Professional Documents
Culture Documents
INV-4835E Datasheet A PDF
INV-4835E Datasheet A PDF
Contents
Description Page
DC Input ......................................................................... 2
AC Input ......................................................................... 2
AC Output ...................................................................... 2
Inverter Default Configuration Values ............................ 3
Inverter Settings with MC2000 Controller ..................... 3
Environmental Requirements ........................................ 3
Mechanical ..................................................................... 3
User Interface ................................................................ 3
Compliances .................................................................. 3
Certifications .................................................................. 3
Technical Data Eaton Telecom Inverter Module INV-
Issue A June 2010
4835E
DC Input
Nominal voltage 48V dc
Operating range: 40 - 60V dc
Isolation AC-DC 4242V dc / 1min
Inrush current < 2*Irated
Isolation DC-enclosure 707Vdc (Varistors and filter capacitor removed) / 1min
Input protection Reverse Polarity Protection
Psophometric noise voltage 1.0mV ITU-T O.41 (16.66 - 6000Hz)
Reflected Psophometric noise current < 1% to YD / T 777-2006
Reflected relative wideband current noise < 10% (0-2Mhz) to YD / T 777 - 2006
Wide Band Noise < 1.0mV psof (25Hz - 5kHz)
< 20mV rms (25Hz - 20kHz)
Peak to peak noise 150mV up to 100MHz
Under voltage warning threshold 45V dc
Under voltage shutdown threshold 40V dc
Over voltage warning threshold 58V dc
Over voltage shutdown threshold 60V dc
AC Input
Nominal input voltage 208/220/230/240V ac
Voltage range 185-265V ac
Frequency 50/60Hz
Synchronization range 47.5 - 52.5Hz; 57 - 63Hz
Maximum input current 17A
Power factor 0.97
AC Output
Power Capacity 3500VA / 2800W
Waveform Pure sine wave
Power factor 0.8
Nominal output voltage 208/220/230/240V ac, selectable
Voltage regulation Max ±2%
Nominal current 16.8 / 15.9 / 15.2 / 14.6A
Output frequency 50/60Hz, manually, field selectable
Frequency variation Max ±0.5%
Crest factor 3:1
THD <3% for linear load, <5% for non-linear load
Capacitive/inductive load -0.8 to +0.8 without exceeding permissible distortion for
resistive load
Efficiency 94% AC Input
90% DC Input
Current limitation Electronic current limitation at overloads and short circuits.
Isolation AC-DC (Pri-Sec) 4242V dc / 1min
Isolation AC-enclosure (Pri-Gnd) 2121V dc / 1min
Surge protection EN61000-4-5.
Telcordia GR-1089 Core ANSI C62.41-IEEE STD 587-1980
Dynamic response <±10%, according to IEC 62040-3 class 1
Over load protection 125% >20s, 150% >10s,
Permanent overload capacity 120% permanent overload capacity @ 30°C
Load sharing < 5 %, at 50-100% load with/without Controller;
Transfer time 0s
Environmental Requirements
Operating temperature range -20 to 60°C (-4 to 158°F)
-20 to 50 °C (-4 to 122°F), full performance
Storage temperature -40 to 85°C (-40 to 185°F)
Operating humidity 90% Relative Humidity (non condensing)
Operating Attitude 1500m
Audible noise 55dB ETS 300 753, class 3.1
Mechanical
Dimension (D, W, H): 360mm x 217mm x 88mm (14.1 in. x 8.5 in. x 3.5 in.)
Weight: 6.75kg (14.85lb)
Cooling Forced air cooling
User Interface
LCD display 3-inch backlit LCD screen with 4 lines by 16 characters
LED Indicator 3, Green, Yellow and Red for normal, warning and fault
Keypad 4 key - Esc, Enter, Up, down
Compliances
Safety: Comply with EN 60950-1/ UL 60950-1
EMC EN300 386:2001. Class B compliance
Certifications
Europe CE-mark
© Eaton Corporation. All Rights Reserved. In the interests of continual product improvement all specifications are subject to change without notice. Performance ratings are valid with all other
variables at Nominal. Specifications guaranteed over rated operating range. Eaton, Matrix, Powerware, Intergy, CellSure, SiteSure, DCTools and PowerManager are trade names, trademarks,
and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other marks are the property of their respective owners.