Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Health Devices IPM System

INSPECTION AND PREVENTIVE MAINTENANCE


__________________________________________________________________________________________

Procedure No. 475-20010301 (Acceptance)


__________________________________________________________________________________________

Mobile High-Efficiency-Filter Air Cleaners


Used For:
Air Cleaners, High-Efficiency Filter, Mobile [18-113]

______________________________________________________________________________________

Also Called: High-efficiency particulate-air (HEPA) cleaners, air filtration units, portable room-air HEPA
recirculation units

Commonly Used In: Patient isolation rooms, waiting areas, respiratory treatment rooms, autopsy
rooms

Risk Level: High

Type Interval Time Required

Major 12 months _____ hours


Minor 2 months _____ hours

Notes:
The minor interval can be adjusted based on the need for prefilter replacement; these filters are
typically changed every 1 to 3 months. Staff members other than service technicians can usually
perform minor inspections and change prefilters.
_______________________________________________________________________________________

Overview
such as TB droplet nuclei. Some units include
Mobile high-efficiency-filter air cleaners are multiple prefilters, charcoal filters to remove
movable devices intended to remove odors, and/or germicidal ultraviolet lamps (i.e., for
Mycobacterium tuberculosis droplet nuclei from ultraviolet germicidal irradiation [UVGI]) intended
room air and thereby reduce the risk of to supplement the HEPA filtration.
tuberculosis (TB) transmission. These units also
reduce the amount of dust, pollen, and other Some HEPA cleaners can be permanently wall or
particles in the air they filter. A mobile air filtration ceiling mounted, and some can have room exhaust
unit uses a fan or blower to move air into its connections. Many of the procedures described
housing and through its filters and then to herein can be applied to these units.
recirculate it throughout the room. The filter
system typically includes a low-efficiency prefilter The U.S. Centers for Disease Control and
to trap gross particulates and a high-efficiency Prevention (CDC) recommends at least 12 air
particulate air (HEPA) filter to trap fine particles, changes per hour (ACH) to significantly reduce the

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 1 of 6
Procedure No. 475-20010301 Mobile High-Efficiency-Filter Air Cleaners (Acceptance)

risk of transmitting TB. The volume of air Recording the minor inspections and indicating the
circulated by the mobile air filtration unit must be next date for filter replacement on a label or
in proper proportion to the room volume to inspection sticker attached to the unit will facilitate
effectively supplement existing ACH provided by routine filter replacement.
the room's heating, ventilating, and air-
conditioning (HVAC) system or to produce at least
the recommended 12 ACH.
Citations
(from Health Devices if not otherwise noted)
In addition, a mobile air filtration unit must be
Mobile high-efficiency-filter air cleaners
positioned in a room so as to ensure that the room
[Evaluation], 1995 Oct;24:370-418.
air is thoroughly mixed. This can usually be
Mobile high-efficiency-filter air cleaners
accomplished by positioning the unit so that the
[Evaluation update], 1997 Jun;26:233+.
filtered air is moved the greatest distance possible
in the room before being blocked or deflected by
walls or furniture or disturbed by other airflows. Test Apparatus, Supplies,
The unit should also be positioned to prevent air
from being directed toward exhaust ducts and
Parts
areas occupied by healthcare workers.
 Leakage current meter or electrical safety
As the filters become loaded (i.e., dirty), the flow analyzer
resistance increases, diminishing the amount of air
moved through the unit and, commensurately, the  Ground resistance ohmmeter
amount of protection offered (i.e., the reduction of
contamination concentration). The filters must be  Airflow-measuring instrument (e.g., flow hood,
periodically replaced, typically every two months anemometer, pitot tube) and appropriate
for prefilters and every two years for HEPA filters, ductwork
depending on the filters' time in use and the
cleanliness of the room air.  Differential pressure gauge capable of
measuring 2 inches of water in 0.01-inch
Most mobile air filtration units have either a filter- increments
quality indicator or manufacturer-designated test
to determine when the filters should be changed.  Particle counter capable of measuring 0.3 μm
The most widely used indicator is a differential particles (optional; required for CDC testing)
pressure gauge that measures the pressure drop
 NIOSH-approved respirators
across the filters. This gauge is typically a relative
indicator; the pressure reading when the filters are
 Gloves
clean must be known to determine the state of the
filters at any given time. Depending on the mobile
 Eye protection (from UVGI lamps)
air filtration unit, the gauge may provide a
measure of the condition of the HEPA filter and the
 Leak test solution
prefilter, or the condition of the HEPA filter alone.
Some units carry a label that describes the use of
the differential pressure gauge and provides a
chart for recording pressure measurements. In Special Precautions
addition, some use lights to signal the filter
condition based on pressure drop and/or an hour Because air filtration units can harbor potentially
meter to indicate time in use, a less reliable infectious organisms, technicians should follow
method of gauging filter condition. universal precautions for infection control (e.g.,
wearing respirators approved by the National
Because the units are used in patient rooms, filter Institute for Occupational Safety and Health
inspection and replacement should be performed [NIOSH], wearing gloves), especially during
by nursing or clinical engineering staff, who should prefilter or HEPA filter replacement or any other
also ensure that the unit is properly positioned in internal work on these units. Rubbing or shaking
the room. In either case, responsibility for testing filters can aerosolize trapped dust and thereby
and replacement must be clearly established. If no create an infection risk. Some units incorporate
simple filter-condition test is available, filters special features or designs to contain the filter and
should be replaced at regular intervals, according minimize the potential for spread of
to the manufacturer's recommendations or as contamination. Used filters should be treated as
determined by the procedure outlined herein. infectious waste. Most filters are disposable;

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 2 of 6
Procedure No. 475-20010301 Mobile High-Efficiency-Filter Air Cleaners (Acceptance)

reusable filters can be disinfected with a soaking Mount/Fasteners. If the air filtration unit is
spray of phenolic disinfectant or undiluted bleach. mounted on a stand or cart, examine the condition
(For more details on infection control, see IPM of the mount. Ensure that the assembly and
Safety.) weight distribution is stable and that the unit will
not tip over when pushed or when a caster is
The internal surfaces of the mobile air filtration jammed on an obstacle (e.g., line cord, threshold),
unit should be disinfected before internal cleaning as may occur during transport.
or maintenance. Refer to the manufacturer's
recommendations for unit disinfection procedures;
Casters/Brakes. Verify that the correct
most recommend gas disinfection using
casters have been supplied with the air filtration
paraformaldehyde vapors. This type of disinfection
unit (e.g., size, correct swivel). (ECRI recommends
is best done outdoors.
5 in [12.7 cm] diameter casters for mobile units to
reduce shock to the unit and to minimize the effort
If the mobile air filtration unit contains UVGI
required to roll the unit across elevator thresholds
lamps, eye protection may be needed for some
and other uneven surfaces.) Verify caster and
procedures. Otherwise, ensure that the lamps are
brake operation, if the unit is so equipped.
not activated whenever they can cause personnel
exposure.
AC Plug. A solidly constructed, good quality
plug with adequate strain relief is acceptable, but
the use of a Hospital Grade plug (identifiable by a
Procedure green dot and/or labeling) will eliminate
guesswork and ensure a plug of acceptable
Before beginning an inspection, carefully read this construction quality. Right-angle plugs are
procedure and the manufacturer's instruction and unacceptable for devices that are moved
service manuals. Be sure that you understand how frequently. A good quality two-prong plug is
to operate the equipment, the significance of each acceptable for double-insulated devices. Replace
control and indicator, and the alarm capabilities. the plug or have the supplier replace it if it is not
Also review special inspection and preventive Hospital Grade or otherwise suitable. Hospital
maintenance procedures or frequencies Grade molded plugs are acceptable.
recommended by the manufacturer.
Examine the AC power plug for damage. Attempt
to wiggle the blades to determine if they are
Qualitative Tasks secure. Shake nonmolded plugs and listen for
rattles that could indicate loose screws.
Chassis/Housing. Check for shipping
damage; report any damage to the manufacturer,
Line Cord. Ensure that the line cord is long
shipper, or service organization, and arrange for enough for the unit's intended application; an
repair or replacement. extension cord should not be required. (A length of
10 ft [3 m] is suitable for most applications.)
Check that the unit is suitably constructed to
withstand normal hospital use and abuse. For The cord should be of suitable quality and current-
instance, a unit with venting on the top of the carrying capacity. Hard Service (SO, ST, or STO),
housing or poorly protected or sealed controls and Junior Hard Service (SJO, SJT, or SJTO), or an
indicators may be prone to fluid entry. (Such equivalent-quality cord should be used.
design deficiencies should usually be recognized
during prepurchase evaluation. However, if any are Verify that the air filtration unit has adequate
evident, discuss corrective action with the protection against power loss (e.g., from
manufacturer. If not correctable, warn users or accidental disconnection of a detachable power
take other preventive measures.) cord or disconnection of the power cord from the
wall). Equipment having a detachable power cord
Examine the exterior of the unit, including louvers should also have adequate capture devices, cleats,
or grilles, for cleanliness and general physical or channels to hold the cord in place. If these are
condition. Ensure that plastic housings are intact, absent, request that the supplier provide suitable
that all assembly hardware (e.g., screws, means of securing the cord. Verify that the unit
fasteners) is present and tight. has adequate alarms or indicators for line-power
loss.

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 3 of 6
Procedure No. 475-20010301 Mobile High-Efficiency-Filter Air Cleaners (Acceptance)

Strain Reliefs. Examine the strain reliefs at Fan/Blower. Check the physical condition and
both ends of the line cord. Be sure that they hold proper operation of the fan/blower. Check
the cord securely. mechanical alignment and proper adjustment of
any pulleys, gears, belts, chains, etc.
Circuit Breaker/Fuse. If the air filtration
unit has a switch-type circuit breaker, check that it Indicators/Displays. Confirm proper
moves freely. If the air filtration unit is protected operation of all lights, indicators, meters, filter-
by an external fuse, verify that the fuse type is quality gauges, and visual displays on the unit.
labeled and that all fuses and spares are the
proper current rating and type. If the value and Ensure that the filter-quality gauge is reading
type are not labeled, check the manual for the properly by operating the unit and then blocking
proper current rating and type and permanently the inlet or outlet. The indicator should change as
mark this information on the unit housing near the described in the manufacturer's literature. When
fuse holder. the unit is unplugged, the indicator should return
to zero or its lower stop.
Verify that accessory outlets have independent
overcurrent protection (fuse or circuit breaker) so Alarms/Interlocks. Verify that configurable
that a short in a device plugged into the accessory alarm features are appropriately set and consistent
outlet or an accessory overload will not disable the among all units. It should not be possible for
air filtration unit. If this is not available, then critical alarms to be turned off, silenced, or
consider labeling the air filtration unit to clearly defeated without adequate warning to the operator
indicate where the unit's fuse or circuit breaker is or automatic alarm reactivation after a short
located, and/or install a fused Hospital Grade (or delay. Such deficiencies should usually be
similar quality) plug on any commonly used recognized during prepurchase evaluation.
accessories that are not already provided with However, if any are found, review the justification
suitable overcurrent protection. for purchasing the air filtration unit and discuss
corrective action with the manufacturer. (Alarm
Tubes/Hoses. Check the presence and features may be optional or programmable.) If no
condition of all hoses (including whether they are remedy is available, a user training program
attached to a differential pressure gauge). Be sure should be instituted to reduce the risk of incorrect
that they are not cracked, kinked, or dirty. use. A warning label on the air filtration unit or a
poster in the area of use may be appropriate.
Filters. Check the condition of all filters by
using the unit's filter-quality gauge or test feature Verify that alarms are loud, distinctive, and/or
or by making a visual inspection. Inspect the bright enough to be noticed in the environment in
sealing surface in the unit for smoothness and which the air filtration unit will normally be used. If
flatness to ensure that the HEPA filter gasket will a remote alarm-indicator is required, verify that it
seat properly without leaking. Some units require is available and functioning. Audible alarm-volume
silicone grease on the HEPA gasket to aid in controls should not allow the alarm to be turned
sealing the joint. The HEPA filter should be off or lowered to an indiscernible volume.
certified as HEPA quality. Ensure that clamps or
other fasteners used to hold the HEPA filter in the Induce alarm conditions to activate audible and
unit are tight and that the HEPA filter cannot move visual alarms. Check that all associated interlocks
in its mounting. or features function (e.g., the line power
disconnect alarm sounds when the unit is
unplugged). If the air filtration unit has an alarm-
Controls/Switches. Discuss appropriate
silence feature, check the method of reset (i.e.,
control settings with the department head and
manual or automatic) against the manufacturer's
users. If alarm capabilities are included, see the
specifications.
Acceptance test for Alarms.

Examine all controls and switches for physical Labeling. Ensure that a filter test label is
condition, secure mounting, and correct motion. If attached to the unit. Such labels are generally
a control has fixed-limit stops, check for proper available from the manufacturer and are used to
alignment, as well as positive stopping. Ensure record the filter-quality gauge readings, test dates,
that each control and switch performs its proper and/or hour meter readings of the mobile air
function. filtration unit for future maintenance. Consider
attaching to the unit a chart of the unit's airflows
versus room volume versus ACH; such charts are

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 4 of 6
Procedure No. 475-20010301 Mobile High-Efficiency-Filter Air Cleaners (Acceptance)

available from the manufacturer. Ensure that the the concentration of 0.3 μm particles in the room air. With
HEPA filter is certified as HEPA quality by the the mobile air filtration unit operating, measure the
presence of a label with records of, at least, the concentration of 0.3 μm particles in the clean airstream by
filter efficiency and airflow resistance. inserting the particle sampling probe well into the exhaust
duct of the cleaner to minimize the entrainment of
room air particles. The reduction in the number of
Battery. Determine the replacement interval for
particles should be at least 99.97%. If a particle
the alarm batteries (if present) and document the
counter is not available, it will be necessary to
interval(s) in an equipment control system or a
have testing performed by an outside agency.
hard copy file for the air filtration unit.

UVGI Lamps (if present). Confirm that


the lamps activate. Some units have visual Quantitative Tasks
indicators for lamp activation. If these are not
present, the lamps can be directly observed in Grounding Resistance. Using an
operation; be sure to use suitable eye protection. ohmmeter, electrical safety analyzer, or
multimeter with good resolution of fractional
Area of Use. Whenever a new unit is put into ohms, measure and record the resistance between
service, determine the volume of the room in the grounding pin of the power cord and exposed
which it will be used. Ensure that the unit's (unpainted and not anodized) metal on the
measured airflow (see the Airflow task) will chassis. Grounding resistance should not exceed
provide or supplement the room's HVAC to 0.5 . If the air filtration unit is double insulated,
produce at least 12 ACH. Record the fan/blower grounding resistance need not be measured; indicate "DI"
setting needed to produce this airflow. Determine instead of the ground resistance value.
the position of the cleaner in the room that will
produce the best mixing of the room air. Chassis Leakage Current. Note: Some
units (especially devices incorporating a
HEPA Seal. CDC recommends that a HEPA seal microprocessor, motor, or compressor) may be
test be performed (1) when the HEPA filter is new, damaged by switching polarity while the unit is on.
(2) whenever a HEPA filter is replaced or If you perform reverse polarity testing, turn off the
reinstalled or the air filtration unit is moved, and unit until the motor stops or for at least 10 sec
(3) every six months. ECRI believes that a slight before switching polarity. Although reversed
reduction in filtration efficiency of units that are polarity testing is not required, it may be advisable
being used only to recirculate air within the same on an air filtration unit of questionable quality.
room will not significantly increase the risk to
people in the area of use and questions the need With the polarity of the power line normal and the
for such frequent testing. However, units that equipment ground wire disconnected, measure
exhaust air to the outside of the room should be chassis leakage current with the air filtration unit
tested to verify that contaminated air is not operating in all normal modes, including on,
bypassing or being entrained downstream of the standby, and off. Record the maximum leakage
HEPA filter. current; it should not exceed 300 µA for patient-
care equipment used in a patient-care vicinity
If it is not necessary to comply with CDC (or [NFPA 99 7-5.1.3.5(a)]. ECRI does not recommend
similar) guidelines, the following alternative can be chassis leakage current tests of double-insulated
considered for units that do not exhaust any air devices.
outside the room. The integrity of the filter and its
mounting should be closely inspected. Examine The measurements should be made with all
each HEPA filter for any rips, tears, or dents in the accessories that are normally powered from the
filter medium and for gouges or tears in the same line cord connected and turned on. This
sealing gasket. Should such defects be found, applies to devices that are plugged into accessory
replace the filter. If practical, use a leak-checking outlets on the air filtration unit and to units that
fluid with the unit operating to detect leaks around are plugged into a multiple-outlet strip so that the
the HEPA filter gasket. (Leak testing cannot be devices are grounded through a single line or
performed on units on which the filter seal is not extension cord.
completely accessible.)
Leakage current must be measured with the air
If CDC testing is required, ensure that the HEPA filtration unit powered by a conventional
filter is properly secured and sealed in the mobile (grounded) power system, even if it is normally
air filtration unit. Using a particle counter, measure used in an area with isolated power. If the air

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 5 of 6
Procedure No. 475-20010301 Mobile High-Efficiency-Filter Air Cleaners (Acceptance)

filtration unit has a special plug (e.g., explosion


proof), a corresponding adapter is required.

Though confirmation of grounding integrity


provides reasonable assurance of safety for
devices with permanent redundant grounding,
NFPA 99 calls for measurement of chassis leakage
current with the redundant ground intact [NFPA 99
7-5.1.3.5]. Where practical, verify that these
devices meet appropriate chassis leakage current
requirements before installation or connection to
ground during acceptance testing.

Be alert for leakage current of the air filtration unit


in the off mode that is greater than about 30 µA
and is greater than or equal to the leakage current
in the on mode. Although this may be normal and
proper for the unit, it may indicate that the on/off
switch is incorrectly wired in the neutral (instead
of the hot) line. Incorrect switch wiring poses a
risk to service personnel who believe that the
power is disconnected when the switch is off.
Check the wiring, or contact the manufacturer.

Airflow. (Note: If the manufacturer provides


unit-specific airflow measurements, this task can
be waived.) Using a flow hood, anemometer, pitot
tube, or other airflow measuring device, determine
the actual airflow produced by a representative
unit at high, medium and/or operating speeds.
Airflow measurement can be difficult to perform
accurately; carefully follow the instrument's
instructions for use. To reduce air turbulence and
allow accurate readings, measure airflow within or
exhausting from a long (at least four times the
size of the exhaust opening), straight duct that has
a large cross-sectional area and that is connected
to the unit's inlet or exhaust. Airflows should be
80% of the manufacturer-specified airflows.

Before Returning to Use


Return controls to their preinspection or normal
pre-use settings.

Confirm that the unit is positioned for the most


effective air cleaning of the room. The
manufacturer's literature should provide guidance
in this matter. In general, the unit should be
positioned so that the filtered air is moved the
farthest distance possible in the room before being
blocked or deflected by walls or furniture or
disturbed by other airflows. The unit should also
be positioned to prevent air from being directed
toward HVAC exhaust ducts and areas occupied by
healthcare workers.

Health Devices Inspection and Preventive Maintenance System 2001 ECRI. All Rights Reserved.
Page 6 of 6

You might also like