This board provides eight programmable relays that can be used to control x-ray room lines as a function of the
generator status (Figure 12).

(a)

–– : Common contact;
–– : Normally open contact ;
–– : Normally close contact
K1-K4 : GROUP I
========== ISOLATION BARRIER
K5-K8 : GROUP II

Relay board P/N 9932.02


(b)
APPLICATION NOTE:
Relays are divided in two groups; Assign each voltage type to
a specific group. Do not mix AC and DC voltage switching
on the same relay group. For example, use group I relays to
commute line-voltage level signals and group II relays to
c) commute low-voltage signals.

(a) Relay board mounted on its Assembly Plate; SPDT Relays ratings:
(b) 12-Position Terminal Block (28-12 AWG). 10 A @ up to 250 VAC;
10 A @ up to 30 VDC
(c) K1-K8 Relays Programmable output mode of operation.

Figure 12 – Relay board option

Document Number 10000.000.EPS ETA.G0 14/30


EPS ETA High-Voltage Generator

1.3.10 Power Distribution Unit (PDU)

A custom power distribution unit (PDU) can be provided as per customer requirements and ancillaries.
Contact EMD Technologies Incorporated for specific requirements.

1.3.11 Universal Chambers Interface Board P/N 11002.000

Consists of a plug-in board and the necessary software to perform AEC exposures on up to 3 different solid
state AEC chambers. This board includes also an additional interface for a standard ion chamber.

Figure 13 – Universal Chambers Interface Board.

Document Number 10000.000.EPS ETA.G0 15/30


EPS ETA High-Voltage Generator

2.0 TECHNICAL SPECIFICATIONS

2.1 ELECTRICAL REQUIREMENTS

2.1.1 Electrical Line Requirements

Overvoltage Category II – The generator is intended to be used in “Overvoltage Category II” locations where
the mains transient voltage would not be higher than 2500 Vpeak.

Three-phase Mains – The generator requires a three-phase electrical line with a protective earth ground (PE) and
an optional neutral (N) wire (4 or 5 wires). Standard line regulation from no load to full load will provide full power
output, at maximum kV.

Figure 14 –Types of Line Configuration.

Typical Wire Size –


Maximum acceptable wire size : Based on the service breaker switch
Type of connectable conductor cross-sections
• For mains contacts
o Single or multi-stranded 2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
o Finely stranded with core end processing 2x (1 ... 16 mm²), 1x (1 ... 25 mm²)
• At AWG conductors for main contacts 2x (18 ... 3), 1x (18 ... 2)

Minimum wire size (*) : 4 AWG (20 mm2) (based on NEMA XR9 for a distance of 50 ft)
Wire size depends on the length of wire.

Grounding wire size (*) : 8 AWG (8 mm2)

(*) Typical values as per the National Electrical Code

Document Number 10000.000.EPS ETA.G0 16/30


EPS ETA High-Voltage Generator

2.1.2 Power Ratings

Table 3- Power Ratings and Electric Line Requirements


Mains Voltage NOMINAL ELECTRIC POWER (4)
Over-current
VAC ± 10% Epsilon
Releases Short Term Long Term (5)
50/60 Hz Configuration
(A) (2)
(3 Phases) (1) (A)(3) (KVA) (A) (KVA)
EPS ETA 45 80 95 58
EPS ETA 50 100 105 68
EPS ETA 55 100 115 73
380 0.6/4.0 0.4/3.0
EPS ETA 65 100 135 85
EPS ETA 70 100 145 90
EPS ETA 80 100 165 105
EPS ETA 45 80 85 58
EPS ETA 50 100 102 68
EPS ETA 55 100 109 73
400 0.6/4.0 0.4/3.0
EPS ETA 65 100 124 85
EPS ETA 70 100 132 90
EPS ETA 80 100 150 102
EPS ETA 45 80 72 60
EPS ETA 50 100 85 70
EPS ETA 55 100 92 76
480 0.8/4.0 0.7/3.0
EPS ETA 65 100 105 88
EPS ETA 70 100 112 93
EPS ETA 80 100 125 105
Notes
(1) Automatic mains selection (no transformer tap configuration required). Automatic kW derating when
mains voltage drops below -12% The system integrator or installer shall be responsible for providing an
adequate means of disconnect from mains supply. Thermal breaker recommended.
(2) The system integrator or installer shall be responsible to provide an adequate over-current release. The
values indicated in this table are suggested figures: the selected overcurrent release should have current
rating versus time curve characteristics higher than the values specified.
The means of disconnect must be located within the reach of the operator/service.
(3) Nominal line current values evaluated with a Mains apparent resistance of supply mains of 0.16 Ω.
(4) Add 4A to current ratings and 3kVA to kVA rating when the Auxiliary Power Supply option is installed.
(5) Values based on [Standby/Ready state] mode.

Document Number 10000.000.EPS ETA.G0 17/30


EPS ETA High-Voltage Generator

Table 4- Mains Apparent Resistance


Mains Voltage Epsilon Maximum Mains Apparent
VAC ± 10% (3 Phases) Configuration Resistance ()
EPS ETA 45 0.20
EPS ETA 50 0.15

380 Volts EPS ETA 55 0.15


(50/60 Hz) EPS ETA 65 0.15
EPS ETA 70 0.12
EPS ETA 80 0.10
EPS ETA 45 0.22

EPS ETA 50 0.17

400 Volts EPS ETA 55 0.17


(50/60 Hz)
EPS ETA 65 0.17

EPS ETA 70 0.17

EPS ETA 80 0.11


EPS ETA 45 0.32
EPS ETA 50 0.24

480 Volts EPS ETA 55 0.22


(50/60 Hz) EPS ETA 65 0.16
EPS ETA 70 0.16
EPS ETA 80 0.16

Document Number 10000.000.EPS ETA.G0 18/30


EPS ETA High-Voltage Generator

2.2 Maximum Power Output

The maximum power output depends upon the power configuration (option chip) and the number of Inverters.

Table 5- Combination of x-ray tube Voltage (kV) & Current (mA) for maximum power (kW)(1)
Tube Current (mA) 200 250 320 400 500 630 800 1000

Nominal kV 150 150 150 150 150 127 100 80


EPS ETA 80
(4 Inverters)
kW 30 37 48 60 75 80

Nominal kV 150 150 150 150 130 103 81 65


EPS ETA 65
(4 Inverters)
kW 30 37 48 60 65

Nominal kV 150 150 150 125 100 79


EPS ETA 50
(3 Inverters)
kW 30 37 48 50

Nominal kV 150 150 140 112 90


EPS ETA 45
(3 Inverters)
kW 30 37 45

(1) Nominal electric power outputs (in kW) are given for 100-ms tube loading time.

Document Number 10000.000.EPS ETA.G0 19/30


EPS ETA High-Voltage Generator

2.3 Tube Loading

2.3.1 Loading Factors

Table 6- Loading Factors as per EPS ETA Generator Configurations


EPS ETA Generator Configurations
X-ray Factor
45-kW 50/55-kW 65/70-kW 80-kW
kV 40 – 150 40 – 150 40 – 150 40 – 150

1-kV steps; X-ray tube voltages according to available electrical power (Table 5).

mA 10 – 500 10 – 630 10 – 800 10 – 1000

____________ 25% increment steps (up to 21 stations) _______________

10 12.5 16 20 25 32 40 50 63 80
100 125 160 200 250 320 400 500 630 800 1000.

mAs (*) 0.4 – 630 0.4 – 1000 0.4 – 1000 0.4 – 1000

______________ 25% increment steps (35 stations) _________________


0.4 0.5 0.63 0.8 1.0 1.25 1.6 2.0 2.5 3.2
4.0 5.0 6.3 8.0 10 12.5 16 20 25 32
40 50 63 80 100 125 160 200 250 320
400 500 630 800 1000.
(*) Total mAs/exposure in single exposure mode. In AEC exposure, the mAs
is limited to 600.

Time (s) 0.001 – 10 0.001 – 10 0.001 – 10 0.001 – 10

___________ 25% increment steps (41 stations, below in ms) ______________

1.0 1.25 1.6 2.0 2.5 3.2 4.0 5.0 6.3 8.0
10 12.5 16 20 25 32 40 50 63 80
100 125 160 200 250 320 400 500 630 800
1000 1250 1600 2000 2500 3200 4000 5000 6300 8000 10000.

Document Number 10000.000.EPS ETA.G0 20/30


EPS ETA High-Voltage Generator

2.3.2 Loading Accuracy and Repeatability

Table 7- Accuracy and Repeatability Specifications (1)


Conditions
X-ray Factor Accuracy Repeatability
kV mA mAs Time
kV(2) ± (5% + 2 kV) ± (1% + 0.25 kV) Any Any Any > 5 ms
mA ± (5% + 0.5 mA) ± (2.5% + 0.5 mA) Any Any Any > 40 ms
mAs ± (5% + 0.2 mAs) ± (2.5% + 0.2 mAs) Any Any Any > 5 ms
Irradiation time(3) ± (5% + 0.2 ms) ± (1% + 0.2 ms) Any Any Any Any

Notes:
1. Accuracy specifications were measured as per IEC 60601-2-54 requirements.

2. kV ripple as per IEC 60601-2-54 requirements.

3. Irradiation time measured as the time interval between the instant high voltage rises above 75%
of its set value and the instant it falls below the same value

Document Number 10000.000.EPS ETA.G0 21/30


EPS ETA High-Voltage Generator

2.4 Exposure Modes

2.4.1 Tube Loading Modes

The generator provides single and serial tube loading with manual and AEC-controlled irradiation time.

Table 8- Available Tube Loading modes


Exposure Mode Description

Single One tube loading for a distinct switch actuation.


Multiple Repeated tube loadings for a distinct Prep switch actuation. Number of exposures depends
upon the product of frame rate and run length factors. For example, a run done @ 30 f/s
with a run length of 10 seconds will result in a maximum of 300 exposures.
Frame rate 7 frame rates available, programmable in service mode up to 30 f/s, with 0.05 f/s increments.
Operative frame rate selected by operator, APR or digital signals.
Run length Maximum total duration of repeated tube loadings allowed by the generator for a distinct
exposure switch actuation:
1, 2, 5, 10, 20, 30, 40, 50 and 60 seconds.

Note: Both operative frame rate and run length factors impact on the allowed tube kW load. The generator ensures
the x-ray tube operating parameters are within safe limits.

Technique Description
3-Point Loads the tube at specific kV, mA and irradiation time factors.

2-Point Loads the tube at specific kV and mAs factors.

AEC mode Loads the tube …


In AEC-mA @ specific kV & mA factors and adjustable backup time (for a given kV);
In AEC-mAs @ specific kV & backup mAs factors.

AEC-Lock Mode First exposure performed in normal AEC mode and the rest of the sequence at a fixed mAs
value obtained from and equal to the first frame. The mode is actuated by a digital input.

2.4.2 AEC Mode Specifications

The nominal shortest irradiation time for AEC exposure is 5 ms, at all x-ray tube current and x-ray tube voltage
combinations.
Maximum mAs: 600 mAs

Document Number 10000.000.EPS ETA.G0 22/30


EPS ETA High-Voltage Generator

Six clinically significant optical density corrections are provided with the AEC mode, varying from the standardized
optical density N= 1 (Figure 15).

Optical density correction (Ion chamber)


0.57 0.69 0.83 1 1.2 1.45 1.75

-3 -2 -1 Normal +1 +2 +3
75 % 82 % 90 % 100 % 110 % 121 % 133 %

Optical density correction (PM tube or photodiode)

Figure 15 –Useful range of optical densities in AEC mode.

Ionization Chamber Interface

Two ion chambers are supported on the standard generator.

• Three independent user-selectable fields (left, middle, right).

Ion Chamber Fields Film/Screen correction tables

• Three film-screen correction tables: Compensation for density relating to film-screen kV curve
characteristics. Compensation ranges from – 80 % up to + 130 % of phototiming level for 12 stations
between 42 kV and 133 kV.

• Other ion chamber interfaces are optional (Table 9). More AEC sensors can be interfaced, depending on
the generator configuration.

Table 9- Optional Additional Ion Chamber Interfaces


Expansion boards Number/Type of AEC Chamber
Photodiode Ion Chamber Fluoro board P/N 11030.001 2 conventional ion chambers
Universal Chambers Interface Board P/N 11002.001 1 conventional ion chamber
3 solid state chambers

Document Number 10000.000.EPS ETA.G0 23/30


EPS ETA High-Voltage Generator

Photomultiplier tube interface

This option requires the PM tube board P/N 9822.01 (Figure 16). The generator provides the PM tube gain circuit
adjustment using a high voltage bias supply from about -200 V to about -950 V.

Photodiode interface

This option requires the Photodiode Ion Chamber board P/N 11030.001 (Figure 16). One BNC type connector
is used for AEC feedback input from the photodiode device.

Photodiode Ion Chamber


Fluoro PMT Board
Fluoro Board P/N 11030.001
P/N 9822.01

Figure 16 – Selection of Fluoro board used for AEC.

Document Number 10000.000.EPS ETA.G0 24/30


EPS ETA High-Voltage Generator

2.5 X-Ray Tube

2.5.1 X-Ray Tube Interface

Type of Tubes Class 1 B (IEC Classification).

Number of Tubes One X-ray tube standard; 2-tube configuration available as an option.

Models Most popular X-ray tube models are supported through a built-in X-ray tube chart. Other
X-ray tube models may be added by the installer.

Tube Filaments
Focal spot number : 2
Current range : Up to 8.1 RMS amperes
Filament power : Maximum 100 watts

Tube Derating
The tube factors (*) can be derated to extend its usable lifetime, to troubleshoot specific conditions or other reasons.

(*) kW, kV and I filament

2.5.2 Focal Spot / Anode Speed

Manual and automatic focal spot selection can be selected.


In auto focal spot selection, the filament is determined as a function of the technique kW and the anode speed. Table
10 below shows the generator algorithm for the selection of the focal spot and anode rotation speed when auto
speed and auto focal spot are enabled. The anode speed is set in the workstation configuration and is not user alterable.

Table 10- Focal spot selection in Auto-Focal Spot Auto-Speed


Tube Loading Focal Spot Anode Speed

kW1 Low
Small
kW2 > kW1 High

kW3 > kW2 Low


Large
kW4 > kW3 High

Document Number 10000.000.EPS ETA.G0 25/30


EPS ETA High-Voltage Generator

2.6 Generator I/Os Basic Specifications

2.6.1 Programmable Inputs

Up to 14 programmable digital inputs are available on the generator for interfacing purposes (10 on Controller
board, 2 on Fluoro board 9822.01 and 4 on Fluoro board 11030.001). All inputs are active low and use isolated
diodes at their front ends. A pull-up voltage (+5VDC or +12VDC) is conveyed to the input terminals for reference.

2.6.2 Open Collector Outputs

Up to 12 programmable digital outputs are available on the generator for interfacing purposes (8 on Controller
board, 4 on Fluoro board 9822.01 and 2 on Fluoro board 11030.001). All outputs are open collector switches to
the system DC return.
Output Reference: Maximum current in on-state: 100 mA (max. current from J14-11)
Maximum voltage in off-state: 30 V

2.6.3 Cable Requirements

The following cables (not supplied with the generator) are the minimum specification requirements to maintain
compliance with the electromagnetic compatibility. No cable shall exceed 30.4 m (100 ft) unless in situ tests are
performed to validate EMC compliance.

1) Low voltage I/O signals: (Generic type) Jacket insulated over 100% foil shield with ground drain conductor,
multi-conductors type, typical 20 AWG stranded, voltage rated for the purpose.

2) X-ray tube rotor supply cable: (Generic type) Jacket insulated over 100%, foil shield with ground drain
conductor, multi-conductors type. 14 AWG minimum stranded, rated 600 volts minimum.

3) Phototube & photodiode cables: RG59 type, 90 % shielded minimum recommended, internal conductor
stranded, BNC connector terminated.

4) X ray tube high voltage cables: Full braid shielded 75 kV type (between 10 to 30 meters long).
Types ll or lll as per NEMA Standard XR 7-1979 (R 1984, 1990), with locking screw available at both
extremities of the cable.

5) Mains line and protective ground cables: Unshielded type, length and wire gauge must be in accordance with
applicable electrical code and local regulations.

Document Number 10000.000.EPS ETA.G0 26/30


EPS ETA High-Voltage Generator

2.7 Environmental Specification

Table 11- Environmental Data


Factor Operation Stock & Transport
Temperature in °Celsius +10 to + 40 -25 to 70
Temperature in °Celsius / hour N/A N/A
Humidity in % (non-condensing) 30 to 75% 10 to 95%
Vibrations / Shock range in Hz 10-55 10-55
Vibrations / Shock amplitude in mm 0.153 0.153
Vibrations / Shock acceleration in G 2G / 30 minutes 2G / 30 minutes
Shock acceleration in G N/A 10
Air pressure in hPa 700 to 1060 700 to 1060
Altitude maximum in m 3000 3000
Miscellaneous Comment
Acoustic noise level : < 52 dB @ 1m
Air cooling : 200 BTU/hr in idle mode
EMC : Refer to Technical Manual, section 1.4
Ambient illuminance level : 100 lux to 1500 lux

Gas Mixture This equipment is not suitable for use in the presence of a flammable anesthetic mixture
with air or with oxygen or nitrous oxide.

PRODUCT DISPOSAL

At the end of its usable lifetime, no particular action is necessary for the disposal of the
product except those locally in force at the installation site.

When the EPS ETA generator is fit with the 2-tube option, it includes a tank containing
approximately 30 liters of dielectric oil. To dispose of this unit at the end of its service
lifetime, make sure it is done in a way that respects the local environmental regulations
in force.

Document Number 10000.000.EPS ETA.G0 27/30


EPS ETA High-Voltage Generator

2.8 Mechanical Data

Dimension in mm (inches) Width Height Length Weight (*)


Generator (standalone) 441 (17 3/8) 492 (19 3/8) 578 (22 3/4) 64-75 kg (140-165 lb)
” .. with cabinet 472 (18 1/2) 806 (32) 776 (30 1/2) 79-90 kg (175-200 lb)
” .. with 2-Tube option & cabinet 472 (18 1/2) 1268 (50) 768 (30 1/4) 113-124 kg (250-275 lb)
(*) Approximately, as a function of power configuration.
Figure 17 – Epsilon Dimensions and Center of Gravity (C.G.).

Document Number 10000.000.EPS ETA.G0 28/30


EPS ETA High-Voltage Generator

Table 12- Mechanical Data


Dimensions (mm)
Crate / Box Weight (kg)
Width Height Length
Standalone in carton crate 600 1100 895 74 -110*
Standalone 441 492 578 64 -75*
Standalone with cabinet 472 812 768 79 - 90*
With 2-Tube option & cabinet 472 1268 768 113 - 124*

(*) Approximately, as a function of power configuration and options.

Front view Side view

Cabinet dimensions in mm (inches) Weight: Approximately 33 lb (15kg)

Figure 18 – Cabinet Dimensions.

Document Number 10000.000.EPS ETA.G0 29/30


EPS ETA High-Voltage Generator

Figure 19 –
Operator Console Dimensions.

3.0 COMPLIANCE INFORMATION

The EPS ETA High-Voltage Generator complies with the following standards and regulations:

Table 13- Regulation and Standards


Market Type Standard

Canada Safety Certified to CAN/CSA-C22.2 NO. 60601-1:2014, IEC 60601-2-54: 2009+ A1: 2015 &
IEC 60601-1-3: 2008+A1: 2013

USA Safety Conforms to AAMI ES60601-1: 2005+A1: 2012, IEC 60601-2-54: 2009+ A1: 2015 &
IEC 60601-1-3: 2008+A1: 2013

Health This product complies with DHHS radiation performances of 21 CFR, Sub-chapter J in
effect at date of manufacturing.

Europe EN 60601-1: 2006+A12: 2014, EN 60601-2-54: 2009+A1: 2015 & EN 60601-1-3: 2008 +A1: 2016

International IEC 60601-1: 2005+A1: 2012, IEC 60601-2-54: 2009+A1: 2015 & IEC 60601-1-3: 2008 +A1: 2013

Important Notice
• Conformity is based on the equipment configured and interconnected as described in the present Technical
Manual. Changes or modifications to this equipment not expressly approved by EMD Technologies Incorporated
could void its conformity to applicable standards.
• Conformity to EN/IEC 60601-2-54 and EN/IEC 60601-1-3 shall be validated when the generator is integrated
within a complete Medical Electrical System.
End of document

Document Number 10000.000.EPS ETA.G0 30/30

You might also like