Charoenchai Transformer Co.,Ltd.

Transformer Specification
Project : TR Code No. : 7932AS

Transformer Technical Data


Type of Transformer - Dry Type Cast Resin
Standard - IEC 60076-11
Number of Phase - 3
Power Rating kVA. 2000/2800
Cooling Method - AN/AF
High Voltage Side kV. 22
: HV Winding - Aluminium
Material
: LV Winding - Aluminium Foil
: Type - Off-Load
Tapping
: Percentage of Tapping % ± 2 x 2.5%
Low Voltage Side V. 400/230
Frequency Hz. 50
Vector Group Symbol - Dyn11
No Load Loss W. 4500
Load Loss At 75 °C W. 17000/33320
Total Losses At 75 °C W. 21500/37820
Impedance Voltage At 75 °C % 6/8.4
Ambient Temperature °C 40
Temperature Rise of Winding °C 100
Winding Insulation - Class F
Noise Level dB(A) 64
Protection Class Enclosure - IP 21
Engineering Division Document No. : SP 7932AS
Prepared By : Dated 19/01/2019 Issue No. : 8 Rev. No. : -
Approved By : Dated 19/01/2019 Dated 19/01/2019
Page 1/3
DOCUMENT No. : SP 7932AS
ISSUE No. : 8 REVISION No. : -
DATE : 19/01/2019

Charoenchai Transformer Co.,Ltd.


Transformer Specification
Project : TR Code No. : 7932AS

Transformer Technical Data


: 25% of Power Rating % 98.90
Efficiency : 50% of Power Rating % 99.13
At P.F. = 1 : 75% of Power Rating % 99.07
: 100% of Power Ratiing % 98.94
Impulse Withstand : High Voltage Side kV. 125
Voltage (BIL) : Low Voltage Side kV. -
: High Voltage Side kV. 50
Applied Potential
: Low Voltage Side kV. 3
Partial Discharge pC. < 10
Routine Test : are Performed on Every Single Transformer Including
 Measurement of Winding Resistance
 Measurement of Voltage Ratio and Vector Group or Phase Displacement
 Measurement of Short-Circuit Voltage Impedance and Load Loss
 Measurement of No-Load Loss and No-Load Current
 Separate Source AC Withstand Voltage Test or Applied Voltage Test
 Induced Voltage Test
 Insulation Resistance Test
 Partial Discharge Measurement
Type Test : can be Performed on Request at Extra Cost

Lightning Impluse Test One Unit Only Total Unit


Temperature Rise Test One Unit Only Total Unit
Sound Level Measurement One Unit Only Total Unit

Page 2/3
DOCUMENT No. : SP 7932AS
ISSUE No. : 8 REVISION No. : -
DATE : 19/01/2019

Charoenchai Transformer Co.,Ltd.


Transformer Specification
Project : TR Code No. : 7932AS

Transformer Accessories
Drawing No. Reference
7932AS 3 PH 22 kV. 400/230 V. 50 Hz. 2000/2800 kVA
SA-2184305 NAMEPLATE IEC STD. (3 PH. 22 kV. AI/AI SGB CAST RESIN)
SA-2184308 NAMEPLATE CONNECTION DIAGRAM (3 PH. 22 kV. SGB CAST RESIN)
SA-2580600 ENCLOSURE IP21 FOR 2000 kVA. STD. LOSSES

ACCESSORIES :
 Thermal Sensing and Control Unit for Autometic Fans Operation Alarm and Tripping Signal for Power Cut-Off
 Thermometer Indicator
 AF Cooling System 5
 Enclosure IP 21
 Bi-Directional Wheels
 Lifting Eyes
 Earthing Terminal
 Name Plate
 Tap Changing With Reconnectable Links
 Standard HV & LV Terminals
 Control Box
 Lightning Arrester

Page 3/3