Engineer’s Manual
V09.98eng 1
OPERATING INSTRUCTIONS FOR CONTROLTRONIK
A1o Power on
ADDITIONAL FUNCTIONS
B Display panel
The above display will give all operating, warning and fault information during operation.
V09.98eng 2
CONTROL MENU’S
DANGER
Incorrect setting of the operating values can cause operational problems with the
compressor.
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 01 ( menu 01 )
* Applies to Genesis only, values shown but not functional on Smart range
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 02 ( menu 02 )
The above procedure will re – set all service intervals that had reached zero hours.
V09.98eng 3
From Version E09 the following procedure should be used.
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 02 ( menu 02 )
Use K4 to change the value to the default time (set in menu 12) then use K1 to scroll to the next
item to be re-set and repeat the above procedure, carry out this for each expired service item.
Please note! The maintenance periods can now be re-set when the timer is within 100 hours of
zero.
DANGER
During operation in auto restart mode the compressor can start up automatically at any
time !
Prior to accessing this menu, Menu 35 must be entered to unlock the access.
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 03 ( menu 03 )then press buttons K2
and K3 together.
DANGER
During operation in Remote control mode the compressor can start up automatically at
any time !
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 05 ( menu 05 ) then press buttons K2
and K3 together.
V09.98eng 4
Remote control of Motor or LoAd
DANGER
Incorrect setting of the limit values can cause severe damage to the compressor and
could invalidate the warranty !
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 10 (menu 10) then press buttons K2
and K3 together.
V09.98eng 5
K1 x 9, Blow down time 0 – 240 seconds
Ensure all TP values are checked before putting machine back into service.
DANGER
Adjustment of the digital inputs from their original settings could prevent the
compressor from starting !
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 11 ( menu 11) Then press buttons K2
and K3 together.
Input NR 2 = N/C
K1 x 1, Input NR 3 = N/C
K1 x 2, Input NR 4 = N/C
K1 x 3, Input NR 5 = N/O
K1 x 4, Input NR 6 = N/O
K1 x 5, Input NR 7 = N/O
K1 x 6, Input NR 8 = N/O
Input NR 1 can not be changed as this is always N/C and assigned to Emergency Stop.
V09.98eng 6
MENU 12 Maintenance Interval Defaults (NEW MENU FROM E09 ONLY)
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 05 ( menu 05 ) then press buttons K2
and K3 together.
The following maintenance intervals can be programmed in this menu, these values will take
effect after the factory stored value has elapsed, ie the value programmed for the Oil filter
change will take effect after the initial 100 hr interval programmed by the factory.
When setting intervals ensure new value has stopped “flashing” before moving to next item to
ensure the new value is stored.
Prior to accessing this menu, Menu 35 must be entered to unlock the access.
Access to the menu is gained by holding buttons K4 and K5 together until all display LED’s
illuminate and flash. Use button K4 to change display to 20 ( menu 20 )then press buttons K2
and K3 together.
Display will test all LED’s and “8” will cycle through display.
V09.98eng 7
MENU 20 Continued
K5 x 14, Fan
DANGER
Use of the factory codes to change original settings could cause severe damage to the
compressor and may invalidate the warranty!
Access to this menu is by holding buttons K4 and K5 together until all display LED’s illuminate
and flash. Use button K4 to change display to 35 ( menu 35 ) then press buttons K2 and K3
together.
This will “ unlock “ the access to ABAC factory settings.
V09.98eng 8
FAULT DISPLAYS
All faults should be rectified and then cleared with the re-set button K6
V09.98eng 9
OPERATION
During normal operation the compressor shows the operating status and the current receiver
pressure.
When first switching on the display will light and scroll through its start procedure. If A1c
illuminates then the power should be switched off at the supply and two incoming phases
should be reversed, once the power is restored press button K6 to re-set.
Press button K2 to start the compressor, the display will show A 0.0 or C 0.0 depending on
whether automatic or continuous run has been chosen ( see menu 1 ). When the intake valve
solenoid is energised to load the compressor an LED will illuminate next to the A or C, the 0.0
will rise with the pressure in the tank until the compressor off-loads at its maximum pressure
( see menu 1 ) If after 5 minutes there is no requirement for air then the compressor will shut
down in “ auto shutdown “ and will automatically re – start upon a requirement for air.
Whilst the power is on to the compressor button K1 can be used to scroll the following
information
K1 x 1, Discharge air / oil temperature (permanent display with twin display unit)
K1 x 3, Loaded hours
To stop the compressor press button K3 and the compressor will run for approximately 30
seconds depending on setting ( see menu 10 )
The emergency stop button SB2 will stop the compressor immediately.
The maintenance warning lights are pre – programmed and not adjustable, the following values
are programmed and after service should be re – set via menu 2.
ACTION 100 HRS 1000 HRS 2000 HRS 3000 HRS 4000 HRS
AIR FILTER # # # # #
OIL FILTER # # # # #
SEPARATOR # # # #
OIL CHANGE # # #
V09.98eng 10